615 Thomas S Boyland St

Brooklyn, NY 11212BBL 3-03541-0001Map

Owner of record: NYC Department Of Education

615 Thomas S Boyland St is a school building built in 1930 in Brooklyn, 11212. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
55
ECB violations
46
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 55

  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator - failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - active
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator - failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 10, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - active
Show 40 more ↓
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 31, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 5, 2011

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 28, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 10, 2003

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active

ECB violations · 46

  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.at thetime of inspection observed and noted at 1st floor near stairway h one

    Jun 8, 2026 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per 1006.1;27-381.noted:at multipurpose room,one emergency exit lighting found inoperative.rem:re

    Apr 5, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner noted:@2fl hallway nonfirerated decorations hung suspended from ceiling.comply w/code.

    Apr 27, 2021 · Penalty $625

    Resolve
  • Class - 2

    28-301.1 unlawful display of artwork in corridors >20% per fdny2008code fc803.3.2 noted:@2fl hallways display of artwork,banners etc. exceeds allowable amt of 20% of wall covering decorations/displays.comply w/

    Apr 27, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Exit door not selfclosing noted:@5fl stairsa&c door checks in disrepair/nonoperational when tested.repair/replace door.

    Apr 27, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner noted:@4fl stairc 1flgym&exit4 doors in disrepair/racked.repair &/or replace.

    Apr 27, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner use of prohibited door &/or hardware per bc1008.1.8 27-271j noted:thruout entire installed door kick stoppers in various locations.provide legal hardware.

    Apr 27, 2021 · Penalty $625

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. remedy; file application, install dlm a

    Oct 2, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Unit was out of service upon time of inspection/ remedy: return to service

    Feb 11, 2020 · Penalty $625

    Active
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at cellar atgirls locker room at bathroom, roof leak during the heavy rain. rmdy: make necessary repair.

    Mar 28, 2018

    Resolve
Show 36 more ↓
  • Class - 2

    28-301.1 unlawful display of artwork in corridors greater than 20% per fdny 2008 code fc 803.3.2 noted: artwork displayed in corridors throughout the bldg is greater than 20% allowed. rmdy: comply with nov

    Mar 28, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: classroom doors at room 401 an room 501 do not close due to harware defectiveness. rmdy: repair door.

    Mar 28, 2018

    Resolve
  • Class - 2

    Water penetration through foundation wall. beneath main entrance along blake ave. ponded water observed. remedy: maintain building.

    Jul 16, 2014

    Resolve
  • Class - 2

    The girls bathroom door hinge is detached from the door frame located on the 1st flr level adjacent to the main entrance. rmdy: re-attach door hinge to door frame.

    Apr 19, 2013

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. noted: at room 502,entry door to class room missing visual panel. remedy: install visual panel.

    Jul 9, 2010

    Resolve
  • Class - 3

    Reissued: 34711582l. failure to maintain in code-compliant manner. noted: sub flring in rooms 510 & 511 has water damage causing flr to buckle causing "un-eveness". remedy: repair flr.

    Jul 9, 2010

    Resolve
  • Class - 2

    Reissue: 34777472m. failure to maintain bldg wall(s) or appurtenances.noted: at cellar level, foundation wall - observed water penetration thru-out. remedy: seal wall.

    Jul 9, 2010

    Resolve
  • Class - 3

    Failure to maintain at cellar level outside oil tank room 2'x 2' masonary column has 4 3' vertical cracks at base up to 1" in width. remedy:repair column.

    May 20, 2009

    Resolve
  • Class - 2

    Failure to maintain unobstructed egress at gym exit 4 to bristol st used for storage of volleyball net also right door binds at saddle making door difficult to open. remedy: remove obstruction repair door.

    May 20, 2009

    Resolve
  • Class - 3

    Reissue: 34711582l flooring bucked room 502,510,511 near windows. remedy: repair flrs.

    May 20, 2009

    Resolve
  • Class - 3

    Reissue: 34711580h in room 408 water entering bldg around left window causing interior plaster to spall. remedy: waterproof bldg outside.

    May 20, 2009

    Resolve
  • Class - 3

    Reissue: 34711587z water entrance cellar from porous foundation south side and hatch door. remedy: waterproof cellar.

    May 20, 2009

    Resolve
  • Class - 3

    Reissue 3456306l. mortar joints missing @ south side of foundation wall interior.also roof parapet spalling in multiple locations.remedy:repair joints.

    Nov 21, 2008

    Resolve
  • Class - 3

    Failures to maintain sub-flooring in room 502,510,511 wood flooring has water damage causing floor to sag.remedy:replace floor (affected area).

    Nov 21, 2008

    Resolve
  • Class - 2

    Illegal hardware on roof access doors key cylinder in place.remedy:remove illegal hardware.

    Nov 21, 2008

    Resolve
  • Class - 3

    Reissue 34563060m. water penetration in room 408. remedy:seal penetration.

    Nov 21, 2008

    Resolve
  • Class - 3

    Reissue 34563062x. water penetration through foundation wall at south side of building into cellar.remedy:seal foundation wall.

    Nov 21, 2008

    Resolve
  • Hazardous

    Re-issue:34474375m. water penetration through 4th floor exterior brickinto interior. location north facade 4th floor ouside of room 408. remedy: stop water penetration.

    Feb 9, 2007

    Resolve
  • Hazardous

    Re-issue:34391030n. plaster wall in room 408 north side minor bulging and forming mold. remedy: repair wall.

    Feb 9, 2007

    Resolve
  • Hazardous

    Failure to maintain brick wall in cellar south side of building through out spalling mortor joints & water entering from exterior of wall to interior of cellar. remedy: maintain south side wall at above locatio

    Feb 9, 2007

    Resolve
  • Hazardous

    Water penetration through foundation wall at south of building in to cellar through out south side wall. remedy: stop water penetration

    Feb 9, 2007

    Resolve
  • Hazardous

    07l10/85bb05. (07) repair car door safety edge (85) perform and file 5 year test

    Oct 17, 2005

    Resolve
  • Non-hazardous

    Water penetration through brickwall. location: north facade @ 4th fl, outside of rm #408. remedy: waterproof brickwall.

    Mar 30, 2005

    Resolve
  • Non-hazardous

    Reissue #34436854m. tile/wood floor area approx. 6' x 2, in disrepair/rotted. location: rm#513. remedy:repair defective flooring.

    Mar 30, 2005

    Resolve
  • Non-hazardous

    17m07/84x10/85bb05 17m 2nd fl gib missing 84x emer. communications in car inoperative. 85bb 5yr test.

    Oct 20, 2004

    Resolve
  • Non-hazardous

    Failure to maintain. defect is water penetrating into boiler room fromaround hatch door. remedy: maintain building.

    May 14, 2004

    Resolve
  • Non-hazardous

    Failure to maintain. defect is loose and missing 12"x 12" ceiling tiles in room #503. remedy: repair ceiling tiles.

    May 14, 2004

    Resolve
  • Non-hazardous

    Failure to maintain. defect is room #513 wood floor is crack and loose. remedy: repair wood floor.

    May 14, 2004

    Resolve
  • Non-hazardous

    "reissue." (34391030n) failure to maintain. defect is 4th floor project room #408 plaster wall is loose and bulging. remedy: repair plaster wall.

    May 14, 2004

    Resolve
  • Non-hazardous

    Failure to maintain - defect is : cellar boiler room roof leaks remedy: repair roof

    Feb 20, 2003

    Resolve
  • Non-hazardous

    Failure to maintain defects are rotten defective bulging and sagging wood floors in rooms # 312 and 512 remedy : repair wood floors

    Feb 20, 2003

    Resolve
  • Non-hazardous

    Failure to maintain defect is 4th floor project room # 408 north plaster wall is loose bulging and forming mold remedy:repair wall

    Feb 20, 2003

    Resolve
  • Non-hazardous

    Failure to maintain exterior wall defect si entire north side brick facade need keying remedy : repair wall

    Feb 20, 2003

    Resolve
  • Non-hazardous

    Failure to maintain defects are 5th floor exit "d" and "e" metal door frames are loose and saggging remedy : repair door frames

    Feb 20, 2003

    Resolve
  • Non-hazardous

    Failure to provide elevator landing sign to elevator bank on fl 1 to 5. failure to provide 3" high alphabetic letter of identification for elevator bank and for stair over the occupancy side of the stair door o

    Oct 15, 2001

    Resolve
  • Non-hazardous

    Failure to maintain building. defect is windows not operable and defective throughout classrooms. repair or replace.

    Apr 21, 1999

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1930
Floors
5
Residential units
—
Building area
103,000 ft²
Lot area
27,800 ft²
Zoning
R6
Community board
316
Council district
41
Block / lot
3541 / 1
Assessed value
$4,724,100
Landmark / historic district
No

Questions about 615 Thomas S Boyland St

Who owns 615 Thomas S Boyland St?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 615 Thomas S Boyland St have violations?

NYC HPD has no housing violations on record for this property.

Is 615 Thomas S Boyland St rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 615 Thomas S Boyland St built?

City records list 1930 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.