Violations at 439 Sheffield Avenue

Brooklyn, NY 11207 · BBL 3-03788-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

The newest 50 of 142 DOB violations. The city keeps the complete history.

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 9, 2020

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 9, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 9, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 9, 2020

    Dob violation - resolved
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 17, 2019

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 17, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 17, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 17, 2019

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator - failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 28, 2018

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 28, 2018

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 28, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    Cease use

    Sep 28, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 4, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 4, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 4, 2017

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2016 inspection/test

    Sep 15, 2017

    Dob violation - active
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2015 inspection/test

    Dec 1, 2016

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 19, 2016

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 19, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 19, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 19, 2016

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2014 inspection/test

    Jun 10, 2015

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 5, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 5, 2015

    Vw-violation work without permit - active
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - active
  • Elevator elevatorrequired

    This pvt replaces pvt 515472

    Jun 10, 2014

    Dob violation - active
  • Elevator elevatorrequired

    Nyc department of education

    Jun 10, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    Nyc department of education

    Jun 10, 2014

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 23, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 23, 2013

    Vw-violation work without permit - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 23, 2013

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2011 inspection/test

    Oct 1, 2012

    Dob violation - active
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 12, 2011

    Dob violation - resolved

ECB violations

The newest 50 of 132 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner. at the time of inspection bulkhead "d" had spalling, peeling and efflorescence cafeteria on 5th floor had bubbling, spalling and efflorescence on the wall

    Mar 24, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection,the emergency lights were not operable:-1 lig

    Mar 24, 2026 · Penalty $1,250

    Active
  • Class - 2

    28-301.1. unlawful placement of furnishings, decorations or other objects at exits that obstruct access to, egress from or visibility thereof per fdny 2008 code; fc 1027.4. at the time of inspection the followi

    Mar 24, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-381(j). at the time of inspection, the following doors had turn knob hardware:-542, 544, 548, 54

    Mar 24, 2026 · Penalty $1,250

    Active
  • Class - 2

    Re-issued 35692076y. at the time of inspection, the following doors were not self-closing. properly:-staircase "d" 2 doors on 5th floor, 549, 545, south side corridor door next to room 510, staircase "a" on 5th

    Mar 24, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue #3566354z: exit door not self-closing room 239, 311 and 545 not self-closing when tested. remedy: repair and/or replace.

    Apr 1, 2025 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code compliant manner. upon inspection, the device is found to be out of service. remedy: restore to service and contact the dob elevator division at [email protected]

    Sep 30, 2024 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code compliant manner. upon inspection, the device is found to be out of service. remedy: restore to service and contact the dob elevator division at [email protected]

    Aug 27, 2024 · Penalty $625

    Active
  • Class - 2

    Reissue #. exit door not self closing. noted: at time of inspection i observed at room 239 exit door not 8616k-closing and not opening and closing properly also at room 546, 311 used to make repair or replace d

    Feb 6, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridor per bc 1006.1;27-381.noted:at 5th floor cafeteria,3rd floor stairwell e,stairwell a,1st floor corr

    Jan 19, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35548428m noted:at the bulkhead stair d,5th floor cafeteria entrance by 540 and stair d,4th floor stair a,3rd floor stair g,corridordoors by 340 and 311,2nd floor stair d,auditorium entrance by 236,1st

    Jan 19, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#356365924 noted:the door to room 545,311 and 239 is not working properly.rem:repair and/or replace.

    Jan 19, 2023 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain bldg in code compliant manner: lack of emergency lighting for exit discharge & public corridors per bc 1006.1;27-542. atthe 5,4,3&2 floor exit light not working on both side above the corrid

    Feb 7, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35548429y failure to maintain bldg in code compliant manner: no firestopping per bc 712.3;27-345. at cellar level in the electrical meter room above the door conduits with no firestopping around them.

    Feb 7, 2022 · Penalty $3,125

    Resolve
  • Class - 1

    3301.1.1 failure to institute adequate afety measure(no helmets)note at time of inspection under permit#322053291 3 workers onsite where doing shoring without using any ppe(helmet)this is hazard and dangerous c

    Jul 26, 2021

    Resolve
  • Class - 1

    Failure to maintain/display onsite documents requried by chapter 33.note at time of inspection,i observed that 3 workers onsite doing shoring and sheeting on behelf of contractor and the qsp had no drawing or d

    Jul 26, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:doors@rms207&239 arent working properly.repair &/or replace.

    Mar 8, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:use of prohibited door &/or hardware per bc1008.1.8;27-371j.noted:@1fl stairf by 132l&staird by 118;smoke doors have kickdown door holders installed.provide lega

    Mar 8, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:no fire stopping per bc712.3;27-345.noted:@cellar level electrical meter rm;has holes aboveentrance doors from electrical conduits.provide/maintain firestopping.

    Mar 8, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue35518198z noted:@3fl smoke by 311,smoke by 340,auditorium entryby 226&222,exterior door@exit4by100,exterior&smoke door@exit3,by 106cl,girls gym entrance by 103cl,1fl smoke by stairh,boys gym by exit9,sta

    Mar 8, 2021 · Penalty $1,562

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application, install dlm, and perf

    Dec 22, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Work being done to device. restore to service so a full inspection can be made by this department.

    Dec 22, 2020 · Penalty $625

    Active
  • Class - 2

    Exit door not self closing properly. at 5th fl at stair"e" 2 exit doors & 3rd fl stair"e"1st fl exit door at 1st fl staircase"f"2 doors,at 1st fl. at staircase"e"3 doors at 1st fl gymnasium 4 doors are not self

    Mar 24, 2020 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing at various locations out of plumb and not closing locations are stairwell a,e 5th floor stairwell a 3rd floor andstairwell a 2nd floor. rmdy: repair and/or replc.

    Feb 4, 2019

    Resolve
  • Class - 2

    Reissue 35322527x failure to maintain building in code compliant manner. noted 4" crack inside room b36/37 below window. rmdy: repair and/orreplace.

    Feb 4, 2019

    Resolve
  • Class - 3

    Failure to maintain bldg in code compliant manner. note: at inspectionconcrete is palling away with large cracks of window wall outside of room b36/37. reissure #35229171h issued on 03/03/17. rmdy: repair and/

    Apr 2, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner noted: at inspection cellar level in the electrical meter room damage along the rearbrick masonry wall and sheet rock. rmdy: repair and/or replace.

    Apr 2, 2018

    Resolve
  • Class - 3

    Reissue# 35177850h. failure to maintain bldg in code compliant manner. concrete is pulling away w/ large cracks of window well outside of room b36/37. rem: comply w/ summons.

    Mar 3, 2017

    Resolve
  • Class - 3

    Reissue# 35177349y. failure to maintain bldg in code compliant manner, water penetration in various areas of bsmt. rem: comply w/ summons.

    Mar 3, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s) and appurtenances. reissue #35129076 l 06/05/15. note: window well has apprx 4" crack at exterior wall of room b 36n/b37. rmdy: comply w/notice of violation.

    Apr 11, 2016

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances. reissue #33129077n 06/05/15 note: water penetration of foundation wall along pennsylvania avenue affecting boiler room, electrical panel room, fan room and

    Apr 11, 2016

    Resolve
  • Class - 3

    Failure to maintain bldg in a code compliant manner. failure to provide 1/4"thick wired glass vision panel where required as per 27-371(b). note: at time of inspection the following doors are non compliant stai

    Apr 11, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. failure to provide wired glass vision panels per 27-371b. the following doors are non compliant: stair a at 1st flight, and 5th flr, stair g at 4th flr, stair

    Jun 5, 2015

    Resolve
  • Class - 2

    Re-issue 35102097k.exit doors not self closing door racked and do not self close at stair a at 4th 3rd and 1st floor. stair a vestible stair a interior doors.cellar door leading to gym 1 & 2 stair d at 3rd floo

    Jun 5, 2015

    Resolve
  • Class - 2

    27-371 re-issue 35102094p vision panels.use of prohibited plexiglass in the following doors stair a,c 1st & 5th fl,stair g at 4th fl,stair d at 4th fl.stair e at 3rf fl.smoke corridor door next to room 340 and

    Jun 5, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg walls or appurtenances.at boys gym and 1st floor observed step cracks at all four walls and 2nd floor.balcony wall.rem:maintain walls,repair cracks

    Jun 5, 2015

    Resolve
  • Class - 2

    Re-issue 35102095r.failure to maintain bldg walls or appurtenances.water penetration of foundation wall along pennsylvania ave affecting boiler room,electrical panel room,fan room and shop area.rem:provide wate

    Jun 5, 2015

    Resolve
  • Class - 2

    Re-issue 35102096z failure to maintain bldg walls or appurtenances.window well has approx.4" crack at exterior wall of rm b 36n/ b37.rem:maintain exterior wall,repair crack

    Jun 5, 2015

    Resolve
  • Class - 2

    Exit doors not self closing the following doors are racked or do not close properly : smole corridor doors next to rm 337 & smoke corridor doors next to rm 324 stair g at gym on 1st fl, interior g doors at 1st

    Jul 23, 2014

    Resolve
  • Class - 2

    Re-issue 35012675y failure to maintain exterior wall of window wall has an approx 4" crack adjacent to window of rm b 36n / b37 remedy: repair crack

    Jul 23, 2014

    Resolve
  • Class - 2

    Re-issue 35012676x failure to maintain water penetrating through foundation wall ( pennsylvania ave side of bldg) into oil tank room, fan room, electrical panel room & shop area in cellar. remedy: provide water

    Jul 23, 2014

    Resolve
  • Class - 2

    27-371(b) re-issue 35012681k vision panels prohibited plexi glass panels installed in doors to rm 328, 312, 405, 238 and stair a @ 5th fl, 4th and 3rd fl. at stair g 5th & 4th fl. at stair d 4th, 3rd fl & 1st f

    Jul 23, 2014

    Resolve
  • Class - 2

    Re-issue 35012682m & 35012678j failure to maintain plaster spalling atthe following areas : at bulkheads, @ rooms 202, 249, 302, 345, 346, 340, 349, 422, 434, 445, 548, 549, 544, 506 & 541 & stair wall to boys

    Jul 23, 2014

    Resolve
  • Class - 2

    Exit directional sign from pool through shower room improperly positioned and not visible from path of egress. remedy: relocate exit directional sign.

    Mar 25, 2013

    Resolve
  • Class - 2

    At exit a interior stair tread cracked and loose. remedy: repair/replace stair tread.

    Mar 25, 2013

    Resolve
  • Class - 2

    Storage of propane tank and other combustible items at bulkhead of stair e. remedy: remove combustibles.

    Mar 25, 2013

    Resolve
  • Class - 2

    Exit doors to boys gym are obstructed. by table, chairs, bleachers andgym equipment. remedy: remove obstructions.

    Mar 25, 2013

    Resolve
  • Class - 2

    Exit door from auditorium left of stage has defective panic hardware preventing door from opening. remedy: repair/replace hardware.

    Mar 25, 2013

    Resolve
  • Class - 2

    Plaster damaged on ceilings of rooms 548,549,545,544,542,506 & 500 also on wall of rm 414. remedy: make all necessary repairs.

    Mar 25, 2013

    Resolve
  • Class - 2

    Sec. 27-371(b). plexi vision panels installed on doors to rooms 238, 405,328,312, stair a & d. 3 & 4 flrs, stair g, 5th flr, stair e 3rd flr and corridor doors adjacent to rm 340. remedy: provide required

    Mar 25, 2013

    Resolve