Violations at 1096 East New York Avenue

Brooklyn, NY 11212 · BBL 3-04599-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

24 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2020)

    Oct 10, 2021

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2019

    Jun 29, 2020

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Apr 29, 1999

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Apr 29, 1999

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Apr 29, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed

ECB violations

The newest 50 of 99 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at every floors/hallways installed hung nonfire retarted decorations to ceilingsthroughout various areas.rem:comply with code.

    Apr 13, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self closing noted at 1st fl main entrance 2nd fl hallway smoke door near rm 205 3rd floor stair f 4th fl stair d 5th fl stairdoors are in disrepair/not closing when tested.rem:repair/replace door

    Apr 13, 2026 · Penalty $625

    Active
  • Class - 2

    Reissue ecb#35692010l failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted at 1st fl play area cafeteria 2nd fl auditorium

    Apr 13, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: two doors were nt closing properly. at the mini school entry doors. remedy: repair and/or replace.

    Apr 18, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Re-issue #35678673l. failure to maintain building in code-compliant manner. on the second floor corridor next to stair c 2 floor. remedy: repair and replace.

    Apr 18, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Re-issue #35678764n. failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors perbc 1006.1 ; 27-381. noted: third floor stairway d four lights, third f

    Apr 18, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35672496m. failure to maintain building in code-compliant manner, illumination for exits, exit discharges and public corridors per bc1006.1; 27-381. noted: at time of inspection i observed the emergenc

    Mar 13, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue #35672493r. failure to maintain building in code-compliant manner. notted: at time of my inspection i observed at the 2nd floor corridor by the stair c need to the auditorium the entrance smoke door by

    Mar 13, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:the emergency light by room#8 is inoperative.rem:repair/replace lighti

    Mar 8, 2023 · Penalty $625

    Active
  • Class - 2

    Exit door not self-closing.noted:the smoke door by exit 1 is not working properly.rem:repair/replace door.

    Mar 8, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency light#19 at the cafeteria is inoperative.rem:repair/replace

    Mar 8, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at room 508,413,460,303,3rd floor stair d,f,2nd floor corridor by stair c,auditorium entrance,smoke by exit 4 and 6,the doors are not working properly

    Mar 8, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35654687x noted:the exterior doors at exit 2,4 and 7 are not working properly.rem:repair/replace door.

    Mar 8, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.noted:the girls restroom by exit 1;the door is not working properly. remedy: repair and/or replace

    May 4, 2022 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing.noted: the smoke door by exit 1 is not work-ing properly. remedy: repair/replaces door.

    May 4, 2022 · Penalty $625

    Resolve
  • Class - 2

    Re-issue #35495693r.noted:at 4th fl smoke at stair d by 411,3rd fl smoke by 205,exterior exit door #7,smoke by exit 6 & the auditorium entrance;the exit doors are not working properly.remedy:repair/replace door

    May 4, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue #354956942.noted:at rooms #508,405,413,& 201;the doors are not working properly. remedy: repair and/or replace.

    May 4, 2022 · Penalty $1,562

    Resolve
  • Class - 1

    Failure to maintain record of pre-shift safety meeting. note: at time of my inspection of a 1 sty bldg topped off at roof construction work in progress. i observed several,workers performing work involving plum

    Aug 11, 2021

    Resolve
  • Class - 2

    Reissue35442704y exit door not seflclosing-noted:following exit doors arent working properly.smoke doors by exit3&thruout entire school.comply w/code.

    Jun 1, 2021 · Penalty $1,562

    Resolve
  • Class - 1

    Superintendent failed to immediately notify dob of accident at construction site-note:at time of my inspection of a 1 story building at foundation stage active jobsite.in response to an incident at jobsite.i re

    Feb 21, 2020 · Penalty $2,500

    Resolve
  • Class - 1

    Work does not conform to ssplan.note:at time of my inspection of a 1 story bldg at foundation stage.i observed a wooden ramp bulk with 2x6 wood and plywood at expo#3 not design in accordance with the ssp this c

    Feb 21, 2020 · Penalty $625

    Resolve
  • Class - 1

    Failure to promptly notify the dept. of an accident on damage to adj property at construction site.note:at time of my inspection in responseto an incident of a damage gas line.upon research in dob records there

    Feb 21, 2020 · Penalty $5,000

    Resolve
  • Class - 1

    Failure to sageguard all persons and properties affected by construction operations.note:at time of my inspection of a building at foundation stage active jobsite.in response to an incident on which workers wer

    Feb 21, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Exit door not self-closing. noted" the following exit doors are not working properly; smoke doors bt exit 7 & exit 3 exterior door, @the mini school k889.rem: repair/replace.

    Jul 30, 2019 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing noted: the following exit doors are not working properly; 1st fl stair f , auditorium entrance, 2nd fl stair f, 3rd fl stair a, 4th fl stair c and the 5th fl satir f.rem: repair /repl

    Jul 30, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code-complaint manner. noted: the following doors are not working properly; 801, 802, 807 & the bay's restroom, @ the(minischool) k889. reml repair and/or replace

    Jul 30, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code-complaint manner. noted; @the cellar vl gas meter room, and building 2exit a+b roof lvl, has spalling paint in various areas. rem: make neccessary repairs.

    Jul 30, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner, noted: the following door are not working properly; 201, 203, 204, 212, 310, 312, 302, 352, 402, 407, 408, 410, 413, 501, 502 & 508.rem: repair and/replace

    Jul 30, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:use of prohibited door and/or hardware per bc 1008.1.8;27-371(j). noted:at the entrance smoke doors,smoke doors behind the security desk,gymnasium,rm 100&30

    Jul 30, 2019

    Resolve
  • Class - 2

    Reissue #35260396y noted: @the cellar lvl waste storage room #13, electrical room 009, and the 4th floor electrical room, penetration in thewalls & ceiling in various areas.rem: provide/maintain fire stopping

    Jul 30, 2019

    Resolve
  • Class - 2

    Noted:@ 5ht fl(stair c)water damage/leak @ pipe from roof(rm 505&rm 512 hallwy)rem:comply w/code

    Jun 1, 2018

    Resolve
  • Class - 2

    Noted;@4th and 5th floors,springs broken on windows throughout.rem:comply w/code

    Jun 1, 2018

    Resolve
  • Class - 2

    Re-issue nov#3521416k failure to maintain bldg in code compliant manner.no fire stopping @electrical rm(4th fl)@bsmt rm 13 andrm 12.waste s storage closet and rm 009.rem:comply w/code.

    Jun 1, 2018

    Resolve
  • Class - 2

    Reissue #35148130r failure to maintain building walls,or appurtenancesnote:at cellar adjacent to oil tank room.the foundation walls have been porous allowing rain water to enter.remedy:maintain exterior wall

    Jul 11, 2017

    Resolve
  • Class - 2

    Reissue#35221416k failure to maintain bldg code compliant manner. no fire stopping bc 412-3;27-345. note: at electrical room 4th fl @ basement rooms 13,12,waste storage closet electrical room 009. remedy: provi

    Jul 11, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. no fire stopping per bc 712.3;27-345. noted: at electrical room 4th fl @ bsmt room 13,12,waste lamp storage,electrical rm,009. remedy: provide/maintain fire

    Nov 17, 2016

    Resolve
  • Class - 2

    Re-issue 35148130r,failure to maintain bldg walls or appurtenances. noted: at cellar adjacent to oil tank room the foundatuion walls has been porous allowing rain water to enter w/standing water to 1".

    Nov 17, 2016

    Resolve
  • Class - 2

    Re-issue#3514131z failure to maintian bldg walls or appurtenances: noted: at cellar (tummel) to wasr heat transfer (chamber) spalling concrete ceiling & wall allowing rain water to enter. remedy: maintain exter

    Nov 17, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg code compliant:lack of emergency lighting per bc 1006.1;27-542.noted:@mini bldg,inoperative emergency lighting w/battery back up throughout.rem:comply w/code.

    Oct 6, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg exterior wall(s) noted:@cellar tunnel to east(heat) transfer chamber,spalling concrete ceiling & wall allowing rain water to enter.rem:comply w/code.

    Oct 6, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg exterior wall(s) noted:@cellar adjacent to oil tank rm,the foundation wall has become porous allowing rain water to enter w/standing water to (1").rem:comply w/code.

    Oct 6, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg code compliant per bc 1016.2;27-369 noted:@left stage exit stage exit down to exit 4 50% obstruction of passageway w/planks,table,chairs stackled.rem:comply w/code.

    Oct 6, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg code compliant per bc 1016.2;27-369 noted @2 fl adjacent to auditorium,card board display decorations obstruct 50% of corridor passage.rem:comply w/code.

    Oct 6, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg code compliant:lack of emergency lighting per bc 1006.1;27-542 noted:@cafeteria,inoperative emergency lighting w/battery back up over exit doors,5 of seven found defective.rem:comply w/

    Oct 6, 2015

    Resolve
  • Class - 2

    Electrical work without permit. observed at 4:55pm (1) 1600 amp service switch installed in service room in basement. also service entrance conductors, feeders, panels. remedy: obtain permit.

    Jul 28, 2014

    Resolve
  • Class - 2

    Reissue: 34941189z foundation wall has become porous and allowing rain water into the gas and oil tank room causing interior damages at thecellar level. rmdy: water proof foundation wall.

    Jun 17, 2013

    Resolve
  • Class - 2

    Reissue: 34941191h the concrete ceiling is cracked & spalling locatedin the gas meter and oil tank room at the cellar level. rmdy: repair and/or replace concrete.

    Jun 17, 2013

    Resolve
  • Class - 2

    Reissue # 34863571z. concrete ceiling cracked/spalling at: cellar gas meter room, oil tank room. remedy: repair defects noted.

    Feb 16, 2012

    Resolve
  • Class - 2

    Stair landings trip hazards - 9x9 floor tiles cracked/bulging at: landings between floors various stairways & floors throughout. remedy: repair/replace tile.

    Feb 16, 2012

    Resolve
  • Class - 2

    Reissue # 34922022n. water penetrating foundation at: cellar oil tank room & gas meter room ceilings. remedy: maintain water proof integrity of foundation.

    Feb 16, 2012

    Resolve