Violations at 525 Lenox Road
Brooklyn, NY 11203 · BBL 3-04844-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
40 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 19, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 11, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 15, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 9, 2010
Dob violation - resolved - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 1, 2009
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 11, 2006
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 1, 1994
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
May 31, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 1, 1993
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 7, 1992
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 25, 1991
Dob violation - dismissed
ECB violations
The newest 50 of 78 ECB violations. The city keeps the complete history.
- Class - 2
Reissue ecb#35692002l exit door not self closing.noted:at 1st fl stairb,exit 9 bathrooms rm 112 & 113 2nd fl teachers lounge rm 262 doors are in disrepair/not closing when tested.rem:repair/replace door.
Apr 17, 2026 · Penalty $1,562
Resolve - Class - 2
Reissue ecb#35692003n failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted at 1st fl cafeteria 4th fl hallway exit sign ne
Apr 17, 2026 · Penalty $3,125
Active - Class - 2
Re-issue #35678806x. failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors perbc 1006.1; 27-381. noted: in the gymnasium to lights in the cafeteria
Apr 15, 2025 · Penalty $3,125
Active - Class - 2
Re-issue #35678807h. exit door not self-closing. noted: room 262 and room 112 and 113, all these doors were not closing properly. remedy: repair/replace door.
Apr 15, 2025 · Penalty $1,562
Resolve - Class - 2
Reissue#35672889n exit door not self-closing noted:at time of my inspection i observed at room 262 and smoke exit 5 and 9 door are not working properly also on the 1st floor corridor at stair g room/112 and 113
Mar 20, 2024 · Penalty $1,562
Resolve - Class - 2
Reissue#35672890k failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at time of my inspection i observed at the auditori
Mar 20, 2024 · Penalty $1,562
Active - Class - 2
Exit door not self-closing.noted:doors at exit 5 not working properly.remedy:repair/replace door
Apr 3, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:at 1st fl corridor at stair g,rm 112 & 113,doors not working properly.remedy:repair and/or replace.
Apr 3, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1; 27-381.noted:at auditorium exit sign #48, em #10 & cafeteria, the emergency lights
Apr 3, 2023 · Penalty $625
Resolve - Class - 2
Exit door not self-closing.noted:doors at exit 5 & 10 not working properly.remedy:repair/replace door.
Apr 3, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:door at rm 262 & smoke by exit 5 & 9 not working properly.remedy:repair and/or replace.
Apr 3, 2023 · Penalty $625
Resolve - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor
Aug 7, 2020 · Penalty $1,250
Resolve - Class - 2
Reissued #35442725n (8-2-2019) failure to maintain buidling in code compliant manner @ cafeteria stair a auditorium exit of main entrance #1 hallway by (room) repair and or replace
Jun 3, 2020 · Penalty $1,562
Resolve - Class - 2
Reissued #35442727r (8-2-2019) exit door not self closing @ 1st floor exit 5 auditoriuum missing or disrepair /not operable repair and or replace door(s)
Jun 3, 2020 · Penalty $1,562
Resolve - Class - 2
Exit door not self closing. noted: at 1st fl exit 5, and auditorium door checks are in disrepair/non operational. remedy: repair/replace door
Aug 2, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner. noted: at 2nd fl staff lounge water penetration/damage with staining at walls and ceiling. remedy: repair and/or replace
Aug 2, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner. noted: at (1st fl) hallway near rm 152, auditorium, exit 9, main entrance #1, cafeteria,stair a doors are in disrepair/racked. remedy:repair and/or replace
Aug 2, 2019
Resolve - Class - 2
Faulure to maintain building in code compliant manner in staff lounge room water penetration from wall and roof.rem:repair and replace.
May 30, 2018
Resolve - Class - 2
Exit door not self closing.in cafeteria(near room n0-117a)one door andin auditorium left side one door not self closing when tested at the time of inspection.rem:repair/replace door
May 30, 2018
Resolve - Class - 2
Failure to maintain building code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381 at cafeteria(door no 155)one fire exit light not illuminated when tested at th
May 30, 2018
Resolve - Class - 2
48t07,68m07,12x10,16b11,15t07.(48t)pressure test info.(68m)missing test info.(12x)dead light.(68)provide designated looby bake tag.(15t)mostassuent cat one.
Dec 11, 2017
Resolve - Class - 2
Faiure to maintain building wall(s) or appurtenances water penetrationinto cafeteria,staff lounge and first floor bridge enclosure to mini school building at roof.remedy:comply with notice of violation.
Jul 26, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits,exit discharges & public corridirs per bc 1006.1;27-542 found defective lights @ library & cafeteria by exit 5 & stair b.
Nov 10, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.@rm 207 upk sink in classrm not working properly rust visible & loose.rem:comply w/notice of vio.
Oct 2, 2015
Resolve - Class - 2
Reissue ecb #34941557n racked doors.@ 1st floor;cross corridor doors near room 152 racked + not closing prop.@ auditorium stage exit door d racked + not closing prop.rem:repair/replace doors.
Aug 18, 2014
Resolve - Class - 2
The concrete ceiling is spalling located at the cellar level by the coal bunker. remedy: repair/replace concrete ceiling.
Jun 4, 2013
Resolve - Class - 2
The ash hoist door is rusted/rotte(d) located at the cellar level. remedy: replace hoist door.
Jun 4, 2013
Resolve - Class - 2
Wall mounted electric heaters not functioning at: 1st story stair g enclosure heater adjacent to playground exit, boys room heater, and at: 2nd story public corridor. remedy: repair heaters.
Feb 13, 2012
Resolve - Class - 2
Water damaged plaster ceiling & wall at: 4th story room 401 plaster ceiling & wall spalling/blistered/water damaged. remedy: repair defects noted.
Feb 13, 2012
Resolve - Class - 2
Doors not closing at: 1st story cross corridor doors near room 152., stage exit door to stair d. at: 3rd story stair b. remedy: replace doors.
Feb 13, 2012
Resolve - Class - 2
Transportable t-8-t6-t-5 have soft spots in flooring by front door severe sagging noted. remedy: replace floor dorthwith
Aug 26, 2011
Resolve - Class - 2
Defective doors noted staircase doors 4 fl stair a,b,e, corridor door next to room 429, 3 fl stair a, 2 floor stair b, f remedy : repair / repalce door
Aug 26, 2011
Resolve - Class - 2
Re 34863950z exterior wall & chimney stress cracks with loose brick mortor noted noted @ north west side auditorium, also chimney on west side parapet level. remedy: repair
Aug 26, 2011
Resolve - Class - 1
Transportable)ramps at transportable in hazards condition t1 - t2 - t3- t5 - t8,also entrance flooring of t5 sagging ramps sagging planks,loose railing,crumbling wooden ramps. remedy: make safe forthwith.
Jul 20, 2010
Resolve - Class - 2
(mini school) defective door at cafeteria exit door. remedy: make safe.
Jul 20, 2010
Resolve - Class - 3
Defective doors throughout 1st floor multiple exit vestibule doors(hitting) frame not closing properly. remedy: repair/replace doors.
Jul 20, 2010
Resolve - Class - 2
Exterior wall & chimney stress cracks with loose brick/mortar. noted: at north west side. (auditorium) stress crack also chimney on west side parapet level. remedy: make safe.
Jul 20, 2010
Resolve - Class - 3
Stwy 3 exit door w/o door check. remedy: provide door check.
May 6, 2009
Resolve - Class - 2
Roof leak over 2nd flr elevator in corridor damaging ceiling tile. remedy: stop roof leak.
May 6, 2009
Resolve - Class - 2
2nd flr ceiling tile damage by water leak over elevator in corridor. remedy: repair & replace ceiling tile.
May 6, 2009
Resolve - Class - 2
Approx 6 ceiling tile missing in rm 428. remedy: repair ceiling tile.
May 6, 2009
Resolve - Class - 2
Gymnasium door,stwy 'b' corridor door off main entrance to cafeteria doors are racked. remedy: repair racked doors.
May 6, 2009
Resolve - Class - 2
1st flr exit 7 & stwy "a" vestibule door not closing. remedy: repair/replace exit doors.
May 6, 2009
Resolve - Class - 2
No key in room that's marked on roof door. no key on entire flr for roof access. remedy: provide key for exit door to roof.
May 6, 2009
Resolve - Class - 2
Re-issue no fire stopping provided above electrical door at cellar level. remedy: provide fire stopping.
May 6, 2009
Resolve - Class - 3
Storage in mechanical room at 1st fl. rem: stop storage in mechanical room
May 6, 2009
Resolve - Class - 2
Plaster is spalling @ 2 locations on the ceiling & wall. room 461 on the 4th floor level & room 313 on the 3rd floor level. remedy: repair /replace plaster wall & ceiling
Sep 25, 2008
Resolve - Class - 2
Reissue : 34508541l no fire stopping provided above the electrical door at cellar level. remedy: provide fire - stopping above the electrical door way
Sep 25, 2008
Resolve - Non-hazardous
Re-issue:34508540j. vertical cracks approx. 4'long located at two corner in the gym on the 2nd floor. remedy: maintain/repair vertical cracks.
Feb 7, 2007
Resolve - Hazardous
No protective guard at roof (gym side) parapet high -24". remedy: provide protective guards.
Mar 16, 2006
Resolve