Violations at 9301 Avenue B
Brooklyn, NY 11236 · BBL 3-04753-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
46 DOB violations, newest first.
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 10, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Residential elevator periodic inspection/test elevatorrequired
Failure to perform category 5 inspection
Jun 1, 2016
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 19, 2012
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2011 inspection/test
Oct 1, 2012
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2010 cat 1 insp/tst
Aug 15, 2012
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Vcat1-elevator annual inspection / test elevatorrequired
Oct 8, 2010
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 25, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 14, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 5, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 30, 2007
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 27, 2005
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Elevator elevatorrequired
3p8501
Apr 6, 2000
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 10, 2000
Dob violation - dismissed - Elevator elevatorrequired
3p8501
Jun 2, 1999
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 20, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active
ECB violations
41 ECB violations, newest first.
- Class - 2
Failure to maintain building in code-compliant manner.at the time of inspection,room 409 ceiling was leaking/water stains were visible room 271 also had ceiling leaks.there was crack glass panels in stairwell b
Apr 16, 2026 · Penalty $1,250
Active - Class - 2
Exit door not self-closing.at the time of inspection,the following exit discharge doors were not self-closing #10,#9,#6.rem:repair/replace door.
Apr 16, 2026 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). at the time of inspection, the following doors had turn knob handles:-413, 351b, 202, 10
Apr 16, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. at the time of inspection, the following doors were not self-closing:-419, 401, 404, 463, 466, 469,351b, 452, 307, 309, 319, 386, 384, 375, 380, corridor d
Apr 16, 2026 · Penalty $1,250
Active - Class - 2
Reissue#35672019j failure to maintain building in code-compliant manner.rem:comply with code repair and/or replace.
Mar 19, 2024 · Penalty $1,562
Resolve - Class - 1
Cease use item: car intermittently shuts down creating a entrapment hazard. class2 items: seal tank leaks. unguarded tank motor leads.
Jan 11, 2024 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:observed during inspection of basement pipes leaking in rm 076(water meter rm) & in boiler rm water tank & collecting in pails.remedy:repair and/or re
Mar 17, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:observed during inspection of front main fire proof self-closing door (fdsc d)window panel shattered & stairwell vision panel at 2nd fl ste also shatt
Mar 17, 2023 · Penalty $625
Resolve - Class - 2
Reissue#35495887p.failure to maintain building in code compliant manner.noted at 4th floor room 465,467,466 at 3rd floor room 313,315,309,301,hallway exit by room 380,at 1st floor exit 9,exit door to playground
May 5, 2022 · Penalty $1,562
Resolve - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. remedy; file application, install dlm a
Sep 25, 2020 · Penalty $1,250
Resolve - Class - 2
Reissued #35442723j(8-2-2019) failure to maintain building in code compliant manner manner door(s) not working properly room 301.303,girls bathroom next room room 309 ,386,401,467 repair and or replace
Jun 2, 2020 · Penalty $1,562
Resolve - Class - 2
Reissued #3542724l failure maintain buidling in code compliament manner exterior metal frames in all area show sign of rusted and spalling paints repair and or replace
Jun 2, 2020 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner:no fire stoppingper bc 712.3;27-345. noted:at the cellar electrical rm and mechanical on the 3rd fl,penetration through the wall in various areas. remedy:pr
Aug 2, 2019
Resolve - Class - 2
28-301.1 unlawful placement of furnishings,decorations or other objects at exits that obstruct access to,egress from or visibility thereof per fdny 2008 code;fc 1027.4. noted:at the cafeteria,exit passageway ob
Aug 2, 2019
Resolve - Class - 2
Exit door not self-closing. noted:the following doors are not working properly;1st fl smoke doors by the auditorium main entrance,auditoriummain entrance and left rear,and the 3rd fl smoke by 371. remedy:repair
Aug 2, 2019
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: the metal fence at all exposures has spalling paint and is rusted in various areas. remedy: repair and/or replace
Aug 2, 2019
Resolve - Class - 2
Failure to maintain building in code complaint manner. noted: the following doors are not working properly; 301, 303, girls restroom by 309,386, 401, & 467. rem: repair and/or replace
Aug 2, 2019
Resolve - Class - 2
Failure to maintain building code-compliant manner:use of prohibited door and/or hardware per bc 1008.1.8;27-371(j). noted:the following doors have kick down holders installed;468,465,407,405,401,303,302 and va
Aug 2, 2019
Resolve - Class - 2
Exit door not self closing.in first floor exit 9 outside door one door.in first floor exit 4 one door outside is not self closing properly in auditorium near exit 7 one door outside and auditorium exit "f"one d
Jun 7, 2018
Resolve - Class - 2
Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc1006.1;27-381 in gym at 3rd floor two existing emergency light are not operational when tes
Jun 7, 2018
Resolve - Class - 2
Failure to maintain building in code compliant manner.no fire stoppingper bc712.3 27-345 observed. no fire stopping done at room 455,352a @ cellar hall between 1st fl & cellar exit a, oil tank room, electrical
Nov 9, 2016
Resolve - Class - 2
Exterior wrought iron rence. exterior 3'high wrought iron fence near exit door on east 94th st side is falling and dilapitated. rmdy: repair fence.
Aug 11, 2014
Resolve - Class - 2
Reissue ecb 35027927n spalling walls and/or ceilings at rooms 301 & 205, ceiling walls spalling from previous water damage. rmdy: repair ceiling/walls
Aug 11, 2014
Resolve - Class - 2
Reissue ecb 35027929r defective doors. at first floor, cross corridor doors new room 152 are defective and out of plumb rendering doors do not close properly. rmdy: repair/replace doors.
Aug 11, 2014
Resolve - Class - 2
Corridor smoke doors defective by room 152 (1st flr). noted: doors notopen & closed properly. remedy: repair/replace doors.
Jul 17, 2013
Resolve - Class - 2
Reissue: 34941975x. the gymnasium exit panic bar is not fully attachedto the door at the 4th flr level rear. remedy: re-attached panic bar.
Jul 17, 2013
Resolve - Class - 2
The plaster on the ceiling is spalling located in room 301 & 205. remedy: repair/replace plaster on ceiling.
Jul 17, 2013
Resolve - Class - 2
Door not closing at 4th story stair f. remedy: replace door.
Mar 2, 2012
Resolve - Class - 2
Reissue 34779304m missing fire proofing on 'i' beams at cellar level stair 'a'. remedy: provide fire proofing.
Sep 1, 2011
Resolve - Class - 2
Roof drain leaking in main entrance lobby. remedy: stop water leak.
May 5, 2009
Resolve - Class - 2
Fire proofing missing on 'i' beams at cellar level over stwy 'a' to boiler boiler room. remedy: provide fire proofing.
May 5, 2009
Resolve - Class - 2
The brick wall is cracked vertically in the gymnasium at the corner approximately 10'ft long 3rd fl level rem: repair / replace cracked brick
Nov 12, 2008
Resolve - Hazardous
Exit door in auditorium by stage (right door) not self-closing. remedy: repair/replace door.
Mar 15, 2006
Resolve - Hazardous
No fire stopping in wall, ceiling & above door frame was provided in electrical rm old wing. remedy: provide/maintain fire stopping
Mar 15, 2006
Resolve - Hazardous
Failure to maintain building. noted defects. sunker drain in playyard outside exit 10. remedy: make repairs.
Mar 13, 2002
Resolve - Non-hazardous
Failure to provide 10 x 12 elevator larding sigh on all floors. failure to provide 3 elevator id signs on all floors. remedy: provide signage as per local law 16/84.
Oct 3, 2001
Resolve - Non-hazardous
Failure to provide emergency pover to exit lights on all floors and stairs. failure to proved emergency pover to exit detl sighs on all floors. remedy: provide emergency pover exit lights and to exit directiona
Oct 3, 2001
Resolve - Non-hazardous
Failure to maintain defect is windowns are defective at old wing sashes are rotten and window sills aew disintegrating at new wing, inoperable window defficult to open. remedy: maintain building provide new win
May 2, 2001
Resolve - Hazardous
Failure to maintain exterior building wall. defect is defect various locations at facade of building old wing-parapet wall have cracks and unstable leaning at inner courtyard. terra cotta fit facades have crack
May 2, 2001
Resolve - Non-hazardous
Failure to maintain bldg. defects are large vertical crack on exterior east side of chimney.loose tin over coping on parapet.crack above no. window in rm. 210.remedy:do all repairs.
May 26, 2000
Resolve - Non-hazardous
74m7. provide fresh air ventilation in shaftway not operated by fused fire control (code requirement 3'x3' minimum).
Dec 5, 1997
Resolve