roofy

7601 19 Avenue

Brooklyn, NY 11214BBL 3-06239-0001Map

Owner of record: NYC Department Of Education

7601 19 Avenue is a school building built in 1936 in Brooklyn, 11214. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
21
ECB violations
66
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 21

  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2020)

    Oct 10, 2021

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2019

    Jun 29, 2020

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    May 6, 1999

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
Show 11 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - dismissed

ECB violations · 66

  • Class - 2

    Reissue ecb #35691654p. failure to maintain building in code-compliantmanner. noted: at(4th fl) classroom #410 with water damage to ceiling/wall cracks/spalling/staining plaster/paint. remedy: comply with code.

    Feb 10, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at(1t fl) gyms, cafeteria(2nd fl) auditorium emergency lights no

    Feb 10, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing. noted: at(1st fl) stairs d, f, and i doorsin disrepair/not closing when tested. remedy: repair/replace door.

    Feb 10, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at(2nd fl) auditorium stairs e and f doors in disrepair/racked. remedy: repairand/or replace.

    Feb 10, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: observed 5 lights in the auditorium, 5 lights above room 205, an

    Feb 21, 2025 · Penalty $1,250

    Active
  • Class - 2

    Re-issue #35676268z. failure to maintain building in code-compliant manner. noted: observed in classroom #410, there are muliple cracks and water penetration in the ceiling next to the window. remedy: repair an

    Feb 21, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35665738r. failure to maintain building in code-compliant manner. several classroom shower signs as water-penetration lead to damaged to ceiling and walls in room # 400b, 410 and 408a. remedy: repair a

    Feb 26, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35650853y.failure to maintain building in code compliant manner.note observed on 5th,4th,3rd,and 2nd floor classroom doors at various locations due to damaged or missing door closers are not self-closin

    Jan 24, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35650852m.failure to maintain building in code compliant manner.note observed on 4th floor classroom#408a,408b and 410 ceiling and walls showing signs of water penetration and damage to the plaster.reme

    Jan 24, 2023 · Penalty $1,562

    Active
  • Class - 2

    Missing shut off valve on oil tank. three shut off valves leaking in back of boiler #1

    May 2, 2022 · Penalty $625

    Active
Show 40 more ↓
  • Class - 2

    Reissue#35548386n.exit door not self-closing.noted observed at classrooms throughout the 5th,4th,3rd and 2nd floors.numerous classroom doorsare not self-closing at various locations of each floor mentioned.e.g.

    Apr 4, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35548388r.failure to maintain building in code compliant manner.noted observed at cellar gas meter room has several vertical cracks on the concrete walls approx 9ft long and water penetration occur when

    Apr 4, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35548387p.failure to maintain building in code compliant manner.noted observed at 4th floor classrooms 408a,408b,and 410 have the ceiling and walls along the windows showing signs of water penetrations

    Apr 4, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35495637m failure to maintain bldg in codecompliant manner.note:observed@cellar level gasmeterrm has vert crack on concrete wall approx9'l.also water penetration cause damage wall&fl.repair &/or replace.

    Mar 26, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35495641p failure to maintain bldg in codecompliatn manner.note:observed classrm doors not selfclosed@rm2fl 201,202,203,204,209,213,3flrms 302,303,4flrms 403,404,405,406,408&5fl 502,503,504,514.repair &/

    Mar 26, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35495639x failure to maintain bldg in codecompliant manner.note:observed spalling plaster 4fl rms408a,410,408b ceiling (illegible) water penetration.repair &/or replace.

    Mar 26, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code complaint manner illumination for exits exit discharges and public corridors per bc 1006.1.27-301;3rd floro across from rm 305,1st floor at gym above door d and g emergency

    May 15, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manenr use of prohibited hardware per bc 1008.18;27-371 (j) noted:observed kickstops installed throughout 5th floor at rooms 500,504b,508,509 provide legal hardwar

    May 15, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35433712j failure to maintain buidling in code compliant manner noted observed at cellar gas meter room vertcial crack on concrete wall approx 9 feet in length repair and or replace

    May 15, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compiant manner spalling plaster at 4th floors room 408a ,410 5th floor room 512 ceiling due to water penetration repair and or replace

    May 15, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner noted observed at gym exit 3 left door leaf does not open due to defective panic bar hardware repair and or replace

    May 15, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain buidling in code compliant manner noted observed classroom doors do not self closed at rooms 2nd floor 201,202,203,204,209,210,213, 3rd floor rms 302.303. 4th floor rooms 403.404.405.406,408

    May 15, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at rooms #302,305 & 504b,doors are not working properly. remedy: repair &/or replace.

    Jun 17, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at the cellar level,gas meter room has a vertical crack on the left wall approx 9'at the boiler rm,audition exits e & f & the 5th fl room 512 has fallin

    Jun 17, 2019

    Resolve
  • Class - 2

    Exit door not self closing. noted: at the multipurpose room stair d and exterior door exit 2, 2nd floor exit i by 213, 5th floor exit i by513 and exit d by 504a, exit doors are not working properly.rmdy: rep

    Jun 17, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner no fire stopping per bc 712.3; 27-345. noted: at electrical room 5"hole around conduit with no fire stopping.rmdy:provide/maintain fire stop

    May 1, 2017

    Resolve
  • Class - 2

    Unlawful display of artwork in corridor greater than 20% per fdny 2008code: fc 803.3.2 noted: artwork displayed in corridors throughout the school is greater than 20% allowed per code. rmdy: comply w/nov.

    May 1, 2017

    Resolve
  • Class - 2

    Corridor width. at 1st floor, security desk at entrance partially blocks exit door from cafeteria. remedy: move desk to not block exit door or get smaller desk.

    Apr 30, 2014

    Resolve
  • Class - 2

    Re-issue # 35023214p. defective door hardware. -at 5th fl stairway exit door d & c & g, door checks defective & disabled. -at 3rd fl stairway exit door g door check defective & disabled. -at 1st fl exit 6, door

    Apr 30, 2014

    Resolve
  • Class - 2

    Illegal door hardware. at auditorium, cafeteria & multi purpose room exit doors, brass door stops attached at the bottom of doors. remedy: remove door stops.

    Apr 30, 2014

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. noted: 1) rain water infiltrating through west foundation wall, creates considerable amount of water at bsmt. remedy: repair/replace.

    Jun 13, 2013

    Resolve
  • Class - 2

    Failure to maintain bldg in a code-compliant manner. noted: present venting system does not created enough fresh air. door left open to supplement fresh air. noted loc: gas meter room at cellar. remedy:

    Jun 13, 2013

    Resolve
  • Class - 2

    Exit door not self-closing. noted: the following doors are not self-closing -5th flr stwy & exit door. stwys d & b exit doors. stwy c door closers ddysfunctional. 3rd flr: stwy g r/h exit door stwy h exit.

    Jun 13, 2013

    Resolve
  • Class - 1

    50a, 51. federal fjfb lp steam boiler,199hp, sn; 50a-referenced boilermalfunctioned and failed in operation at apprx 9:15am on may 14,2013. "dry firing" occurrence noted.evidence of severe overheating on the fi

    May 14, 2013

    Resolve
  • Class - 2

    Storage of combustible decorations on 3rd flr draped across corridor obstructing exit signs. remedy: remove obstructions.

    May 18, 2011

    Resolve
  • Class - 2

    Failure to maintain adequate firestopping observed in electric meter rm several open penetrations of walls into adjoining spaces rem; maintain adequate fire stopping

    Apr 22, 2010

    Resolve
  • Class - 3

    Failure to maintain exterior walls or appurtenances in that water is being allowed to penetrate into bldg at the 4th & 5th flrs due to a defective roof,parapet & facade. area of water penetration is various thr

    Aug 1, 2008

    Resolve
  • Hazardous

    Failure to maintain. reissue #34509947x. no fire stop was provided in the wall in electrical room. remedy: replace/repair fire stop.

    Apr 19, 2007

    Resolve
  • Non-hazardous

    No fire stopping was provided in the wall in electrical room (basement) remedy: provide/maintain fire stopping.

    Mar 2, 2006

    Resolve
  • Non-hazardous

    1/2"-1.0" cracks in interior brick wall rm 605(vent room) remedy: repair/replace brick wall.

    Mar 2, 2006

    Resolve
  • Non-hazardous

    Water leaks in the ceilings from roof in rooms #512,502 all corridor, 510,513,506 (5 flr) remedy: repair roof.

    Mar 2, 2006

    Resolve
  • Non-hazardous

    Failure to maintain building - defect is :needs pointing throughout b uilding. remedy : maintain building - make all necessary repairs

    Mar 4, 2004

    Resolve
  • Non-hazardous

    Failure to provide panic hardware where required. location-cafeteria- occupancy 323. remedy: provide panic hardware.

    Jan 22, 2004

    Resolve
  • Non-hazardous

    Failure to maintain-note water damage to walls & ceilings & missing plaster. locations boys bathroom 5th floor girls bathroom 4th floor boiler room near exit 4 medical room-note- active leaks-cannot determine w

    Jan 22, 2004

    Resolve
  • Non-hazardous

    Failure to maintain noted missing broken loose tile in locations walls floors bys bathroom 5 floor girls bathroom 4 floor boys bathroom 3 floor cefeteria floor kitchen floorand wall and around door leading from

    Jan 7, 2003

    Resolve
  • Non-hazardous

    Failure to maintain noted water damage to walls and cieling missing plaster locations rm 401 above window rm 302 above window boys bathroom 5 floor girls bathroom 4 floor boiler room near exit 4 medical room re

    Jan 7, 2003

    Resolve
  • Non-hazardous

    Re issue failure to provide panic hardware where required ocation cateteria remedy: provide panick hardware.

    Jan 7, 2003

    Resolve
  • Hazardous

    Exit door obstructed inoperable noted exit doors in various location do not open. locations door #9 right side unable to open using substantial force exit doors #2,#3,#6,#7 are very tifht force used to open. re

    Jan 7, 2003

    Resolve
  • Non-hazardous

    Door not self closing noted at 3 floor door #5 not self closing hardware broken. remedy: repair door closure.

    Jan 7, 2003

    Resolve
  • Hazardous

    Failure to maintain defect is: class windows replace with non-rated plywood location: boiler room. remedy: make safe do repairs.

    Mar 5, 2002

    Resolve

Complaints

  • Unsanitary condition

    Garbage/recycling storage

    Jul 17, 2017 · Apt BLDG

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1936
Floors
5
Residential units
—
Building area
115,000 ft²
Lot area
72,000 ft²
Zoning
R5
Community board
311
Council district
43
Block / lot
6239 / 1
Assessed value
$9,718,200
Landmark / historic district
No

Questions about 7601 19 Avenue

Who owns 7601 19 Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 7601 19 Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 7601 19 Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 7601 19 Avenue built?

City records list 1936 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.