4019 18 Avenue
Brooklyn, NY 11218BBL 3-05416-0048Map
Owner of record: NYC Department Of Education
4019 18 Avenue is a school building built in 1933 in Brooklyn, 11218. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 38
- ECB violations
- 61
- HPD complaints
- 1
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 38
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active
Show 28 more ↓
- Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Construction other optional
Hazardous
May 19, 1999
Dob violation - dismissed - Construction other optional
C-construction other optional
May 19, 1999
Dob violation - dismissed - Construction other optional
C-construction other optional
May 19, 1999
Dob violation - dismissed - Construction other optional
Hjazardous
May 19, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed - Plumbing none
P-plumbing none
May 11, 1988
Dob violation - dismissed
ECB violations · 61
- Class - 2
Re-issue #35720879n. altered/changed building occupied without a validcertificate or occupancy as per 28-118.3.1-28.118.3.2. noted: 3p0008480 for mini school issued feb-7 1996 was only good for 5 years. remedy:
Jan 29, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: crack onfacade around building areas on roof, broken bricks and mortar missingon stones letting water into building. re-issue #35720881m. remedy: re
Jan 29, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: interiorsmoke doors does not close properly at the "cafeteria entrance door". interior classroom door does not close properly, 1st floor "1m7". reme
Jan 29, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: interiorclassroom doors do not close properly, 3rd flr-301, 307, 2nd flr-208, 207, 206, 203. 1st flr-103, 108. remedy: repair and/or replace.
Jan 29, 2026 · Penalty $1,250
Active - Class - 2
Reissue 35688848n. altered/changed building occupied without a valid cof o as per 28-118.3.1 782/86 3p0008480 for minischool issue feb 7 1996 only good for 5 years. remedy: obtain a valid c of o or discontinue
Jul 7, 2025 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. crack on facadearound building areas on roof broken bricks and mortar missing, mortarmissing on stones letting water into building. remedy: repair and/or r
Jul 7, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. emg lights in the gym not working when tested. remedy: repair and/or replace.
Jul 7, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. exterior doors for minischool base of frames rusted and have holes. remedy: repair and/or replace.
Jul 7, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner. exterior door frames rust at base with holes in it. remedy: repair and/or replace.
Jul 7, 2025 · Penalty $1,250
Resolve - Class - 2
Altered/change building occupied without a valid certificate of occupancy as per 28-118.3.1-28-118.3.2 record documents c of o #237301 issued 02/07/1996 stated as temporary 02/07/2001. remedy: obtain valid cert
Feb 5, 2025 · Penalty $1,250
Active
Show 40 more ↓
- Class - 2
Reissue #35663243j(6/23/22)failure to maintain building in code-compliant manner.noted:observed during inspection of staircase b roof level light fixture broken/detached resting on floor.remedy:repair and/or re
Mar 29, 2023 · Penalty $1,562
Resolve - Class - 2
Exit door not self-closing noted:at 1st floor stair c,smoke by the main entrance to the building,basement smoke by exit 2 and 4;the exit doors are not working properly.rem:repair/replace door.
Jun 23, 2022 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:outside ofexit 1 has a metal fence panel that is broken and is hanging.rem:repair and/replace.
Jun 23, 2022 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:at outsideat exit 1;the bottom of fence has cracks and missing masonry in various areas throughout.rem:repair and/or replace.
Jun 23, 2022 · Penalty $625
Resolve - Class - 2
28-301.1 reissue#35584165h noted:at exposure 3:the storage room has gas powered equipment being stored in the room without any mechanical ornatural ventilation.rem:comply with notice of violation.
Jun 23, 2022 · Penalty $3,125
Resolve - Class - 2
Reissue#35584164x noted:at exposure 3 storage room:have a rather that is broken and another that is hanging creating a hazardous condition and risk of potential collapse.rem:repair and/or replace.
Jun 23, 2022 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:at roof level on stair b side;there is a light fixture that is broken and have electrical wires exposed.rem:repair and/or replace.
Jun 23, 2022 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.observed:at exp #3 storage room,roof structure a support beam (wooden beam) is detached from its anchor beam to be anchored and avoid possible accident.reme
Jul 27, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.use of prohibitedoor and/or hardware per bc 1008.1.8 27-371(j)observed:kick stops installed in all classrooms.remedy:provide legal hardware.
Jul 27, 2021 · Penalty $625
Resolve - Class - 2
28.301.1 re issue # 35442766j failure to provide natural or mechanical ventilation to occupied spaces per mc 401.2.observed:at exp #3 storage room gas equipment without mechanical or natural ventilation.remedy
Jul 27, 2021 · Penalty $3,125
Resolve - Class - 2
Failure to provide nautral or mechanical ventilation to occupied spaces per mc 401.2 note @basement lvl in boiler room storgae of gas equipment(snoblower, lawn mowers, weed wacker, leaf blowers & chainsaw)along
Aug 15, 2019 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner. at ps k124: thefollowing doors are racked and damaged and do not close: exit 2 at 2ndflr, exit 5 at 3rd flr and gymnaisum doors in 306.rmdy: repair and/or
May 8, 2015
Resolve - Class - 2
Doors not closing at 3rd story corridor door adjoining room 301 rem: repair and/or replace door
Mar 13, 2012
Resolve - Class - 2
Corridor smoke doors are defective located on the 3rd fl level by room301 ( noted : door closer is defective causing door not to be self closing ) remedy: repair and /or replace door closer
Oct 12, 2011
Resolve - Class - 2
Furniture desks in corridor banners hanging from ceiling and projecting from walls remedy:remove obstructions
Jun 4, 2009
Resolve - Class - 3
Exterior doors webster st exit (2) spalling rust and rot bottom of doors remedy:repair/replace doors
Jun 4, 2009
Resolve - Class - 3
Water penetration from roof door 308 remedy:repair roof
Jun 4, 2009
Resolve - Class - 2
Electric meter and oil tank rm used for storage of school furniture & maintenance supplies:remedy:discontinue illegal use remove items
Jun 4, 2009
Resolve - Class - 3
Spalling plastic above door 308 on corridor ceiling and classroom ceiling remedy:repair ceiling
Jun 4, 2009 · Penalty $500
Resolve - Class - 2
Reissue 34711768j corridors all fl s partiall obstructed w/ school furniture and book cases remedy:remove obstructions
Jun 4, 2009
Resolve - Class - 2
Desk chairs in place on both side of corridors reducing passage way from fls 1 to 3rd fl rem: provide proper corridor width
Oct 23, 2008
Resolve - Class - 2
All interior exit doors on east west and south racked not closing rem: repair doors
Oct 23, 2008
Resolve - Hazardous
Reissue(34475095m-34510332h)metal hatched used to exit 3rd fl to the roof are rusted and cannot open creating a haz condition in case of fire or emergency. remedy:remove obstruction remove exit signage
May 4, 2007
Resolve - Non-hazardous
Reissue: 344705093z. exit corridor blocked w/tables /chairs & bookcases leading to exit doors 1st fl. remedy: remove obstructions from the exit corridor.
Feb 8, 2006
Resolve - Non-hazardous
Reissue: 34475096y. hallways on 1, 2 & 3rd fls are blocked w/tables, chairs & chairs & book cases leading to exit doors. remedy: remove tables, chairs & book cases from hallways.
Feb 8, 2006
Resolve - Non-hazardous
Reissue: 34475095m. metal hatchers on roof level are rusted & very hard to open which creates a hazardous condition. remedy: replace/repair metal hatchers.
Feb 8, 2006
Resolve - Non-hazardous
Noted : first floor exit corridor required width decreased by obstructions - deck, chairs, tables, dark bench, security desk / chair remedy:remove obstructions, maintain corridors clear
Apr 15, 2005
Resolve - Non-hazardous
Noted : failure to maintain gas meter room free / clear of storage of materials & equipment. remedy : remove all storage, maintain gas meterroom clear
Apr 15, 2005
Resolve - Hazardous
Noted : east & west 3rd floor roof metal scuttle hatches have deteriorated signigicantly and are not readily openable creating a hazardous condition remedy : replace scuttle hatches
Apr 15, 2005
Resolve - Non-hazardous
Noted : 3rd, 2nd & 1st floor corridor exits required width decreased by obstructions - desks, chairs, tables, show case, magazine rack etc... remedy : remove obstructions, maintain corridors clear
Apr 15, 2005
Resolve - Non-hazardous
Noted : failure to maintain required fire stopping within boiler room - east entry entry above door wall penetrations remedy : provide / maintain fire stopping
Apr 15, 2005
Resolve - Non-hazardous
Failure to maintain -noted- windows throughout school are defective and not working properly.windows are loose,screwed closed to prevent windows from falling apart. 1st,2nd, and 3rd floor.windows need to be rep
Jan 26, 2004
Resolve - Hazardous
Failure to maintain building interior & exterior noted cafeteria walls bulding inward due to moisture penetration from coal bunker remedy maintain building make necessary repair
Jan 5, 2004
Resolve - Hazardous
Failure to maintain building interior & exterior noted windows broken and inoperable remedy maintain building make necessary repai
Jan 5, 2004
Resolve - Non-hazardous
Failure to maintain noted bathroom stall partitons rusted corroded sharp edges location: mini school boys bathroom. remedy: replace stall partitons.
Mar 12, 2003
Resolve - Non-hazardous
Failure to maintain noted bathroom stall partitons rotted rusted corroded sharp edges location cafeteria boys bathroom 2 floor boys bathroom. remedy; replace stall partitions.
Mar 12, 2003
Resolve - Hazardous
Re-issue. failure to maintain noted windows throughout school are defective and not working properly windows are loose, screwed closed to prevent them from falling. remedy; repair or replace windows.
Mar 12, 2003
Resolve - Non-hazardous
Failure to maintain noted: at bulkhead east west doors inoperable sticking have to force open and closed. remedy; repair repalce bulkhead doors.
Mar 12, 2003
Resolve - Non-hazardous
Failure to maintain building noted defects 1 floor east side bathroom is deteriorating. remedy: repair bathroom.
Mar 5, 2002
Resolve - Hazardous
Failure to maintain building noted defects windows are broken & defective throughout school hazardous. remedy; repair or replace windows.
Mar 5, 2002
Resolve
Complaints
- Plumbing
Water supply
May 24, 2004 · Apt BLDG
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1933
- Floors
- 3
- Residential units
- —
- Building area
- 35,100 ft²
- Lot area
- 45,583 ft²
- Zoning
- R6A
- Community board
- 314
- Council district
- 40
- Block / lot
- 5416 / 48
- Assessed value
- $3,754,800
- Landmark / historic district
- No
Questions about 4019 18 Avenue
Who owns 4019 18 Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 4019 18 Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 4019 18 Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 4019 18 Avenue built?
City records list 1933 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.