Violations at 245 Gravesend Neck Road

Brooklyn, NY 11223 · BBL 3-07123-0066 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

18 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 21, 2013

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    May 26, 1999

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    May 26, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active

ECB violations

The newest 50 of 73 ECB violations. The city keeps the complete history.

  • Class - 2

    Reissue ecb #35720933p. failure to maintain building in code-compliantmanner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at (1st fl)cafeteria emergency lights not

    Mar 12, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue ecb #35720935z. failure to maintain building in code-compliantmanner. noted: at basement electric meter rm with storage of multiple items boxes, ladders, electric supplies etc... remedy: comply with cod

    Mar 12, 2026 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at electrical room, illegal storage of misc. items containing card board boxes, ladders electrical supplies. remedy: remove illegal storage from ele

    Jul 10, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Exit door not self-closing. noted: at exitt 3, all doors and at exit 4, all 3 door not self-closing. remedy: repair/replace door.

    Jul 10, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at cafeteria 3 emergency exit lighting and at auditorium 3 light

    Jul 10, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: second floor hallway next to room 208 and 212, fourth floor next

    Jul 2, 2024 · Penalty $625

    Resolve
  • Class - 2

    Reissue35560621x (5/3/21) failure to maintain bldg in codecompliant manner:@auditorium (2fl) chairs in deteriorated condition such as delaminated,peeling,sprinklers,broken,loose,missing seat/back supports.in va

    May 10, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35560623j(5/3/21) exit door not selfclosing:@4fl smoke from notselfclosing properly@3fl exitf,e,4fl gym 3exit doors not selfclosing.replace/repair doors

    May 10, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not selfclosing properly@3fl exit e,f.2exit doors 4fl gym stairf exit11 1exit door not selfclosing properly@time of insp when tested.repair/replace door.

    May 3, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner illumination for exits,exit discharges&public corridors per bc1006.1;27-381.4fl gym 2place each place 3lights,2fl auditorium (right side of stage) 1place 2lights

    May 3, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue35495140r doi5.12.20 failure to maintain bldg in codecompliant manner.@2fl auditorium,chairs falling apart,wood has splinters of exposed,also some chairs missing back.repair &/or replace.

    May 3, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: observed on the 1st fl in the cafeteria,on the 2nd fl in the auditorium

    May 12, 2020 · Penalty $625

    Resolve
  • Class - 2

    Re-issue #35423157k exit door not self-closing. noted: on the second floor exit #13 outside of the auditorium the door is not closing properly. remedy: repair/replace door

    May 12, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35423158m failure to maintain bldg in code compliant manner. noted: at the 2nd fl auditorium chairs are falling apart,some are broken & some of the seats are missing. remedy: repair &/or replace.

    May 12, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.illumination fo exits,exit discharges & public corridors per bc 1006.1;27-381.noted:attransportables t-3,t-5&t-6,emergency lights are inoperative.rem:repair

    May 13, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at 2nd floor,room 217,bathroom wall tiles are loose and missing.rem;repair and/or replace.

    May 13, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at 2nd fl auditorium,chairs are falling apart,wood has splinters of exposed.alsosome of the chairs are missing the back rest.rem:repair and/or replace

    May 13, 2019

    Resolve
  • Class - 2

    Exit door not self closing.noted:at main entrance to the bld,2nd floorexit 13(right rear,outside of auditorium)single door,3rd floor,exit e not working properly due to defective hardware.rem:repair/replace door

    May 13, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at 3rd fl.classrooms 338,337,331,are missing door checks.rem:repair and/or replace.

    May 13, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.illumination forexits,exit discharges & public corridors per bc 1006.1;27-381.noted:atcafeteria,rear kitchen(137),2nd floor auditorium by main entrance,emer

    May 13, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at 1st fl @ exit a&b,spalling plaster due to water penetration. remedy: make necessary repairs.

    May 12, 2017

    Resolve
  • Class - 2

    Sec. 28-301.1 unlawful display of artwork in corridors greater than 20% per fdny 2008 code;fc 803.3.2. noted: artwork displaced in corridors throughout the bldg is greater than 20% allowed per code.

    May 12, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at electrical room,illegal storage of snow shovel,leaf racks,water bottles. remedy: comply w/notice of violation.

    May 12, 2017

    Resolve
  • Class - 2

    Facade water penertration.@ 1st fl electrical panel room,water from facade penetrates through walls.rem:waterproof are of facade.

    Jul 18, 2014

    Resolve
  • Class - 2

    Reissue ecb#35022779h auditorium doors.@ 2nd fl,auditorium doors racked preventing doors from closing properly.rem:repair/replace auditoriumdoors.

    Jul 18, 2014

    Resolve
  • Class - 1

    T-4 seveere damage to sub-flring & joist support at main entrance. t1 & 2 severe subflring damage at entrance door holes/sagging. remedy: make safe. replace flring.

    Jun 12, 2013

    Resolve
  • Class - 2

    Water penetration into rooms 433, around drains and in auditorium south side ceiling, exit 12 vestibule area. remedy: seal penetration.

    Jun 12, 2013

    Resolve
  • Class - 2

    Reissue 34953901l. defective doors.1st flr exit 13' vestibule door (auditorium doors).2nd flr stairs a,b,f. 3rd flr stairs a,b,f. 4th flr stairs a,b,f. basement electrical panel room door. remedy:repair/replace

    Jun 12, 2013

    Resolve
  • Class - 1

    Loose/falling mortar joints at north side above exit staircase e, affected area approx 120' long. remedy: provide shed inside yard along north side approx 120' under exit e.

    Jun 12, 2013

    Resolve
  • Class - 2

    Doors not closing at: 2nd floor stairs a,b & f 3rd floor stairs a,b & f 4th floor stairs a,b, & f basement electric panel room. remedy: repair &/or replace doors.

    Apr 17, 2012

    Resolve
  • Class - 2

    Unauthorized storage at electric room service room has storage of maintenace equipment rem: remove all items maintain service room storage free

    Sep 16, 2011

    Resolve
  • Class - 2

    Missing fire stop at custodial closets rooms 228 & 328 inside closet over door and back wall no fire stop to concealed spaces at conduit penetrations rem: provide fire stop seal all opening

    Sep 16, 2011

    Resolve
  • Class - 2

    Missing vision panels at 3fl ten room from classroom 303 to room 325 with no vision panels installed rem: provide code compliant vision panels

    Sep 16, 2011

    Resolve
  • Class - 2

    Racked doors the fire proof are racked to frame and not operating properly at 4th floor stairway b 3fl stairway a rem: repair doors to properly open and self close

    Sep 16, 2011

    Resolve
  • Class - 2

    Defective door at electric service room the fire proof door is not self closing w/ holes drilled in door exposing acm asbestos rem: replace door

    Sep 16, 2011

    Resolve
  • Class - 3

    Failure to maintain.observed:cracked wire glass stairwell panel 3fl stair 10/11.remedy:maintain building.

    May 25, 2010

    Resolve
  • Class - 2

    Failure to maintain egress clear and unobstructed.observed:perimeter aisles of auditorium used for storage of school furniture and rolling display/blackboards.remedy:remove obstruction,maintain clear egress.

    May 25, 2010

    Resolve
  • Class - 2

    Failure to maintain.observed:electric meter room #101 used for storageof gas powered and other snow removal equipment.remedy:discontinue illegal use,keep room clear.

    May 25, 2010

    Resolve
  • Class - 2

    Failure to maintain.observed:racked f.p.s.c. doors,won't properly close at auditorium by rm 212,exit doors interior by rm 127,stair d fls 243,exit 3 fl.remedy:maintain building.

    May 25, 2010

    Resolve
  • Class - 2

    Reissue 34792041x.failure to maintain observed:spalling plaster exterior wall rms 423,416a,412,403,221,217.rem:maintain building.

    May 25, 2010

    Resolve
  • Class - 2

    Failure to maintain.observed:f.p.s.c. doors between t 1&2,t3&4,t5&6 are racked, won't close.remedy:maintain building.

    May 25, 2010

    Resolve
  • Class - 2

    Hardware defective. 1- auditorium - exit 12 - closer not functional. 2- 1st flr exit 10/11 - closer not functional. 3- 4th flr double door buck (at the gym outside rm 435). loose and framing. remedy: repair

    Jun 18, 2009

    Resolve
  • Class - 2

    Reissue - 34504810m. spalling at head of window joist plaster in rooms: 416a, 412, 431 and 217. remedy: make necessary repairs.

    Jun 18, 2009

    Resolve
  • Hazardous

    Failure to maintain noted:stairway exit door @ stairway c 4th fl in disrepair need to be replaced. remedy:repair/replace door.

    May 16, 2007

    Resolve
  • Hazardous

    Failure to maintain.noted:lighting in all stairwells not @ proper illumintation low lighting dark all stairways. remedy:repair /replace lighting.

    May 16, 2007

    Resolve
  • Hazardous

    Failure to maintain interior. noted:interior wall @ 2nd fl principals office above main entrance was removed from exterior work & never replaced correctly. remedy:repair or replace wall.

    May 16, 2007

    Resolve
  • Hazardous

    Failure to maintain exterior wall. noted: entire exterior wall in needof repairs & pointing, mortar missing thru-out facade & ornamental pc thru-out.remedy:repair & ,maintain exterior walls.

    May 16, 2007

    Resolve
  • Hazardous

    Reissue # 34504812x: noted:water penetration from unknown source in basement next to vacuum pumps. remedy:make all repairs.

    May 16, 2007

    Resolve
  • Hazardous

    Reissue # 34504811y noted: there is water penetration @ room 431 from the roof. remedy:repair & maintain roof.

    May 16, 2007

    Resolve
  • Hazardous

    Reissue # 34504810m.noted: water penetration through the walls above windows @ rooms 416a, 412 & 423. remedy: repair and maintain exterior walls

    May 16, 2007

    Resolve