roofy

2045 Linden Boulevard

Brooklyn, NY 11207BBL 3-04327-0024Map

Owner of record: 2045 Linden LLC

2045 Linden Boulevard is a school building built in 1973 in Brooklyn, 11207. The owner of record is 2045 Linden LLC. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
25
ECB violations
51
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 25

  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 2, 2020

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 9, 2018

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Construction other optional

    Owner resp to keep bldg in safe cond,foll vehicular collision into east stairwell at sideyard 3/23/17.the impact damaged the brick cavity wall facade&cmv backup wall.remedy:owner retain pe engr eval collision area,& prep plans&obtain perm for perm repairs of masonry or other defects by 4/21/17.engage dob reg cont'r to subst comp work by 5/12/17

    Mar 28, 2017

    Dob violation - dismissed
  • Construction other optional

    Due to vehicle crashing itno egress stairwell on exposure # 4 ( miller avenue ) exteriro block wall damaged on ist floor level

    Mar 23, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 5, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 6, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 28, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 27, 2009

    Dob violation - active
Show 15 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 25, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 19, 2005

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 19, 2003

    Dob violation - resolved
  • Elevator elevatorrequired

    3p6816

    Aug 30, 2002

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 6, 1998

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 1996

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 17, 1995

    Dob violation - dismissed
  • Public assembly none

    Pa-public assembly none

    Sep 2, 1994

    Vp*-violation unserved ecb- dismissed
  • Public assembly none

    Pa-public assembly none

    Sep 2, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - dismissed

ECB violations · 51

  • Class - 2

    Reissue#35721182h at the time of inspection,the following emergency lights were not operable #40,#43,#37,4 lights in cafeteria,3 lights in gym,#41(1 blown bulb).rem:repair/replace lighting.

    Mar 31, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).aat the time of inspection,the following room doors had then knob handles 301,305,308,310,2

    Mar 31, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.at the time of inspection,spalling and efforesence was observed at clerestory window in stairwell a on 3rd floor.rem:repair and/or replace.

    Mar 31, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing.at the time of inspection exit discharge#5 was not self-closing.rem:repair/replace door.

    Mar 31, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1(2014 code); 27-381, bc 1008.1(2022 code). noted at 3 floor box #40, 43, stair b,

    Jul 15, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.noted the door to room 220,209,120,and 121 are not working properly.remedy:repair and/or replace.

    Jan 26, 2023 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing.noted on 3rd floor corridor by 315,306,stair b,1st floor gym exterior door at exit 5,the doors are not working properly.remedy:repair/replace door.

    Jan 26, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:illumination forexits,exit discharges,and public corridors per bc1006.1;27-381.noted at the cafeteria em#12 and 21 and 1st floor exit sign by the elevator b

    Jan 26, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner no fire stopping perbc 712.3/27-345. noted: at 1st fl gas b& electric meter room fire stopping missing none w/holes & opening throughout in various locations.

    Apr 5, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at 1st fl gas meter rm storage of various items file cabinet,toiletries,boxes etc.remedy: comply with code.

    Apr 5, 2021 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors per bc 1006.1/27-281. noted: at 1st fl gym & cafeteria emergency lights were non operational when test

    Apr 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to mintain bldg in code compliant manner. noted: at 1st fl gymdoor in disrepair/racked. remedy: repair &/or replace.

    Apr 5, 2021 · Penalty $625

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor

    Apr 3, 2020 · Penalty $6,250

    Active
  • Class - 2

    Failure to maintain building in code compliant manner () bathroom on 3rd floor 316 stall broken busted masonry wall broken tiles missing. rmdy: repair replace

    Feb 25, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. noted at 3rd floor,bulkhead area,missing, broken, soiled ceiling tiles. rmdy:repair/repl ace ceiling tiles.

    Jan 26, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. noted at electricalroom, storage of 4 shopping carts. rmdy: remove illegal storage fromelectrical room.

    Jan 26, 2018

    Resolve
  • Class - 2

    Unlawful display of artwork in corridors greater than 20% per fdny 2008 code; fc 803.3.2 noted: artwork displayed in corridors throughout the bldg is greater than 20% alllowed.rmdy:comply w/nov.

    Jan 26, 2018

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances.noted:room 301 on linden blvd side,water coming in from the side of the wall,also water is coming from the bulkhead ceiling.rem:maintain exterior building w

    Apr 4, 2017

    Resolve
  • Class - 2

    Re-issue 35194631m. failure to maintain bldg in code compliant manner:lack of emergency lighting for exit, exit discharges & public corridorper bc 1006.1; 27-542. noted: @ laundry room 1 emergency lighting with

    Apr 4, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner:lack of emergency lighting for exits,exit discharges & public corridor-per bc 1006.1;27-542 noted @lunch room 3 emergency lighting w/battery back up observed i

    May 4, 2016

    Resolve
  • Class - 2

    Re-issue#35107634j exit doors not self-closing front entry doors racked & do not self-close.rem:repair or replace doors.

    Jun 24, 2015

    Resolve
  • Class - 2

    27-369 combustibles excessive combustibles on corridor walls @ 2nd fl on 3rd fl combustibles protruding from corridor walls.rem:remove combustibles.

    Aug 8, 2014

    Resolve
  • Class - 2

    Exit doors not self closing.main front ext entry doors not self closing due to door checks.rem:replace door checks.

    Aug 8, 2014

    Resolve
  • Class - 2

    Water penetrating through roof causing damage to ceilings at stair 'a'& rm 301. remedy: make necessary repairs.

    Aug 30, 2013

    Resolve
  • Class - 2

    Excessive combustible art work & signage on walls of corridors at 2&3 flrs, and in stairs a&b. rmdy: remove combustibles.

    Mar 11, 2013

    Resolve
  • Class - 2

    Water damage ceiling tiles due to roof leak in room 301 and at stair a3rd floor. rmdy: make all necessary repairs.

    Mar 11, 2013

    Resolve
  • Class - 2

    Exterior door at stair b racked and sticks. door at cafeteria (room 125) closer partially detached. rmdy: make all necessary repairs.

    Mar 11, 2013

    Resolve
  • Class - 2

    School staff members are parking their vehicles on school property by entering at pedestrian crosswalk, located at miller ave & linden blvd.remedy: discontinue parking vehicles on school property.

    Apr 27, 2012

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.noted:@ the 1st flr level custodian's office gas meter room is lacking fresh air ventilation.provide fresh air ventilation to gas meter rm.comply w/bldg code.re

    Apr 6, 2011 · Penalty $500

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.no fire stopping perbc 712.3;27-345 noted:failure to provide adequate firestopping betwee n custodians office,gas meter rm & eletrcial panel rm.rem:provide/main

    Apr 6, 2011

    Resolve
  • Class - 2

    Occupancy contrary to that allowed by the cofo or bldg dept records.noted:@ exposure 4 exterior sideyard(open lot)on linden blvd & miller ave is being used as a school parking lot for approx 8 cars contrary to

    Apr 6, 2011 · Penalty $1,200

    Resolve
  • Class - 2

    The electrical room is being used as a storage room consisting of a chair, file cabinets on the 1st flr level. remedy: remove stored items.

    Apr 20, 2010

    Resolve
  • Class - 2

    Exterior children's playground area on linden blvd & miller ave is being used as a parking area w/marked spots (8 spots). 5" curb was removed for entrance for cars. remedy: remove cars at play area.

    Apr 20, 2010

    Resolve
  • Class - 2

    Interior gas room is lacking fresh air ventilation at the 1st flr level. remedy: provide/maintain fresh air ventilation.

    Apr 20, 2010

    Resolve
  • Class - 2

    Exterior roof has become porous and allowing rain into the bldg causing interior damages in rm 301 on the 3rd flr level. remedy: water-proofexterior roof.

    Apr 28, 2009

    Resolve
  • Class - 2

    Reissue: 34563904n. corridor smoke doors do not close properly next torm 314 on the 3rd flr. noted: door hinge is defective causing door to be out of plumb. remedy: repair/replace doors.

    Apr 28, 2009

    Resolve
  • Non-hazardous

    Reissue 34563904n defective doors 1,2,3 fl corridor doors hitting doorframe also 1 fl vestibule doors on exit b door hitting frame remedy: repair/replace door

    Jun 5, 2008

    Resolve
  • Non-hazardous

    Use of illegal hardware. fire/smoke doors in corridors 2nd floor, 3rd floor have passage locks on them. remedy: remove illegal hardware.

    Mar 8, 2007

    Resolve
  • Non-hazardous

    Failure to maintain- interior. doors that are racked in the frame & can not close properly 1st fl- stairway a- 1 door. 2nd fl- stairway a- 1door. fire/ smoke doors in corridor by rms #208- 1 door, #211- 2 doors

    Mar 8, 2007

    Resolve
  • Non-hazardous

    Failure to maintain- interior. re-issue #34510367h locations of doors that are racked & do not close properly fire/ smoke doors in cooridors by rm #213, 305, 307, 314. remedy: repair/ replace doors.

    Mar 8, 2007

    Resolve
  • Non-hazardous

    Exit door adjacent to room 108 is sheared at hinge connection causing door to be racked. defective door 3rd flr exit to roof opposite room 311, and opposite to room 307. corridor doors adjacent to room 213 are

    Feb 28, 2006

    Resolve
  • Non-hazardous

    "reissue" (34386120k).failure to maintain.defects are:roof leaks at various locations.locations are:1)bulk head 2)3rd floor corridor between room #311 and exit door.3)corridor between rooms #308 and 323.4)roof

    May 20, 2004

    Resolve
  • Non-hazardous

    "reissue" (34386121m).failure to maintain.defect is bulkhead east side sheetrock wall loose and bulging.remedy:repair wall.

    May 20, 2004

    Resolve
  • Non-hazardous

    "reissue". (34386122y).failure to maintain.deffects are:2nd and 3rd floor girls bathroom metal partitions are corroded.remedy:replace bathroom partitions.

    May 20, 2004

    Resolve
  • Non-hazardous

    Failure to maintain.defect is:roof leaks at various locations.remedy:maintain bldg make all repairs

    Jan 20, 2004

    Resolve
  • Hazardous

    Failure to maintain defects are 2 and 3 floors girls bathrooms metal stall dividers are rotten and defective with sharp edges. remedy; replace bathroom stall dividers.

    Feb 26, 2003

    Resolve
  • Non-hazardous

    Failure to maintain defect is bulk head east side sheetrock wall loose and bulging. remedy; repair wall.

    Feb 26, 2003

    Resolve
  • Non-hazardous

    Failure to maintain defects are roof leaks at various locations 1, bulk heas 2, 3 floor corridor between room #311 and exit doors 3, corridor between rooms #308 and 323, 4, roof leaks in room #324 and library.

    Feb 26, 2003

    Resolve
  • Non-hazardous

    Failure to maintain defect is: roof leaks at 3rd fl hallway adjacent to stairwell. remedy: repair roof/stop water penetration. repair damaged drop ceiling.

    May 8, 2001

    Resolve
  • Non-hazardous

    Failure to maintain defects are: (1).crack brick support columns at the front of building.(2).roof leaks at various locations.(3).defective drop-ceiling acoastic tiles.remedy: maintain building, make all repair

    May 8, 2000

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1973
Floors
3
Residential units
—
Building area
42,112 ft²
Lot area
19,000 ft²
Zoning
R6
Community board
305
Council district
42
Block / lot
4327 / 24
Assessed value
$2,959,650
Landmark / historic district
No

Questions about 2045 Linden Boulevard

Who owns 2045 Linden Boulevard?

The owner of record in NYC Department of City Planning PLUTO data is 2045 Linden LLC.

Does 2045 Linden Boulevard have violations?

NYC HPD has no housing violations on record for this property.

Is 2045 Linden Boulevard rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 2045 Linden Boulevard built?

City records list 1973 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.