Violations at 1957 Nostrand Avenue

Brooklyn, NY 11210 · BBL 3-04994-0023 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

38 DOB violations, newest first.

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 22, 2021

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Residential elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Jun 1, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 25, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 30, 2012

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2008

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 6, 2006

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    May 31, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed

ECB violations

The newest 50 of 81 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code compliant manner.lack of emergency lighting for exits,exit discharges and public corridors per bc 1006.1;27-542.noted:at 1st fl library rm 117 not installed/provided without

    Apr 21, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at outsideplayground near exit 8 concrete floor cracked/deteriorating/missing creating a tripping/falling condition.

    Apr 21, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue ecb#35692005r failure to maintain building in code-compliant manner.noted:at 1st fl left side rear of auditorium/stair h window/wallwith vertical cracks throughout.rem:repair and/or replace.

    Apr 21, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue ecb#35692006z failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 1st fl auditorium emergency lights not worki

    Apr 21, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue ecb#35692007k exit door not self closing.noted:at 2nd fl hallway smoke door near rm 208 1st fl exit 2,7,cafeteria,library rm 113 doors are all indisrepair/not closing when tested.rem:repair/replace door

    Apr 21, 2026 · Penalty $1,562

    Active
  • Class - 2

    Exit door not self-closing. noted: on the first floor exit 5 the door on the right, exit 4 the door on the right, exit 2 the door on the right also exit 7 the door on the right all these doors were not closing.

    Apr 16, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: in the auditorium stage area twelve lights were not operational

    Apr 16, 2025 · Penalty $1,250

    Active
  • Class - 2

    Re-issue #35678811k. failure to maintain building in code-compliant manner. noted: observed at the rear of the auditorium on the left side there are cracks on both sides of the window. remedy: repair and/or rep

    Apr 16, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35673079x failure to maintain building in code-compliant manner.noted:at time of my inspection i observed at the auditorium to left side of stage in exit passageway a vertical crack on the wall approxim

    Mar 25, 2024 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexit,exit discharges & public corridors per 1006.1; 27-381.noted:defective emergency lighting observed at cafeteria 1 light,at auditorium 4

    Mar 22, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at exit "f" outside missing mortar exposing 1" opening btwn concrete steps.remedy:make necessary repairs.

    Mar 22, 2023 · Penalty $625

    Active
  • Class - 2

    Reissue #35654719l failure to maintain building in code-compliant manner-noted:at auditorium left of stage in exit passageway 10' vertical crack on wall near window.remedy:make necessary repairs.

    Mar 22, 2023 · Penalty $1,562

    Active
  • Class - 2

    Reissue #35654723y failure to maintain building in code-compliant manner.noted:cafeteria door missing door closer.also at 1st fl at exit d & e one exit door racked & does not close properly.remedy:repair/replac

    Mar 22, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    28-301.1 failure to provide ventilation to gas meter room per p115.6(1968 code)fgc appendix e(e4,2014 code)noted observed at time of inspection at basement gas meter area,no ventilation provided.remedy:comply w

    May 11, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code complaint manner.noted observed during inspection of cafeteria doors not operational due to door being racked or missing hardware.remedy:repair and/or replace.

    May 11, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35577481y.failure to maintain building in code compliant manner.noted observed during inspection of auditorium(left of stage)in exitpassageway window area has a vertical crack approx 10ft long.remedy:re

    May 11, 2022 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35442694j(8/02/2019)at failure to maintain building in code compliant manner:at auditorium approx 10'0 vertical crack hear window to exit it.ceiling lack above from main auditorium entrance show make st

    Jun 10, 2021 · Penalty $1,562

    Active
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. remedy; file application, install dlm a

    May 28, 2021 · Penalty $1,250

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor

    Aug 7, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: @3rd fl;exits, stair d, one door & @exit 6, stair e, one door not close properly due to hardware.rem: repair/replace door.

    Aug 2, 2019

    Resolve
  • Class - 2

    Reissue #35342207p failure to maintian building in code compliant manner.noted: @auditorium approx 10' vertical crack in wall near window leading to exit h @ left side of the stage. also celing leak above the

    Aug 2, 2019

    Active
  • Class - 2

    Reissue #35342209z failure to maintain building in code complaint manner noted: spalling plaster in room no 352, 354, 342, 252 due to water penetration through facade.rem: repair/replace make necessary repairs.

    Aug 2, 2019

    Resolve
  • Class - 2

    Reissue nov #35221456p.stair identification signs missing or defectivenoted:exit doors 1st fl stair exits not identified.rem:comply with code

    Jun 13, 2018

    Resolve
  • Class - 2

    Noted: at stair a at bulkhead door saddle missing causing water damageat room 306. rmdy: comply with code.

    Jun 13, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliantmanner. noted: at rear (non public walkway) with concaved pavers. tripping hazard. rmdy: comply with code.

    Jun 13, 2018

    Resolve
  • Class - 2

    Noted: broken windows: 1-nostrand av 14 panes broken; 2-at rear park ing lot 5 panes broken; 3-at room 252 broken window. rmdy: comply w/code.

    Jun 13, 2018

    Resolve
  • Class - 2

    Reissue nov #3527241h noted: 1-roof water penetration into 3rd floor classrooms. water damage throughout floor;2-observed damage from waterat room 352 (wall; 3-at electric meter room; ceiling and wall;4-at sta

    Jun 13, 2018

    Resolve
  • Class - 2

    Reissue nov#35272242j noted: at 1st flr handicap entrance, at auditorium, at 1st flr near at exit b fpsc door not self closing when tested.rmdy: comply with code.

    Jun 13, 2018

    Resolve
  • Class - 2

    Reissue nov #35272245p noted: apprx 10' vertical crack at wall (window) leading to exit from auditorium. rmdy: comply with code.

    Jun 13, 2018

    Active
  • Class - 2

    Failure to maintain bldg in code compliant manner.noted;apprpx 10 ft veritcal crack was observed on wall near window at corrideor leading to exit from auditorium at leftside.rem:repair

    Jul 19, 2017

    Active
  • Class - 2

    Failure to maintain bldg in code-compliant manner;lack of emergency lighting for exits,exit discharges and public corridors per bc1006.1;27-542.noted:defective emergency lighting was observed at cafeteria exit

    Jul 19, 2017

    Resolve
  • Class - 2

    Exit door not self-closing.noted:at 1st fl handicapped entrance door,aat left exterior exit from auditorium at 1st fl exterior rear exit,at exit 8 doors are not self-closing.rem:repair/replace door

    Jul 19, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.note:water penetration from roof was observed at staircase(e)bulkhead walls at rm 316,306 and 304.ceiling at 3rd fl ceiling at public corridor near rm #354 and

    Jul 19, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.noted:@3rd fl hallway,outside rm 352,water leaking from ceiling/roof.rem:comply w/code.

    Nov 15, 2016

    Resolve
  • Class - 2

    Stair identification signs missing or defective note:@exit doors,@1st fl, stair exits not identified.rem:comply w/code.

    Nov 15, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.notd:@(cafetia),@rear door exit,emergency lights not working @gym,high hat emergency lights not working.rem:comply w/code.

    Nov 15, 2016

    Resolve
  • Class - 3

    Failure to maintain bldg in code-compliant manner.noted:@1st fl,exit 10,stair a fpsc doors rotted bottom.rem:comply w/code.

    Nov 15, 2016

    Resolve
  • Class - 2

    Exit door not self closing.noted:@1st fl (cafeteria) (rear doors) fpsc doors hinge broken.rem:comply w/code.

    Nov 15, 2016

    Resolve
  • Class - 2

    Reissue nov 35023482c noted:@cellar,ash hoist steel doors &frame rotted.rem:comply w. code.

    Nov 15, 2016

    Resolve
  • Class - 2

    Reissue: 35107718r failure to maintain bldg wall(s) or appurtenances noted: evidence of water penetration into rooms from facade at room 352,354,342 and cellar.rmdy: comply with code.

    Nov 15, 2016

    Resolve
  • Class - 2

    Re issue nov #35148137j failure to maintain bldg in code compliant manner.noted:@1st fl gym,drop ceiling tile(s) broken/missing.rem:comply w/code

    Nov 15, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg code compliant.lack of emergency lighting perbc1006.1;27-542.noted @ 1st fl cafeteria 50% inoperative emergency lighting w/ battery back up for exits.rem comply w/ code

    Oct 7, 2015

    Resolve
  • Class - 2

    Reissue#35107716n failure to maintain bldg code compliant.noted @ 1st fl gym,6 drop ceiling acoustical tiles missing.rem comply w/ code

    Oct 7, 2015

    Resolve
  • Class - 2

    Reissue ecb #34941308m facade water penetration.water penetrating fromfacade into rooms 352,354,342,252 & cellar.rem:water proof facade.

    Aug 15, 2014

    Resolve
  • Class - 2

    Reissue ecb #35023479k racked door bulkhead door racked & not closing prop.rem:repair/replace bulkhead door.

    Aug 15, 2014

    Resolve
  • Class - 2

    Reissue ecb 35023481j gym ceiling tiles.@ 1st floor gym,there are several missing ceiling tiles.rem:install missing ceiling tile.

    Aug 15, 2014

    Resolve
  • Class - 2

    Reissue ecb #35023482l ash hoist door.ash hoist steel doors & frame are rotted.rem:replace ash hoist doors + frame.

    Aug 15, 2014

    Resolve
  • Class - 2

    Ash hoist steel doors and framing rotted out. rmdy: maintain building as per code.

    Jun 19, 2013

    Resolve
  • Class - 2

    Reissue 34941307k gym ceiling tiles missing at various locations. rmdy: repair and/or replace.

    Jun 19, 2013

    Resolve
  • Class - 3

    Water penetration from wall and/or roof.3story rooms 352,354,348,342; 2-story room 252; 1story gym. cellar foundation walls; roof bulkhead spalling b&d; roof bulkhead spalling d&e.rmdy:maintain building as per

    Jun 19, 2013

    Resolve