Violations at 190 Woodbine Street
Brooklyn, NY 11221 · BBL 3-03360-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
32 DOB violations, newest first.
- Elevator elevatorrequired
E-elevator elevatorrequired
Nov 30, 2021
Dob violation - resolved - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 in 2020
Jun 20, 2021
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 22, 2020
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 8, 2016
Dob violation - resolved - Elevator elevatorrequired
Nyc department of education
Jun 2, 2014
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 25, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 23, 2008
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 30, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 21, 2005
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 30, 2004
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 10, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 20, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 25, 1991
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 29, 1990
Dob violation - dismissed
ECB violations
The newest 50 of 60 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner.noted:at enire 3rd fl hallway/smoke doors 309,367,365,357,355,349,321 no handles provided/installed/missing.rem:repair and/or replace.
May 5, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:at 3rd fl hallway doors 321,309,367,365,357,355,349 installed/used key locking device
May 5, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at every floor/hallways installed/hung nonfire retarted decorations to ceilings throughout various areas.rem:comply with code.
May 5, 2026 · Penalty $1,250
Active - Class - 2
Reissue ecb#35714712m failure to maintain building in code-compliant manner.noted:at hallway door#349,hallway smoke doors near rm#331,318 2nd fl stair a,hallway smoke doors near rm#234,222 1st fl hallway smoke
May 5, 2026 · Penalty $3,125
Active - Class - 2
Reissue ecb#35717413y failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 1st fl auditorium,cafeteria emergency lights
May 5, 2026 · Penalty $3,125
Active - Class - 2
Reissue #35677560k: failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006,1; 27-381. illumination exit discharge not operational when te
May 5, 2025 · Penalty $3,125
Active - Class - 2
Reissue #35677561m: failure to maintain building in code-compliant manner: door not close properly @ 3rd floors 357 near staircase c, 355 near staircase c to room 234. 1st floor staircase d. remedy: repair and/
May 5, 2025 · Penalty $3,125
Active - Class - 2
Reissue #35672882k. failure to maintain building in code-compliant manner. at time of my inspection i observed at the 3rd floor at room 328,321, stairwell c and stairwell a and room 368 room stairwell and spall
May 9, 2024 · Penalty $1,562
Active - Class - 2
Reissue #35672883m. failure to maintain building in code-compliant manner: illumination foe exits, exit discharges and public corridors per bc 1006.1; 27-381. at time of my inspection, i observed the exit 8 at
May 9, 2024 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code compliant manner.noted the retainer wall outside exit 6 has spalling and missing masonry in various areas leaving the rebars exposed to the elements.remedy:repair and/or rep
Mar 15, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc1006.1;27-381.noted the exit sign at first floor stairwell d by exit 8 and the main entranc
Mar 15, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. noted:at 3rd fl corridor by 325,321c,corridor by stair a,365d,corridor by stair d,357c,corridor by stair c, 355b,349d, 349, smoke by 349a, 221d,209c,corrid
Mar 15, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner.illumination forexit,exit discharges and public corridors per bc1006.1;27-381.noted observed at ground floor hallway between exit 5 and 6 emergency light no
Apr 15, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35486746r exit door not self closing 2 doors at cafeteria not self closing when tested as well as 1 main entrance door not self closing when tested. remedy: comply with code.
Apr 16, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35321800n :exit door not self closing: 2 doors @ cafeteria not self lcosing also the doors at main entrance not self closing repair and or replace
Apr 10, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue# 35321800n exit doors not self closing exterior doors in cafeteria and main entrance and secondary main entrance doors not working properly not open and closing properly. remedy: replace doors
Apr 2, 2019
Resolve - Class - 2
Exit door not self closing. at the time of inspection,exterior doors 2 in cafeteria does not close properly,main entrance on woodbine st door #4 cannot open. remedy: repair/replace doors.
Feb 26, 2018
Resolve - Class - 2
Re-issue 35200799y failure to maintain building wall(s)or appurtenances noted:at exterior play yard rubber fall protection mat missing trim in various areas and curling up and causing a trip hazard need to be
Apr 7, 2017
Resolve - Class - 2
Failure to maintain bldg wall(s)or appurtenances.noted:@exterior playyard rubber fall protection miat missing trim in a fre areas&curling upin other areas.rem0maintain miat.rem:comply w.code.
Jul 14, 2016
Resolve - Class - 2
27-766 noted:vision panels.use of prohibited plexi glass thermoplastic@the following doors:all smoke cross corridor doors on 3rd flr.stair'c' @3rd flr.stair 'd' @3rd flr room 126.rem:comply w.code.
Jul 14, 2016
Resolve - Class - 2
27-371(b) re-issue: 35094668h. vision panels. use of prohibited plexi glass/thermoplastic at the following doors: all smoke cross corridor doors on 3rd flr. stair "c" at 3rd flr, stair "d" at 3rd flr room 126.
May 20, 2015
Resolve - Class - 2
Reissue 35094671z. failure to maintain bldg walls or appurtenances: at exterior play yard. rubber fall protection mat missing trim in a f ew areas and curling up in other areas.rmdy: maintain mat.
May 20, 2015
Resolve - Class - 2
Re-issue # 35016932y. 27-333. parapet (local law 40 of 1960). parapet wall does not meet required height of 42"inches nb 286-1970. remedy: provide protective guards or raise parapet height.
May 13, 2014
Resolve - Class - 2
Failure to maintain at exterior play yard. rubber fall protective mat missing in some areas & curling up in another area creatint trip hazards. remedy: repair & replace mats where necessary.
May 13, 2014
Resolve - Class - 2
Combustilbe materials in corridors. excessive combustilbes in hallway of 3rd & 2nd floor & door of room 149. remedy: remove combustibles from corridors & doors.
May 13, 2014
Resolve - Class - 2
Use of prohibited door &/or hardware per bc 1008.1.8; 27-371(j). use of door stop prohibited. door stops on following doors need to be removed: at 3rd fl fire door next to gym stairs,rm 132,133,134,135,145,149,
May 13, 2014
Resolve - Class - 2
27-371(b). vision panels. plexiglass in the following: rm 365,stair d 3rd fl,rm 357,stair c 3rd fl,rm 355,rm 323,smoke corridor doors next to stair b,rm 233a,rm 126,entry door to cafeteria next to stair c 1st
May 13, 2014
Resolve - Class - 2
Re-issue # 35016935j. failure to maintain. lintels above windows at 2nd floor (madison street) are corroding & sagging. remedy: make necessary repairs.
May 13, 2014
Resolve - Class - 2
Re-issue # 35016936l. failure to maintain. goose neck duct cover detached from duct work penetrating roof & laying on roof. remedy: re-attach duct cover.
May 13, 2014
Resolve - Class - 2
Re-issue # 35016937n. no fire stopping in wall openings of electrical room, gas meter room & corridor outside b11. remedy: maintain & provide fire stopping.
May 13, 2014
Resolve - Class - 2
97**failure to maintain elevator device.respondent failed to provide proper access in order that the dept can perform periodic inspections per 28-304.6 and appendix k of the bldg code.respondent failed to prov
May 6, 2013
Resolve - Class - 2
Openings in walls of electric room with no fire stopping. remedy: provide fire stopping.
Apr 25, 2013
Resolve - Class - 2
Good neck duct cover detached from duct work and laying on roof. rmdy: reattach duct cover.
Apr 25, 2013
Resolve - Class - 2
Lintels above windows at 2nd floor on madison street side are corroding and sagging. rmdy: make necessary repairs.
Apr 25, 2013
Resolve - Class - 2
Kick down door stops on doors to room 321,367,309,365,363,357,349,221,209,267,265,263,257,255,249,235,233,and cafeteria. remedy: remove door stops.
Apr 25, 2013
Resolve - Class - 2
Reissue 34941893m stair at rear exit from gym missing handrail betwn 1&2 flr. rmdy: provide handrail
Apr 25, 2013
Resolve - Class - 2
27-333. reissue 34941892k. parapet wall does not meet required heightof 42"parapet is apprx 36" high nb 286-1970 (34510294x - 2006) rmdy: raise parapet to require height.
Apr 25, 2013
Resolve - Class - 2
Interior rear gymnasium stair exit between 1st & 2nd fl level the metal hand rail is missing. remedy : replace missing hand rail
Mar 21, 2012
Resolve - Class - 2
Mic. 27-333/334 reissue : 34895328p exterior roof top parapet wall does not meet the minimum required height of 42" inches noted : height ofparapet wall only reacges approximatly 36" inches high. nb-286-1970
Mar 21, 2012
Resolve - Class - 2
Sec. 27-333. re-issue #34770818z. at roof top level parapet does not meet the required minimum height 42". remedy: raise parapet to required height or provide guard rail to meet requirement.
Feb 28, 2011
Resolve - Class - 2
Reissue: 34692076h roof parapet height does not meet the minimum height requirement. noted: parapet height is approx 3' feet high. parapet must be 42" inches high. (new building #28/1970). remedy: raise parapet
Apr 8, 2009
Resolve - Class - 2
Reissue: 34692075x the gas meter room (b11) does not have fresh-air ventilation at cellar level. remedy: provide fresh-air ventilation.
Apr 8, 2009
Resolve - Class - 3
Reissue 34569873r roof parapet height is approx.3'high parapet minimumheight should be 42 inch high nb # 286/1970 27-334 remedy:provide 42" protection guards
Jul 17, 2008
Resolve - Class - 3
Reissue 345698742 no ventilation installed inside gas meter rm b11 at cellar level.remedy:provide ventilation
Jul 17, 2008
Resolve - Non-hazardous
Re-issue # 34510296j. no ventilation installed in the gas meter room (b11) on cellar level. remedy: provide ventilation.
Apr 13, 2007
Resolve - Hazardous
Sec.code:27-334. re-issue # 34510294x. roof parapet height is approx. 3 feet high. parapet minimum height should be 42 inches high. (n.b. # 286/1970). remedy: extend parapet height to minimum high to 42 inches.
Apr 13, 2007
Resolve - Hazardous
Reissue: 34510297l (partial) no fire stopping applied at pipe penetration at electrical rm on cellar level. remedy: provide fire stopping.
Apr 13, 2007
Resolve - Non-hazardous
Cellar b13 electrical power room missing fire-stopping at wall penetration. also noted: b24 elevator machine room missing fire stopping above entry door. remedy: provide/maintain fire stopping.
Feb 7, 2006
Resolve - Hazardous
Cellar room b11 sprinkler/gas meter room has no ventilation as required. remedy: provide/maintain ventilation.
Feb 7, 2006
Resolve - Non-hazardous
Second floor fan room across from class room 249a, entry door cut opening approx. 3 feet x 3 feet in door and installed wire guard over opening for computer main frame inside fan room. remedy: replace door.
Feb 7, 2006