Violations at 6500 16 Avenue
Brooklyn, NY 11204 · BBL 3-05551-0018 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
The newest 50 of 51 DOB violations. The city keeps the complete history.
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Construction other optional
Structure rendered non-compliant. at time of inspection damage observed to have been sustained to roof and 4th floor classroom ceiling due to construction worker on scrapping machine where roof collapsed approximately 10'x10' area into classroom 403 along exposure 4 at 6500 16th avenue brooklyn ny, 11204.
Jul 5, 2019
Dob violation - dismissed - Construction other optional
Structure rendered non-compliant. at time of inspection damage observed to have been sustained to roof and 4th floor classroom ceiling due to construction worker on scrapping machine where roof collapsed approximately 10'x10' area into classroom 403 along exposure 4 at 6500 16th avenue brooklyn ny, 11204.
Jul 5, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 31, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 4, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 27, 2011
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 14, 2007
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Construction other optional
C-construction other optional
Sep 8, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Elevator elevatorrequired
3p7562
Aug 23, 2002
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Construction other optional
C-construction other optional
May 4, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 29, 1990
Dob violation - dismissed - Elevator elevatorrequired
(74)seal plunge
Nov 6, 1989
Dob violation - resolved
ECB violations
The newest 50 of 112 ECB violations. The city keeps the complete history.
- Class - 2
Exit door not self-closing. noeted: at(3rd fl), gym (1st fl) stair h and (basement) stair g doors in disrepair/not closing when tested. remedy: repair/replace doors.
Feb 9, 2026 · Penalty $625
Active - Class - 2
Reissue ecb #35691632l. failure to maintain building in code-compliantmanner. noted: at(basement) electric and gas meter rms with water penetration foundation walls. remedy: reair and/or replace.
Feb 9, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors lights not working when tested throughout various areas. remedy: repair/replace lighting.
Feb 9, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. illuminatio forexits, exit discharges and public corridor per bc 1006.1; 27-381. noted: observed on the fourth floor next to room #403, also at the entranc
Feb 19, 2025 · Penalty $1,250
Resolve - Class - 2
Re-issue #35676266p. failure to maintain building in code-compliant manner. noted: observed at basement level in the electrical and gas meter room, there is signs of water penetration throughout the foundation
Feb 19, 2025 · Penalty $3,125
Active - Class - 2
Reissue#35665134j failure to maintain building in code-compliant manner.at basement level gas meter room electrical room water penetration throughout foundation walls from outside.rem:repair and/or replace.
Feb 21, 2024 · Penalty $1,562
Resolve - Class - 2
Reissue#35665132l failure to maintain building in code-compliant manner.at cellar b & 1st floor elevator entry brass saddles to loose/unhinged created a tripping hazards.rem:repair/and or/replace.
Feb 21, 2024 · Penalty $1,562
Resolve - Class - 2
Re-issue #35636387p failure to maintain building in code compliant manner.note:observed at 1st fl & basement level elevator entry walkway unsecured metal saddles creating tripping hazard at both locations.remed
Jan 18, 2023 · Penalty $1,562
Resolve - Class - 2
Re-issue #35636386n failure to maintain building in code compliant manner.note:observed at basement level,gas meter & electrical meter rooms foundation walls damp & showing signs of water penetration from exter
Jan 18, 2023 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner.observed at toi at the entry door to the elevator on 1st floor and the basement,the metal saddles are loose,uneven and not secured properly.this creates a t
Mar 30, 2022 · Penalty $625
Resolve - Class - 2
Reissue#35553896j failure to maintain building in code compliant manner.observed at toi there are signs of water penetration thru foundationwalls at electric meter room and gas meter room.rem:repair leak.
Mar 30, 2022 · Penalty $1,562
Resolve - Class - 2
Exit door not self closing properly at basement level(stair'g'& exit 7)1 exit door in lunch room & auditorium(at exit 9)inside 1 exit door not self closing properly at the time of inspection. when tested.
Apr 14, 2021 · Penalty $625
Resolve - Class - 2
Reissue#35129273k date of issue 6-04-2015 failure to maintain bldg in code compliant manner. the following rooms have water damage either onwalls or ceilings,105,205,207,213,215,307,304,303,402 & both 3rd fl &
Apr 14, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35260618k date of issue 5-05-2017 failure to maintain bldg in code compliant manner. noted: water damage to ceiling & walls causing spalling plaster due to water penetration through roof. remedy: repair
Apr 14, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35289897l date of issue 8-24-2017 failure to maintain bldg in code compliant manner. at basement electrtical room spot of water penetration through wall & floor. remedy: repair &/or replace/maintain bld
Apr 14, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to comply w/the comm's order contained in summons/vio#39005079h issued on 07-05-19 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. work does not conform to approved construction documents &/or
Oct 5, 2019
Resolve - Class - 2
Failure to comply w/the comm's order contained in summons/vio#39005078x issued on 07-05-19 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. failure to safeguard all persons & property affected by constru
Oct 5, 2019
Resolve - Class - 2
Sidewalk shed/scaffolding does not meet code specifications at exposure 1 roof level netting on scaffolding defective and hanging at time of inspection conform to code specofcations
Sep 10, 2019 · Penalty $5,000
Resolve - Class - 1
Work does not conform to approved construction documents and or approved amendments. at time of inspection plans and engineers report indicate removal of roofing with skid steer loader model # ss16 cheetah with
Jul 5, 2019
Resolve - Class - 1
At time of inspection observed at roof where 2 workers 1 on machine and another chipping parapet wall with an additional machine in an approx: 10'x10' area overloading and penetrated into concrete slab in multi
Jul 5, 2019
Resolve - Class - 1
Failed to notify the department of an incident that resulted in a fatality or injury.a worker was injured when a concrete slab collapsed through into an empty classroom below.was taken by ambulance to the hospi
Jul 5, 2019
Resolve - Class - 2
Exit door not self-closing.noted:at the 1st floor,exit10,auditorium right rear exit9 and the 3rd floor gymnasium main entrance,exit doors are not working properly due to defective hardware.rem:repair/replace do
May 28, 2019
Resolve - Class - 2
Failure to maintain bld.in code compliant manner.noted:at the cafeteria kitchen,1st floor rooms 111,125a,126,2nd fl.,rm205,3rdfl.rms.307,317323a,327a and the 4thfl.,rm 403,doors are not working properly due to
May 28, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted at the gymnasium by stairway a,auditorium main entrance,emergency ligh
May 28, 2019
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. service equipment boiler at cellar level,boiler room,steam vacuum pump has exessive leak present. remedy: maintain boiler equipment.
Mar 21, 2018
Resolve - Class - 2
Sec. 411.1/411.1.3 appliances shall be connected to the piping system by rigid metallic pipe & fittings. where appliances are equipt w/casters or are subject to periodic movement,appliances shall be connected
Mar 21, 2018
Resolve - Class - 2
Reissue #35270743z (lower class) failing to maintain building in code-compliant manner. noted: at basement electrical room spot of water penetration through wall and floor. rem: maintain building in code-compli
Aug 24, 2017
Resolve - Class - 1
Reissue# 35216510k. failure to maintain bldg in code-compliant manner. noted @ time of insp observed @ basement level electric room water oenetration through wall, causing water damage, in danger of contact w/
Jun 8, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted at various doors an installed kick stops. remedy: provide legal hardware.
May 5, 2017 · Penalty $530
Resolve - Class - 2
Re-issue ecb#35216508l failure to maintain bldg in code compliant manner: noted at the 4th fl water penetration from the roof to the ceilingin various classrooms. also observed water penetration on walls in var
May 5, 2017
Resolve - Class - 2
Re-ssie ecb#35216509n failure to maintain bldg in code compliant manner: noted: at the basement gas meter room not operational fresh air vent. remedy: repair &/or replace.
May 5, 2017
Resolve - Class - 2
Re-issue ecb#35216510k failure to maintain bldg in code compliant manner: noted at the basement electrical room,water pentretion through wall. remedy: repair &/or replace.
May 5, 2017
Resolve - Class - 2
Reissue: ecb#35216511m exit door not self closing. noted at the bulkhead stair'f'& various classrooms w/old defective doors that are not closing. remedy: replace doors.
May 5, 2017
Resolve - Class - 2
Failure to maintain building in code compliant manner. noted: at exp #1, right side to main entrance, between the 1st floor and 2nd floor, defective brick facade with cracked masonry. rem: comply with code/repa
Oct 21, 2016
Resolve - Class - 2
Exit door not self closing. noted: at bulkhead staircase (f), rm #420,rm #215, 220, 115 and exit door next to exit (d), the doors have defective in the hinges and closers. rem: comply with code.
Oct 21, 2016
Resolve - Class - 1
Failure to maintain building in code compliant manner. noted: at basement level, electric room, penetration through wall with water damage in damage in danger of contact with electrical panel creating a hazardo
Oct 21, 2016
Resolve - Class - 2
Reissue nov# 35129269h failure to maintain building in code compliant manner. noted: at basement level, gas meter room, fresh air vent not operable. rem: comply with code.
Oct 21, 2016
Resolve - Class - 2
Reissue nov# 35129273k, 35024028x. failure to maintain building in code compliant manner. noted: water damage to ceiling and walls causing spalling plaster due to water penetration through roof or wall at the f
Oct 21, 2016
Resolve - Class - 2
Failure to maintain bldg walls and or appurtenances.water penetration from roof.water penetrating from roof above room 202 and stairway b.rem:comply with nov
Jun 4, 2015
Resolve - Class - 2
Failure to maintian bldg in code compliant manner.water penetration.re-issue ecb 35094464x.the following rooms have water damage either on walls or ceilings.105,205,207,213,215,307,304,303,402 & both 3rf fl & 4
Jun 4, 2015
Resolve - Class - 2
Failure to maintain bldg walls and appurtences facade water penetration:re-issue ecb 35094465h 105,205,207,213,215,303,304,307 and 3rd fl and 4th fl.dressing rooms.rem:comply with nov
Jun 4, 2015
Resolve - Class - 2
Failure to maintain bldg walls and or appurtenanes foundation walls.re-issue ecb 35094466j.water penetrating through foundation walls into oil tank room & staircase h conditions have gotten woese from previous
Jun 4, 2015
Resolve - Class - 2
Failure to maintan bldg walls or appurtenances.windows-reissue ecb 35094467l.window balances for approx.90% of window throughout bldg are not operable making it difficult to open or close windows.rem:comply wit
Jun 4, 2015
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.fresh air vent:re issue ecb 35094468n.at gas meter room,fresh air vent in operable.rem:comply with nov
Jun 4, 2015
Resolve - Class - 2
Gas meter room fresh air vent. fresh air vent in gas meter room not operable. remedy: repair fresh air vent in gas meter room.
May 5, 2014
Resolve - Class - 2
Windows. window balances on approx 90% of windows not operable making it difficult for windows to open or close properly. remedy: repair window balances or replace windows.
May 5, 2014
Resolve - Class - 2
Foundation wall. water penetrating from foundation wall into oil tank room & staircase h. remedy: provide foundation wall water proofing.
May 5, 2014
Resolve - Class - 2
Water penetration from facade. water penetrating from facade into following rooms: 105,205,207,213,215,303,304,307 & bookroom between 3rd & 4th floors. remedy: provide water proofing of facade.
May 5, 2014
Resolve - Class - 2
Re-issue # 35024028x. water penetration. the following rooms have water penetration from walls: 105,205,207,213,215,307,304,303, bookroom located between 3rd & 4th floors. at basement, water penetrating into st
May 5, 2014
Resolve - Class - 2
Re-issue # 35024029h. door checks. in basement cafeteria, 4 doors from kitchen have missing door checks. remedy: install door checks.
May 5, 2014
Resolve