Violations at 126 Atkins Avenue
Brooklyn, NY 11208 · BBL 3-03990-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
32 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - dismissed - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 in 2020
Jun 20, 2021
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 9, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 29, 2008
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 2, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 4, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 22, 2005
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Nov 19, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 21, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations
The newest 50 of 69 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner. lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1; 27-542. noted: at (3rd fl)gym rm 311 not installed/provided with
Mar 27, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: at through (roof to 1st fl)stair b with water damage/staining to ceilings/walls with spalling paint/plaster. remedy: repair and/or replace.
Mar 27, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: at (1st and 2nd floor)hallway installed/hung non-fire retartent decorations toceilings. remedy: comply with code.
Mar 27, 2026 · Penalty $1,250
Active - Class - 2
Reissue ecb #35721162k. failure to maintain building in code-compliantmanner. noted: (1st fl)smoke door/exits 8, 9, 10, 6 doors in disrepairof saddles/frame. remedy: repair and/or replace.
Mar 27, 2026 · Penalty $3,125
Active - Class - 2
Reissue ecb #35721163m. exit door not self-closing. noted: at (1st fl)auditorium, exit 1, 2, stair a, c doors in disrepair/not closing. remedy: repair/replace door.
Mar 27, 2026 · Penalty $1,562
Active - Class - 2
Reissue ecb #35721165x. failure to maintain building in code-compliantmanner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. notes: at (1st fl)auditorium, gym, cafeteria eme
Mar 27, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:observed during inspection of 3rd floor stair a by rm 338,were not self closing due to defective/missing hardware.rem:repair and/or replace.
Jan 19, 2023 · Penalty $625
Resolve - Class - 2
Reissue#35644326l(2/1/22)failure to maintain building wall(s)or appurtenances.noted:observed at cellar level by elevator room water penetration,wall have become porous allowing water info space,causing rusting
Jan 19, 2023 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building walls & appurtenances at cellar level elevator water penetration through walls.reissue#35542767(03/29/2021).rem:repair/seal foundation walls.
Feb 1, 2022 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code-compliant manner:exit 4 & 5 by room 111,stair e by room 313,stair a by 236,b by rm 250 etc.reissue#35542768l(3/29/2021)rem:repair/and or replace.
Feb 1, 2022 · Penalty $1,562
Resolve - Class - 2
Exit door not self closing. noted: observed during inspection exteriorexit door#7,was not self closing,also it would not open w/o extreme amount of pressure to force it to function properly. remedy: repair/rep
Mar 29, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: observed during inspection fire proof self closing doors at stair c by r 313,stairb by rm 250,stair a by rm 236,stair c by rm 111,exit 4 & 5 by room 111
Mar 29, 2021 · Penalty $625
Resolve - Class - 2
Reissued#35498366n failure to maintain bldg walls or appurtenances. noted: observed during inspection at the cellar level,foundation wall bythe elevator is porous & allowing water to penetrate through.
Mar 29, 2021 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building wall(s) or appurtenances.re-issue ecb#35383985m,issued 2/5/19.noted:exterior foundation wall water penetrate onto walls of cellar level elevator(street elevator)door is rusted.remed
Jun 16, 2020 · Penalty $3,125
Resolve - Class - 2
Mobile boiler and oil tank onsite without dob+dot+fdny permits displayed-boiler#+inspection not displayed-no keys onsite for safety fence and mobile boiler for inspection access, maintain boiler; correct viola
May 17, 2019
Resolve - Class - 2
Reissue 3523562j (3/23/17) failure to maintain bldg walls or appurtenances. note: exterior foundation wall water penetrate onto walls of cellar level elevator (street elevator). rmdy: maintain exerior building
Feb 5, 2019
Resolve - Class - 3
Reissue 35297722j failure to maintain building in code compliant manner noted: 1st floor cafeteria and gym exit doors is not close properly due to warping and cannot close properly. rmdy:repair and/or repl
Feb 5, 2019
Resolve - Class - 3
Reissue 35297723l (1/23/18)failure to maintain bldg in code compliantmanner. various locations of windows throughout the bldg are defectivecannot open or close. rmdy: repair and/or replace.
Feb 5, 2019
Resolve - Class - 3
Failure to maintain bldg in code-compliant manner.various windows trhroughout bldg are defective making them hard to open/close.rem:comply w/summons
Jan 23, 2018
Resolve - Class - 3
Failure to maintain bldg in code-compliant manner.1st fl exit door at cafeteria and gym are racked and warping not allowing to be open/closed properly.rem:comply w/summons
Jan 23, 2018
Resolve - Class - 2
Reissue# 35177855r. failure to maintain bldg in code compliant manner, bldg walls or appurtenances. exterior foundation wall has become porous allowing water to penetrate into sidewall of cellar level by elevat
Mar 23, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant walls & appurten. reissued#35129095k. note: exterior foundation wall has become porous allowing rain water to penetrate into sidewall of cellar level next to elevator
Apr 12, 2016
Resolve - Class - 3
Failure to maintain bldg in a code compliant manner. failure to provide 1/4" thick wired glass vision panel where required as per 27-371 (b).note: @ time of insp @ room doors 101,102,103,104,105,107,110,112,130
Apr 12, 2016
Resolve - Class - 2
Failure to maintain bldg code-compliant manner.failure to provide wired vision panel glass as per 27-371(b)noted non-compliance at the following doors.101,102,103,104,105,107,110,112,130,132,134,136,350,250,248
Jun 8, 2015
Resolve - Class - 2
Re-issue 35013482m failure to maintian bldg walls or appurtenances.exterior foundation wall has became porous allowing rain water to penetrate into sidewall at cellar level next to elevator machine room.rem:wat
Jun 8, 2015
Resolve - Class - 2
27-371 reissue 35107102z.vision panels use of prohibited plexiglass in the following doors.101,102,103,104,105,107,110,112,130,132,134,136,250,248,246,224,242,229,228,221,212,214,208,207,206,205,204,203,202,201
Jun 8, 2015
Resolve - Class - 2
Fail to maintain exterior.@ main entry @ brick step out:cracks in brick & @ underside concrete spalling.rem:maintain exterior.
Jul 29, 2014
Resolve - Class - 2
Fail to maintain.plaster spalling @ ceiling of stage @ auditorium & @ ceiling in room 331.rem:maintain interior.
Jul 29, 2014
Resolve - Class - 2
27-766 fresh air in gas meter room.no fresh air vent in gas meter room.rem:provide fresh air.
Jul 29, 2014
Resolve - Class - 2
Fail to maintain.the following class rooms doors do not have required glass or any vision panels:rooms:234,238,331,311,309.rem:provide required glass panels.
Jul 29, 2014
Resolve - Class - 2
27-371(b)re-issue 35013476x vision panels plexiglass vision panels throughout bldg & @ rear of auditorium & classroom exits leadings to playard.broken glass panels @ same stair entrances.rem:provide required gl
Jul 29, 2014
Resolve - Class - 2
Re-issue 35013478j fail to maintain fire-stopping.holes in masonry wall bet gas rm & elect room @ pipe penetrations missing fire stopping.also in boiler room to crawl space/storage room.rem:provide/maintain fir
Jul 29, 2014
Resolve - Class - 2
Re-issue 35013481k exit doors not self closing.the following doors do not close or are racked:exterior doors to playground from rooms 136/134 & 132/130,104/102 lunch room exit doors.exterior exit 7,exterior 4/5
Jul 29, 2014
Resolve - Class - 2
Reissue 34933319h water penetrating in through foundation wall @ sidewall,elevator, water present on flr of cellar at time of inspection. rem: make necessary repairs.
Feb 27, 2013
Resolve - Class - 2
Doors at exit 6, exit 4 & corridor doors @ 2nd flr across from rm 236 are racked preventing them from closing properly and exterior exit doors at exit 4 are swelled & dont open. rem: repair or replace doors.
Feb 27, 2013
Resolve - Class - 2
Hole in masonry wall connecting gas a electric rooms and at pipe penetrations without fire stopping. rem: provide fire stopping.
Feb 27, 2013
Resolve - Class - 2
Exit lights in auditorium above entrance and at gym exit leading to school yard are not working. rem: repair or replace lights.
Feb 27, 2013
Resolve - Class - 2
28-371 (b) plexi vission panels installed on all classroom doors throughout building. rem: provided required glass panels.
Feb 27, 2013
Resolve - Class - 2
Exterior foundation wall has become porous & allowing rain water into the building causing interior damages located at the cellar level by the sidewalk elevator. remedy: water proof exterior foundation wall.
Feb 14, 2012
Resolve - Class - 2
Failure to provide fresh air ventilation in the gas meter room @ the cellar lvl rem: provide fresh air vent to gas meter room
Mar 10, 2011
Resolve - Class - 2
The plaster on the wall is spalling located in room 211 ( library ) 2nd fl remedy: repair and / or replace plaster
Apr 7, 2010
Resolve - Class - 2
Exterior metal grill adjacent to the sidewalk is bent out of shape leaving open gaps located on atkins ave remedy: repair and / or replace metal grill
Apr 7, 2010
Resolve - Class - 2
The electrical room (c17) is lacking fire-stopping located at cellar level. remedy: provide/maintain fire-stopping.
Apr 21, 2009
Resolve - Class - 2
The gas meter room (c13) does not have fresh air ventilation located at cellar level. remedy: provide fresh air ventilation.
Apr 21, 2009
Resolve - Class - 3
50. low pressure steam heating boiler #2. 50 referenced boiler structure has an elevation in excess of 8 feet. there is no provision for safe access to the top of the unit by operations maintenance and inspecti
Nov 25, 2008
Active - Class - 3
50. low pressure steam heating boiler #1. 50 referenced boiler structure has an elevation in egress of 8feet. there is no provision for safeaccess to the top of the unit by operations, maintenance and inspectio
Nov 25, 2008
Resolve - Hazardous
Use of illegal hardware. on bulk head doors exiting to roof, the doorshave keyed locks. remedy: remove illegal hardware.
Feb 27, 2007
Resolve - Hazardous
Failure to maintain-exterior. doors that have broken closers. 1st floor-room 130-1 door, 2nd floor-staircase b-1door, 1st floor-custodian door needs crow bar to open his door. remedy: repair/replace doors.
Feb 27, 2007
Resolve - Hazardous
Failure to maintain-exterior under construction water penetration through exterior wall into staircase #3 & into room #250 & #350 causing water damage. reissue #34474576z. remedy: repair water damage, water
Feb 27, 2007
Resolve - Hazardous
Partial reissue #34508962j. failure to maintain - exterior at roof -3 areas - approx. 100 % each missing insulation & gravel. remedy: replace insulation & gravel.
Feb 27, 2007
Resolve