Violations at 525 Lenox Road

Brooklyn, NY 11203 · BBL 3-04844-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

40 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2014 inspection report

    Oct 1, 2015

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2014 inspection report

    Oct 1, 2015

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2014 inspection report

    Oct 1, 2015

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 19, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 11, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 15, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 9, 2010

    Dob violation - resolved
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 1, 2009

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 11, 2006

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    May 31, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1993

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed

ECB violations

The newest 50 of 78 ECB violations. The city keeps the complete history.

  • Class - 2

    Reissue ecb#35692002l exit door not self closing.noted:at 1st fl stairb,exit 9 bathrooms rm 112 & 113 2nd fl teachers lounge rm 262 doors are in disrepair/not closing when tested.rem:repair/replace door.

    Apr 17, 2026 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue ecb#35692003n failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted at 1st fl cafeteria 4th fl hallway exit sign ne

    Apr 17, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35678806x. failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors perbc 1006.1; 27-381. noted: in the gymnasium to lights in the cafeteria

    Apr 15, 2025 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35678807h. exit door not self-closing. noted: room 262 and room 112 and 113, all these doors were not closing properly. remedy: repair/replace door.

    Apr 15, 2025 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35672889n exit door not self-closing noted:at time of my inspection i observed at room 262 and smoke exit 5 and 9 door are not working properly also on the 1st floor corridor at stair g room/112 and 113

    Mar 20, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35672890k failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at time of my inspection i observed at the auditori

    Mar 20, 2024 · Penalty $1,562

    Active
  • Class - 2

    Exit door not self-closing.noted:doors at exit 5 not working properly.remedy:repair/replace door

    Apr 3, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 1st fl corridor at stair g,rm 112 & 113,doors not working properly.remedy:repair and/or replace.

    Apr 3, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1; 27-381.noted:at auditorium exit sign #48, em #10 & cafeteria, the emergency lights

    Apr 3, 2023 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing.noted:doors at exit 5 & 10 not working properly.remedy:repair/replace door.

    Apr 3, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:door at rm 262 & smoke by exit 5 & 9 not working properly.remedy:repair and/or replace.

    Apr 3, 2023 · Penalty $625

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor

    Aug 7, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Reissued #35442725n (8-2-2019) failure to maintain buidling in code compliant manner @ cafeteria stair a auditorium exit of main entrance #1 hallway by (room) repair and or replace

    Jun 3, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued #35442727r (8-2-2019) exit door not self closing @ 1st floor exit 5 auditoriuum missing or disrepair /not operable repair and or replace door(s)

    Jun 3, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self closing. noted: at 1st fl exit 5, and auditorium door checks are in disrepair/non operational. remedy: repair/replace door

    Aug 2, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: at 2nd fl staff lounge water penetration/damage with staining at walls and ceiling. remedy: repair and/or replace

    Aug 2, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: at (1st fl) hallway near rm 152, auditorium, exit 9, main entrance #1, cafeteria,stair a doors are in disrepair/racked. remedy:repair and/or replace

    Aug 2, 2019

    Resolve
  • Class - 2

    Faulure to maintain building in code compliant manner in staff lounge room water penetration from wall and roof.rem:repair and replace.

    May 30, 2018

    Resolve
  • Class - 2

    Exit door not self closing.in cafeteria(near room n0-117a)one door andin auditorium left side one door not self closing when tested at the time of inspection.rem:repair/replace door

    May 30, 2018

    Resolve
  • Class - 2

    Failure to maintain building code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381 at cafeteria(door no 155)one fire exit light not illuminated when tested at th

    May 30, 2018

    Resolve
  • Class - 2

    48t07,68m07,12x10,16b11,15t07.(48t)pressure test info.(68m)missing test info.(12x)dead light.(68)provide designated looby bake tag.(15t)mostassuent cat one.

    Dec 11, 2017

    Resolve
  • Class - 2

    Faiure to maintain building wall(s) or appurtenances water penetrationinto cafeteria,staff lounge and first floor bridge enclosure to mini school building at roof.remedy:comply with notice of violation.

    Jul 26, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits,exit discharges & public corridirs per bc 1006.1;27-542 found defective lights @ library & cafeteria by exit 5 & stair b.

    Nov 10, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.@rm 207 upk sink in classrm not working properly rust visible & loose.rem:comply w/notice of vio.

    Oct 2, 2015

    Resolve
  • Class - 2

    Reissue ecb #34941557n racked doors.@ 1st floor;cross corridor doors near room 152 racked + not closing prop.@ auditorium stage exit door d racked + not closing prop.rem:repair/replace doors.

    Aug 18, 2014

    Resolve
  • Class - 2

    The concrete ceiling is spalling located at the cellar level by the coal bunker. remedy: repair/replace concrete ceiling.

    Jun 4, 2013

    Resolve
  • Class - 2

    The ash hoist door is rusted/rotte(d) located at the cellar level. remedy: replace hoist door.

    Jun 4, 2013

    Resolve
  • Class - 2

    Wall mounted electric heaters not functioning at: 1st story stair g enclosure heater adjacent to playground exit, boys room heater, and at: 2nd story public corridor. remedy: repair heaters.

    Feb 13, 2012

    Resolve
  • Class - 2

    Water damaged plaster ceiling & wall at: 4th story room 401 plaster ceiling & wall spalling/blistered/water damaged. remedy: repair defects noted.

    Feb 13, 2012

    Resolve
  • Class - 2

    Doors not closing at: 1st story cross corridor doors near room 152., stage exit door to stair d. at: 3rd story stair b. remedy: replace doors.

    Feb 13, 2012

    Resolve
  • Class - 2

    Transportable t-8-t6-t-5 have soft spots in flooring by front door severe sagging noted. remedy: replace floor dorthwith

    Aug 26, 2011

    Resolve
  • Class - 2

    Defective doors noted staircase doors 4 fl stair a,b,e, corridor door next to room 429, 3 fl stair a, 2 floor stair b, f remedy : repair / repalce door

    Aug 26, 2011

    Resolve
  • Class - 2

    Re 34863950z exterior wall & chimney stress cracks with loose brick mortor noted noted @ north west side auditorium, also chimney on west side parapet level. remedy: repair

    Aug 26, 2011

    Resolve
  • Class - 1

    Transportable)ramps at transportable in hazards condition t1 - t2 - t3- t5 - t8,also entrance flooring of t5 sagging ramps sagging planks,loose railing,crumbling wooden ramps. remedy: make safe forthwith.

    Jul 20, 2010

    Resolve
  • Class - 2

    (mini school) defective door at cafeteria exit door. remedy: make safe.

    Jul 20, 2010

    Resolve
  • Class - 3

    Defective doors throughout 1st floor multiple exit vestibule doors(hitting) frame not closing properly. remedy: repair/replace doors.

    Jul 20, 2010

    Resolve
  • Class - 2

    Exterior wall & chimney stress cracks with loose brick/mortar. noted: at north west side. (auditorium) stress crack also chimney on west side parapet level. remedy: make safe.

    Jul 20, 2010

    Resolve
  • Class - 3

    Stwy 3 exit door w/o door check. remedy: provide door check.

    May 6, 2009

    Resolve
  • Class - 2

    Roof leak over 2nd flr elevator in corridor damaging ceiling tile. remedy: stop roof leak.

    May 6, 2009

    Resolve
  • Class - 2

    2nd flr ceiling tile damage by water leak over elevator in corridor. remedy: repair & replace ceiling tile.

    May 6, 2009

    Resolve
  • Class - 2

    Approx 6 ceiling tile missing in rm 428. remedy: repair ceiling tile.

    May 6, 2009

    Resolve
  • Class - 2

    Gymnasium door,stwy 'b' corridor door off main entrance to cafeteria doors are racked. remedy: repair racked doors.

    May 6, 2009

    Resolve
  • Class - 2

    1st flr exit 7 & stwy "a" vestibule door not closing. remedy: repair/replace exit doors.

    May 6, 2009

    Resolve
  • Class - 2

    No key in room that's marked on roof door. no key on entire flr for roof access. remedy: provide key for exit door to roof.

    May 6, 2009

    Resolve
  • Class - 2

    Re-issue no fire stopping provided above electrical door at cellar level. remedy: provide fire stopping.

    May 6, 2009

    Resolve
  • Class - 3

    Storage in mechanical room at 1st fl. rem: stop storage in mechanical room

    May 6, 2009

    Resolve
  • Class - 2

    Plaster is spalling @ 2 locations on the ceiling & wall. room 461 on the 4th floor level & room 313 on the 3rd floor level. remedy: repair /replace plaster wall & ceiling

    Sep 25, 2008

    Resolve
  • Class - 2

    Reissue : 34508541l no fire stopping provided above the electrical door at cellar level. remedy: provide fire - stopping above the electrical door way

    Sep 25, 2008

    Resolve
  • Non-hazardous

    Re-issue:34508540j. vertical cracks approx. 4'long located at two corner in the gym on the 2nd floor. remedy: maintain/repair vertical cracks.

    Feb 7, 2007

    Resolve
  • Hazardous

    No protective guard at roof (gym side) parapet high -24". remedy: provide protective guards.

    Mar 16, 2006

    Resolve