roofy

158 Richmond Street

Brooklyn, NY 11208BBL 3-04126-0047Map

Owner of record: NYC Department Of Education

158 Richmond Street is a school building built in 1870 in Brooklyn, 11208. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
19
ECB violations
33
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 19

  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
Show 9 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    May 27, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed

ECB violations · 33

  • Class - 2

    Reissue ecb#35721187r failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 1st fl exit 4 emergency light not working wh

    Mar 30, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted 2 floor 207, 1fl. 106, basement smoke exit 2 and 3, doors are not closing properly. remedy: repair and/or replace.

    Jul 11, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits; exit discharges and public corridors per bc 1006.1; 27-381. noted at 1 floor exits 4 and 6 emergency lights are inoperable. remedy:

    Jul 11, 2025 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self closing.noted:observed at exit door #4 door not operational at time of inspection to open it is more than allowed.remedy:repair/replace door.

    Jan 13, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination for exits exit discharges and public corridors per bc 1006.1; 27.381 at basement level em #8 next to girls' bathroom stair c exterior door.reis

    Feb 4, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.no fire stopping per bc 712.3; 27-345 at electrical meter room several holes in different area at cellar/basement reissued #35546516n(3/30/2021)remedy:provi

    Feb 4, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Stair and/or floor identification sign missing and/or defective @ exterior exits door(s) #9 inside and in various doors in different locations.reissue #35546518r(3/30/2021)remedy:install and/or repair signs.

    Feb 4, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self-closing stair c by exit door stair d(2nd fl) room 207 exterior door #8 by girls' bathroom.reissue #35546515l (3/30/2021)remedy:repair/replace door.

    Feb 4, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: no fire stopping per bc 712.3;27-345. noted: at the basement level electrical meter room;has holes in the wall above the entrance door in various areas through

    Mar 30, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Exit door not self closing. noted: at stair d by 207,stair c exterior exit door,& basement level exterior exit door #8 by the girls restroom;the doors are not working property. remedy: repair/replace door.

    Mar 30, 2021 · Penalty $625

    Resolve
Show 23 more ↓
  • Class - 2

    Stair &/or floor identifiction signs missing &/or defective. noted: atthe exterior exit doors are missing identification numbers,etc exit 9.on the interior side of the bldg on various doors throughout the bldg.

    Mar 30, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner;illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: at stair c by the exterior exit door & basement level em#8 by the girls

    Mar 30, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors as per bc1006.1;27-381.noted:at cellar(5)existing emergency lights are not working operational wh

    Apr 6, 2017 · Penalty $530

    Resolve
  • Class - 2

    Reissue #35129157n failure to maintain in code-comliant manner.noted:@boilerroom mortar deteriorating @brick wall.rem:make necessary repairs.

    May 2, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.noted:@2nd fl next to room 201 above the ceiling spalling paster.rem:make necessary repairs.

    May 2, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner:@ cellar level in boiler/gas meter room:mortar deteriorating @ brick wall.rem:repointing required.

    Jun 12, 2015

    Resolve
  • Class - 2

    27-371(b)vision panels:the following rooms have vision panles painted over or are not provided.room 201,101,102,100,107 & 108.rem:provide required glass panel or remove paint.

    Jun 12, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.failure to provide wired vision panels glass per 27-371(b)the following doors do not have required wired glass rm 201,101,102,100,107 and 108.rem:provide wired

    Jun 12, 2015

    Resolve
  • Class - 2

    Reissue 35013128j.use of prohibited door hardware.stair a&b being heldopen by hook & eye hardware @ 2nd floor.kick down dor steps installed on doors throughout 1st floor rm 206 kitchen & other places.rem:remove

    Aug 7, 2014

    Resolve
  • Class - 2

    Fail to maintain.water penetration creating plaster spalling in rooms 104,207,206,204.rem:maintain walls/plaster.

    Aug 7, 2014

    Resolve
  • Class - 2

    Fail to maintain.water penetration from roof/exterior into several classrooms:rooms 204,206,207&104.rem:maintain exterior.

    Aug 7, 2014

    Resolve
  • Class - 2

    Kick down door stops installed on doro to rooms 104,105,106,107,206, kitch,boiler room, and various other places.rmdy: remove door steps.

    Feb 20, 2013

    Resolve
  • Class - 2

    At stair c 2st floor leading to exit handrail is disconnected from mounting bracket at top end of stair. remedy: repair or replace handrail.

    Feb 20, 2013

    Resolve
  • Class - 2

    Reissue : 34770764m exterior foundation wall has become porous and allowing rain water to entering the building causing interior damages in the gas meter room @ cellar level. remedy: water proof exterior founda

    Apr 15, 2010

    Resolve
  • Class - 2

    Foundation wall has become porous and allowing rain water into the gasmeter room causing interior damages at cellar level.remedy:water proofexterior foundation wall.

    Apr 22, 2009

    Resolve
  • Class - 2

    2fl corridor hallway is storing tables, chairs, book. remedy:remove stored items.

    Apr 22, 2009

    Resolve
  • Hazardous

    Defective doors multiple doors leading to stairways thru-out entire school doors hitting fl door frame remedy:repair replace doors

    Jun 3, 2008

    Resolve
  • Non-hazardous

    Failure to maintain.defects are roof leaks in attic and room #107.remedy:repair roof

    Jun 3, 2004

    Resolve
  • Non-hazardous

    Failure to maintain.defect is wall plaster in room #107 loose and bulging.remedy:repair wall plaster

    Jun 3, 2004

    Resolve
  • Non-hazardous

    Failure to maintain.defect is room #202 sheet rock walls not tape.remedy:tape sheetrock walls

    Jun 3, 2004

    Resolve
  • Non-hazardous

    Failure to provide emergency lighting fixture within corridor and stair(4) on 2nd & 3rd floor-failure to provide emergency power for lighting fixture within corridor & stair (4) on floor 2 & 3 remedy:provide em

    Aug 21, 2001

    Resolve
  • Non-hazardous

    Failure to maintain. defects are: 1) defective window found throughoutschool. 2) interior/exterior doors and frames needs to be upgraded. 3)the roof upper floor leaks at various locations. remedy: maintain bldg

    Aug 11, 2000

    Resolve
  • Non-hazardous

    Failure to maintain building. defect is windows not operable in cafeteria kitchen and paint peeling in cafeteria ceiling throughout. repair or replace.

    May 27, 1999

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1870
Floors
2
Residential units
—
Building area
8,228 ft²
Lot area
15,000 ft²
Zoning
R4
Community board
305
Council district
37
Block / lot
4126 / 47
Assessed value
$370,350
Landmark / historic district
INDIVIDUAL LANDMARK

Questions about 158 Richmond Street

Who owns 158 Richmond Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 158 Richmond Street have violations?

NYC HPD has no housing violations on record for this property.

Is 158 Richmond Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 158 Richmond Street built?

City records list 1870 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.