200 Linwood Street

Brooklyn, NY 11208BBL 3-03926-0045Map

Owner of record: NYC Department Of Education

200 Linwood Street is a school building built in 1895 in Brooklyn, 11208. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
19
ECB violations
85
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 19

  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    May 20, 1999

    Dob violation - active
  • Construction other optional

    C-construction other optional

    May 20, 1999

    Dob violation - active
  • Construction other optional

    C-construction other optional

    May 20, 1999

    Dob violation - active
  • Construction other optional

    C-construction other optional

    May 20, 1999

    Dob violation - active
Show 9 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Apr 5, 1993

    Vpw-violation unserved ecb-work without permit-active
  • Construction other optional

    C-construction other optional

    Apr 5, 1993

    Vpw-violation unserved ecb-work without permit-active
  • Construction other optional

    C-construction other optional

    Aug 18, 1992

    Vp-violation unserved ecb-active

ECB violations · 85

  • Class - 2

    Re-issued 35721153z. at the time of inspection, the following doors are not self-closing-402, 401, 404, 411, 311, 307, 304, 306, 301, 202, 204, 205, 212, 109, 102, vestibule door at main entrance, vestibule doo

    Mar 25, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issued 35721155m. at the time of inspection there was water infiltration in rooms in rooms 410, 404, 306, staircase "d" as a result of defective roof. remedy: maintain exterior building wall.

    Mar 25, 2026 · Penalty $6,250

    Active
  • Class - 2

    Re-issued 35721152r. at the time of inspection, emergency light #29 incafeteria was inoperable emergency light #37 in staircase "c" was inoperable. emergency light #31 in staircase was inoperable, 2 emergency l

    Mar 25, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8, 27-371(j). at the time of inspection, the following doors had turn knob hardware:-402, 401, 403, 41

    Mar 25, 2026 · Penalty $1,250

    Active
  • Class - 2

    28-301.1. unlawful placement of furnishings, decorations or other objects at exits, that obstruct access to egress from or visibility thereof per fdny 2008 code; 1027.4. at the time of inspection, security desk

    Mar 25, 2026 · Penalty $1,250

    Active
  • Class - 2

    28-301.1. unlawful display of artwork in corridors greater than 20% per fdny 2008 code; fc 803.3.2. at the time of inspection, the 2nd and 1st floor corridors had excessive amount of artwork exceeding 20% as pe

    Mar 25, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public-corridors per bc 1006.1; 27-381. noted: at cafeteria at exit 1, one emergency exit lighting found inoper

    Jul 16, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: following class rooms, door closer are missing class room 108, 210, 207, 204, 303, 304, 307, 309, 310, 311. remedy: repair/replace door.

    Jul 16, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building wall(s) or appurtenances. noted: ceiling leak at staircase "d" at 4th floor, room 410, 404, 306 due to defective roof. remedy: make necessary repairs.

    Jul 16, 2025 · Penalty $2,500

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at cellar exit-4, one smoke door do not open/close properly. remedy: repair/replace door.

    Jul 16, 2025 · Penalty $1,250

    Active
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted: class room #108 has kick down door holders attached to the door. remedy: remove i

    Jul 16, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35644194z failure to maintain building in code-compliant manner.noted:at 4th fl.roof leak causing damage to the ceiling in room 410 and stairway ceiling.rem:repair and or/replace.

    Jan 20, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at electrical room at cellar,illegal storage of chairs,desk.rem:remove illegal storage from electrical meter room.

    Jan 20, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manne.noted:at 4th fl all the classroom doors are missing door closers.rem:repair/replace door.

    Jan 20, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1,27-381 reissue35546474y(2/5/21)@4fl auditorium&gym.repair/replace lighting

    Jan 28, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner reissue35546526r(2/5/21) gas&electric rm illegal items in storage use.repair&/replace (remove items illegally from storage)

    Jan 28, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:reissue35546472k(2/5/21)@14fl staird.water penetration thru ceiling cause spalling&paint stains.repair &/or replace

    Jan 28, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at(basement level)gas & electric meter rooms storage at various items/materials deck,chairs,boxes,ladders,construction equipment etc. remedy: comply wit

    Feb 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing. noted: at(1st fl)main entry(double doors)&(basement)stair f door checks in disrepair/non operational when tested. remedy: repair/replace door.

    Feb 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors per bc 1006.1/27-381. noted: at (4th fl)auditorium &(basement)cafeteria/gum emergency lights were non

    Feb 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at(4th fl)stair d water penetration/damage to ceiling w/spalling plaster/paint & staining. remedy: repair &/or replace.

    Feb 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at(1st fl)main entry(double doors)&(basement)stairs b,d doors in disrepair/racked.remedy: repair &/or replace.

    Feb 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35381273p date of issue 1-31-20. failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridirs per bc 1006.1'27-381. in 4th fl auditorium 3 place each place

    Mar 19, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35381271l date of issue: 1-31-19 failure to maintain bldg in code compliant manner no fire stopping per bc 712-3;27-345 no fire stopping at 1st fl corridors which 3 electrical conduit(pitting)in very

    Mar 19, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#34381272n date of issue: 1-31-19 failure to maintain bldg in code compliant manner 1st through 4th fl pipings(electrical)show gap inoutside of electrical conduits. remedy: repair &/or replace.

    Mar 19, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued 35311563j; failure to maintain building in code compliant manner; lack of emergency exits lighting inoperable in gym, auditoriumlunch rooms. rmdy: repair and/or replace lighting.

    Jan 31, 2019

    Resolve
  • Class - 2

    Reissued #35177338z; fail to maintain building in code compliant man ner: 1st through 4th floors pipings (electrical) show gap in outside of electrical conduits. rdy: repair and/or replace.

    Jan 31, 2019

    Resolve
  • Class - 2

    Reissued 35311561x. no firestopping at 1st floor corridors which 3 electrical conduit piping in vary sized. rmdy: provide/maintain fire stopping.

    Jan 31, 2019

    Resolve
  • Class - 2

    Re-issue#35177338z.failure to maintain bldg in code-compliant manner.no fire stoppimg per 712.3;27-345.noted:at 1st fl corridor 3 piping w/hole around the piping w/no fire stopping.also at cellar cafeterial var

    Jan 24, 2018

    Resolve
  • Class - 2

    28-301.1 unlawful display of artwork in corridors greater than 20% per fdny 2008 code; fc 803.3.2 noted: artwork displayed throughout the bldg corridors is greater than 20% allowed.rmdy: comply with nov.

    Jan 24, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. noted at gas meter room, illegal storage of boxes of tiles, track cans, ladders, chairs. extension cords. rmdy: comply w/nov.

    Jan 24, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. lack of emergency lighting for exits, exits discharges and public corridors per bc 1006.1; 27-542. noted: emergency exit lighting observed inoperative at follo

    Jan 24, 2018

    Resolve
  • Class - 2

    Reissue# 35177336p. occupancy contrary to that of bldg dept records. @ cellar, electrical panel room used as custodians office. rem: comply w/ summons.

    Mar 10, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. note: @ time of insp @ cellar level in electrical room make shift custodians office (chains,desk,papers,electronics,etc)& also storage in gas room (chains,pape

    Mar 22, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. note: @ the time of insp @ 4th flr level room 400 girls bathroom a 2' x 3' hole in ceiling. rem: comply w/ the nov.

    Mar 22, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. note: @ time of insp in main hall corridor from 1st flr-4th flr 3 electrical piping tubes(10",4" & 2" in diameter) penetrates through floor through ceiling 18"

    Mar 22, 2016

    Resolve
  • Class - 2

    Reissue 35107108j.failure to maintain bldg in code compliant manner.in room 251:wood floor rotted causing floor to sag due to previous radiator leak.rem:repair floor.

    Jun 4, 2015

    Resolve
  • Class - 2

    27-371(b)vision panles.no vision panels into classroom through out bldg except far 4 fl.plexiglass vision panel in room 107,@ exit 2 bsmt & exit 4 in bsmt.rem:provide required glass panels.

    Jul 29, 2014

    Resolve
  • Class - 2

    Fail to maintain.wooden floor in room 251 rotted causing fl to sag.@ room 203,radiator replaced,but flooring not replaced leaving a hole approx 12"x12"open.rem:repair/replace wood flooring.

    Jul 29, 2014

    Resolve
  • Class - 2

    Fail to maintain.weight of computer router panel attached to wall in room 208 is causing plaster wall to crack & seperate from wall studs.rem:support weight of panel.

    Jul 29, 2014

    Resolve
  • Class - 2

    Fire stopping.@bsmt lvl;fire stopping missing @ cafeteria penetrations& various penetrations in bsmt.rem:provide/maintain fire stopping.

    Jul 29, 2014

    Resolve
  • Class - 2

    Fail to maintain.water penertration @ exterior facade on elton str creating damage to interior.rem:maintain exterior bldg wall.

    Jul 29, 2014

    Resolve
  • Class - 2

    Re-issue 35013149z.fail to maintain:plaster spalling @ walls in rooms 305 & 303,in hallway bet.rooms 404 & 403 & in rom 413.in room 305 plaster damage from ceiling to floor.rem:maintain interior,make necesary r

    Jul 29, 2014

    Resolve
  • Class - 2

    Storage of computers, tires, rims, boxes, chairs, & carts in gas service room. rem: remove all storage from gas rm.

    Feb 26, 2013

    Resolve
  • Class - 2

    Reissue 34933309y. plaster spalling on walls at windows of 4th floor auditorium. rem: make necessary repairs.

    Feb 26, 2013

    Resolve
  • Class - 2

    Wooden flr in the storage room is rotten causing the flr to sink creating a hole approx 12" located adjacent to the windows in room 351 on the 3rd flr level. remedy: repair/replace wooden flr.

    Feb 9, 2012

    Resolve
  • Class - 2

    The plaster on the walls is spalling located in room 403 & 4th flr auditorium. remedy: repair/replace plaster on the wall.

    Feb 9, 2012

    Resolve
  • Class - 2

    Exterior wall has become porous and allowing rain water into the bldg causing interior damages in the custodian's office at the lower level.remedy : water - proof exterior wall

    Apr 8, 2010

    Resolve
  • Class - 2

    Corridor hallway has many desk & chairs being used as class sessions located on the 1st fl level. remedy: remove tables & chairs from corridor

    Apr 8, 2010

    Resolve
  • Class - 2

    The gas meter room is being used as a storage room consisting of boxesof paper towels at the lower level. remedy: remove stored items at gasmeter

    Apr 8, 2010

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1895
Floors
3
Residential units
—
Building area
55,712 ft²
Lot area
22,500 ft²
Zoning
R4
Community board
305
Council district
37
Block / lot
3926 / 45
Assessed value
$4,292,100
Landmark / historic district
INDIVIDUAL LANDMARK

Questions about 200 Linwood Street

Who owns 200 Linwood Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 200 Linwood Street have violations?

NYC HPD has no housing violations on record for this property.

Is 200 Linwood Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 200 Linwood Street built?

City records list 1895 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.