DOB building violations

22 DOB violations, newest first.

  • Construction other optional

    Borough commissioner has ordered all work stopped underpermit #b00981804-l1 on 10/5/2026. due to construction superintendentwithdrawal

    Oct 16, 2026

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active

ECB violations

The newest 50 of 80 ECB violations. The city keeps the complete history.

  • Class - 2

    Re-issue 35678656j. at the time of inspection, cracks at the right of bulkhead on parapet wall. remedy: repair and/or replace.

    Apr 2, 2026 · Penalty $3,125

    Active
  • Class - 2

    28-301.1. unlawful display of artwork in corridors greater than 20% per fdny 2008 code; fc 803.3.2. at the 4th and 5th floor corridors had excessive artwork, far greater than 20% as permitted by code. remedy: c

    Apr 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Stair and/or floor identification signs missing and/or defective. at the time of inspection, the stairwells on 2nd and 3rd floor did not have designation. 4th floor stairwell did not have designation except for

    Apr 2, 2026 · Penalty $625

    Active
  • Class - 2

    Exit door not self-closing. at the time of inspection, exit discharge e and d were not self-closing. remedy: repair/replace door.

    Apr 2, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. no fire-stopping per bc 712.3-27-345. at the time of inspection, both electrical meter rooms had throughwall/ceiling penetrations. remedy: provide/maintain

    Apr 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection; illuminated exit light at exit "i" was inope

    Apr 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Re-issue 35721278m. at the time of inspection, the oil tank room ceiling had chunks of concrete missing, exposing wire mesh. remedy: repair and/or replace.

    Apr 2, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue 35671839k. at the time of inspection, the bulkhead a/b and c/d had spalling and efflorescence as a result of water infiltration. (2)cracked glass panel in staircase "d" on 5th floor. remedy: repair and

    Apr 2, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8.; 27-371(j). at the time of inspection, the following doors had turn knob handles:-201, 205, 206, 20

    Apr 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Re-issue 35721277k. at the time of inspection, the following doors were not self-closing:-vestibule door to exit "i", vestibule door to exite, (1)door at main entrance vestibule, 2 doors at staircase "c" on 1st

    Apr 2, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.oil tank room broken concrete on wall open hole and broken concrete on ceiling above tanks.rem:repair and/or replace.

    Jul 21, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.classroom door don't close missing hardware 211,313,312,306,304,303,302,301,451,409,410,417,420.rem:repair and/or replace.

    Jul 21, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to provide power for emergency exit lights.emg lights in gym and in lunch room not working when tested.rem:provide adequate power for emergency exit lights.

    Jul 21, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35671842l failure to maintain building in code-compliant manner.noted:at time of inspection i observed at the roof level adjacent tothe bulkhead and the parapet wall has crack on the right side.also the

    Feb 28, 2024 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc1006.1;27-381.noted at stairwell g,on 5th floor,gym rear exit,3rd floor gym,1st floor stair

    Feb 7, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted at roof level,adjacent to bulkhead c and d,the parapet wall has cracks on the right side.also the wall in front of that has running step cracks in var

    Feb 7, 2023 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.noted at rooms# 459,455,420,411,263,259,256,212,and 202 the doors are not working properly.remedy:repair and/or replace.

    Feb 7, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35553680k.noted at bulkhead c and d,4th floor stair a by 401,3rd floor stair e by 356,3rd mid-landing stair e,gym entrance,1st floorcafeteria entrance by stair c,smoke by 111,smoke at playroom stair f a

    Feb 7, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35636424p.noted at various bulkheads throughout the building have cracks and spalling in several places on the walls and ceiling.remedy:repair and/or replace.

    Feb 7, 2023 · Penalty $1,562

    Active
  • Class - 2

    Reissue: 35553679n failure to maintain bldg in code compliant manner: noted: at roof top bulkhead stairway various cracks @ ceiling & walls.remedy: repair & or replace.

    Feb 3, 2022 · Penalty $1,562

    Active
  • Class - 2

    1/4 test plug missing from gas piolit regulator pipe/boiler feed tank pump leaking; correct violation and submit the certificate of correction

    May 4, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing. noted: at roof to bulkheads a/b & c/d selfclosers were non operational/missing when tested. remedy: repair/replace door.

    Mar 29, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. use of prohibited door &/or hardware per bc 1008.1.8(27-371(j). noted: at every level throughout in various locations kick door stoppers installed.

    Mar 29, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner no fire stopping perbc 712.3/27-345. noted: at basement electric meter room fire stopping missing/none throughout in various locations. remedy: provide/maintain

    Mar 29, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors per per bc 1006.1;27-381. noted:at(5th fl)gym(1st fl)indoor playground & cafeteria emergency lights

    Mar 29, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at(1st fl)exits e,f,g & cafeteria door in disrepair racked. remedy: repair &/or replace.

    Mar 29, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at roof top bulkhead stair d/c w/having vertical/horizontal cracks throughout in various locations. also at front entrance stairs/walkway cracked/liftin

    Mar 29, 2021 · Penalty $625

    Active
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at roof level bulkheads water penetration damage to ceilings/walls w/spalling plaster/paint. remedy: repair &/or replace.

    Mar 29, 2021 · Penalty $625

    Active
  • Class - 2

    Operation of a place of assembly w/o a current certificate of operation.noted:@1st flr,auditorium area,the place of assembly.certificate #301578601 posted for 637 person is expired.rem:comply w.code.

    Jun 30, 2016

    Resolve
  • Class - 2

    Operation of a place of assembly w/o a current certificate of operation.noted:@1st flr,cafeteria area,the place of assmebly certificate #301584453 posted for 448 person is expired.rem:comply w.code.

    Jun 30, 2016

    Resolve
  • Class - 2

    Operation of a place of assembly w/o a current certificate of operation.noted:@3rd flr,gym area,the place of assembly certificate #301581465posted for 510 person is expired.rem:comply w.code.

    Jun 30, 2016

    Resolve
  • Class - 2

    Operation of assembly w/o a current of operation.noted:@5th flr,gym area,the place of assembly certificate #301578521 posted for 380 person is expired.rem:comply w.code.

    Jun 30, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner:lack of emergency lighting for exits.exit discharges &public corridors per bc1006.1,27-542.noted:@1st flr cafeteria area &1st flr auditorium area,3rd flr gym ar

    Jun 30, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. failure to provide wired glass vision panels per 27-3716 (b) at time of inspection i observed no wired glass on the following doors:auditorium main entry door

    Jul 7, 2015

    Resolve
  • Class - 2

    27-371(b) reissue 35107645p vision panels.note use of prohibited plexiglass vision in the following doors:auditorium main entry door & rear exit doors,exit d 1st fl,exit i 1st fl,rm 201,207,209,208,202 & 459.re

    Jul 7, 2015

    Resolve
  • Class - 2

    Reissue 35107647z exit door not self closing.the following doors racked:exit stair a/b 1st fl,stair g 1st fl & 5th fl gymnasium door.rem repair or replace door

    Jul 7, 2015

    Resolve
  • Class - 2

    Exit doors not self-closing at t-1,t-5,t-6,t-7. rmdy: repair or replace door.

    Aug 11, 2014

    Resolve
  • Class - 2

    Exit doors not self closing; following doors are racked or exit stair a/b 1st floor stair "g" 1st flr and 5th fl gymnasium door. rmdy: repair or replace door.

    Aug 11, 2014

    Resolve
  • Class - 2

    Failure to maintain. failure to provide support for air conditioning units in the following locations 3rd fl(room 303), at atkins avenue side 4th fl (room 419) at playyard area, 2nd flr (teachers lounge) at

    Aug 11, 2014

    Resolve
  • Class - 2

    27-371(b) reissue 35012370n vision panels. use of prohibited plexiglass vision panels in the following doors: auditorium main entry door and rear exit doors (aud), exti d 1st fl, exit i 1st fl, rm 201,206,207,

    Aug 11, 2014

    Resolve
  • Class - 2

    Sec. 27-371(b). plexi-vision panels installed on doors to rms 305,263,209,208,206,202,201 and on deck to stair g 3rd flr gym. remedy: provide required glass panels.

    Mar 7, 2013

    Resolve
  • Class - 2

    Reissue #34954454n plaster spalling on walls of stair a&b at 495 flr wlevel, in room 580 (gym office) and in rooms 401,403 & 407. also ceiling damaged in library rm 307 at pipe penetration from boys restroom

    Mar 7, 2013

    Resolve
  • Class - 2

    The plaster on stair a & b is spalling located in between the 4th & 5th flr level & room 560 (gym office) on the 5th flr level. remedy: repair/replace plaster.

    Apr 19, 2012

    Resolve
  • Class - 2

    The plaster on the walls & ceiling is spalling located in rooms 401,403,407 & 408 (4th flr level). remedy: repair/replace plaster on wall.

    May 27, 2011

    Resolve
  • Class - 2

    Exterior brick facade has become porous & allowing rain water into bldg causing interior damages in room 401,403,407,408 on the 4th flr level. remedy: water-proof exterior brick facade.

    May 27, 2011

    Resolve
  • Class - 2

    Interior wood trim at transportables t-2 is loose and hanging. remedy:repair and/or replace wood trim.

    May 19, 2010

    Resolve
  • Class - 2

    Exterior wooden ramp & stairs @ the transportables is rotten & fallingapart by t-1 & t-2 in the school yard.remedy:repair and/or replace wooden ramp/steps.

    May 19, 2010

    Resolve
  • Class - 2

    Interior concrete ceiling is cracked and spalling located at basement level under exit 6 & exit 1.rem:repair and/or replace concrete.

    May 19, 2010

    Resolve
  • Class - 2

    Reissue:34744027n. the plaster is spalling off the wall located in room 460,401 (4th fl) & room 560 & 514 (5th floor) & roof bulkheads. remedy:repair and/or replace plaster.

    May 19, 2010

    Resolve
  • Class - 2

    Reissue: 34646403z. use of prohibited door and/or hardware. noted: illegal hardware door at exit "c" have key cylinder locks. remedy: provide legal hardware.

    Apr 30, 2009

    Resolve