Violations at 235 Palmetto Street

Brooklyn, NY 11221 · BBL 3-03343-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

39 DOB violations, newest first.

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 30, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 21, 2020

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 5, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    Nyc department of education

    Jun 2, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 10, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 1, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 1, 2010

    Dob violation - resolved
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 26, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 29, 2008

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 23, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 28, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 21, 2005

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Elevator elevatorrequired

    3p10687

    Aug 22, 2001

    Dob violation - resolved
  • Construction other optional

    Failure to maintain building: defect school playfield uneven cracked in various lacations throughout remedy: maintain buildiing make safe

    Jun 21, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active

ECB violations

The newest 50 of 104 ECB violations. The city keeps the complete history.

  • Class - 2

    Reissue ecb#35730844n failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 1st fl auditorium,cafeteria,gym,hallway near

    May 4, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue ecb#35720845p failure to maintain building in code-compliant manner.noted:at 1st fl exits 1 and 13 door frames/srddles rotting/lifting/rubbing.rem:repair and/or replace.

    May 4, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue ecb#35720846r exit door not self closing.noted:at 3rd fl hallway smoke door near rm 313(2nd fl)hallway smoke door near rm 243(1st flstair b,g exit 13,1 doors are in disrepair not closing when tested.rem

    May 4, 2026 · Penalty $1,562

    Active
  • Class - 2

    Exit door not self-closing. hallway/corridor/staircase door not self-closing when tested first floor next to rm 137 and hallway on first floor hallway. remedy: repair and/or replace.

    Jul 15, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. observed exit door at grand level 3, 2, 1, 13 saddle lift and making it difficult to open door. remedy: repair and/or replace.

    Jul 15, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner for emergency lighting for exits, discharges and public per bc 717.3; 27-345. emergency light not working when tested. b-1 basement hallway, b-2 rm14 hallwa

    Jul 15, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35672700k failure to maintain building in code-compliant manner.at time of my inspection i observed at the roof level.roof leak causing damage to the ceiling at room 329 and stairwell b bulkhead ceiling

    May 6, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35672701m failure to maintain building wall(s)or appurtenancesat time of my inspection i observed at the cellar level foundation wall has become porous allowing the rain water into the gas meter room an

    May 6, 2024 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35672702y failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.at time of my inspection i observed at the cafeteria main

    May 6, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.illumination exits,exit discharges and public corridors per 1006.1;27-381.noted at cafeteria main entrance,exit 6 and at auditorium,4 emergency light exits

    Mar 15, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building walls or appurtenances.noted at cellar foundation wall has become porous allowing the rain water into the gas meter room,electrical room and boiler room.remedy:maintain the exterior

    Mar 15, 2023 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35651097m failure to maintain building in code compliant manner.noted roof leak causing damage to the ceiling at room 329 and stairwell b bulkhead ceiling.remedy:make necessary repair.

    Mar 15, 2023 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35651099x failure to maintain building in code compliant manner.noted at wilson ave side at exit 14,concrete step and railing posts in state of disrepair.remedy:make necessary repairs.

    Mar 15, 2023 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.noted:observed at palmetto side & gates ave side concrete step leading into building in state of disrepair causing tripping hazard due to erosion.remedy:rep

    Apr 13, 2022 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code compliant manner illumination of exits exit discharge & public corridors per bc1006.1;27-381.noted:observed emergency lighting not operational when tested at various locatio

    Apr 13, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35553986n failure to maintain building in code compliant manner.noted:observed at roof level at all bulkhead staircase water penetration damage to inside from 3rd to 2d floor.remedy:repair and/or repla

    Apr 13, 2022 · Penalty $1,562

    Active
  • Class - 2

    Reissue #35553987p failure to maintain building in code compliant manner.noted:observed ongoing damage due to water penetration from roof to lower floor in hallway & room all on 3rd floor.remedy:repair and/or r

    Apr 13, 2022 · Penalty $1,562

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor

    Nov 30, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35473125l at room 329 ceiling has damage due to ongoing into penetration-also ceiling at 327,227,3 fl staircase'b'have ongoing water penetration issues. remedy: comply with code.

    Apr 15, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    At roof top bulkhead at exterior walls at staircase b,c,d,e,f have become porous allowing ongoing water to interior areas of 2nd & 3rd floorlocation. remedy: comply with code.

    Apr 15, 2021 · Penalty $625

    Active
  • Class - 2

    Reissue #35383868n:failure to maintain building in code compliant manner rm 329 has water damage on ceiling due to water penetration also noted where damage throughout 3rd floor due to leaks from roof all bulkh

    Apr 14, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted in electrical closet main closet in basement has boxes and ladders and other stuff being stored in the electrical room. remedy:remove all boxes and l

    Apr 3, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted room 329 and 3rd floor stairwell b ceiling have water damage due to roof leaking. remedy: repair and or replace

    Apr 3, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.127-542. noted: at auditorium area, inoperative emergency lights with

    Mar 1, 2018

    Resolve
  • Class - 2

    Exit door not self closing. noted: at 2st floor, main entrance door and at 2nd floor. staircase (g), the doors have defective in the top hinge and not close completely. rmdy: comply w/code/repair or replace.

    Mar 1, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner noted at cafeteria and room 237, missing ceiling tiles, also at library at 3rd floor, observed damaged ceiling tiles. rmdy:comply w/code

    Mar 1, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc1006.1;27-381.noted:emergency light packs through out school were not working properly at

    Apr 7, 2017 · Penalty $2,500

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.not or stopping per bc712.3;27-345.noted:at time of inspection,observed no fire stopping in electrical closets on 3rd.flr next to room 320.2nd flr next to

    Apr 7, 2017 · Penalty $2,500

    Resolve
  • Class - 2

    Reissue 35094654r. failure to maintain bldg in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-542. the following emergency lighting not working. at cafe

    May 29, 2015

    Resolve
  • Class - 2

    27-371(b) reissue 35094653p vision panels. no vision panels on smoke corridor doors next to stair c at 2nd and 3rd flr or next ot stair b on 3rd flr and room 220 plexi vision panels on the following doors: 316,

    May 29, 2015

    Resolve
  • Class - 2

    Illumination for exits, exit discharges & public corridors per bc 1006.1; 27-381. the following emergency lighting not working: at cafeteria exit #6 & entrance to cafeteria. gymnasium main entrance emergency l

    May 12, 2014

    Resolve
  • Class - 2

    Re-issue # 34957604n. 27-371(b). vision panel. plexiglass installed on following doors: rms:131,133,135b,147,148,209,209c,209d,209b,212,229d,229a,233,235,241b,241d,237,239d,248,256,255b,255c,255d,326,317a,317a

    May 12, 2014

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. plaster damage from water penetration in the following rooms: 300,327,329,355a & in stairway h at 3rd floor. remedy: repair damage.

    May 12, 2014

    Resolve
  • Class - 2

    Re-issue # 35015985n. failure to maintain bldg walls or appurtenances. water penetration through roof into stairway "h" & into room 329,300,355a & room 327. remedy: repair roof.

    May 12, 2014

    Resolve
  • Class - 2

    Re-issue # 35015988z. no fire stopping per bc 712.3; 27-345. observed no fire stopping at penetrations at stairway c 3rd fl, electrical panel room in cellar & boiler rm in cellar. remedy: provide/maintain fire

    May 12, 2014

    Resolve
  • Class - 2

    67l10,11t16,13i10,61g11,48t15,68m07,17h11,77m07,100y13,70y02,10j01,16t07. 67l-repair;11t-missing braille tab;13i-lens;61g-unreadable fuses; 48t-current pressure test; 68m-recent entries; 17h-where needed; 77m-

    Jul 1, 2013

    Resolve
  • Class - 2

    Openings at pipe penetrations in electric rm w/no fire stopping. remedy: provide fire stopping.

    Apr 3, 2013

    Resolve
  • Class - 2

    Kick down door stops installed on doors and rooms 355f,355a,313,327c, 322a. remedy: remove door stops.

    Apr 3, 2013

    Resolve
  • Class - 2

    Wall tiles loose & missing at 3rd flr boys and womens restrrooms & 1stflr h/c restroom. remedy: make all necessary repairs.

    Apr 3, 2013

    Resolve
  • Class - 2

    Reissue 34957604n. water penetrating through roof at rms 300,355a & 327 also at stair h 3rd flr. remedy: repair roof.

    Apr 3, 2013

    Resolve
  • Class - 2

    Sec. 27-371(b) plexi vision panels installed on doors to rooms 135b,133,131,147,148,341 corridor doors, rms 341c,248,256,237,239d,229a,221,209c,209b,326,255b,255c,255d, library. remedy: provide fpsc doors as

    Apr 3, 2013

    Resolve
  • Class - 2

    Exterior roof has become porous & allowing rain water into the 3rd floor level at room 300,355a & stair 'h' causing interior damages. remedy: water proof exterior roof.

    Mar 28, 2012

    Resolve
  • Class - 2

    Reissue: 34901965x exterior foundation wall has become porous & allowing rain water into the fan room at cellar level causing interior damages. remedy: water proof foundation wall.

    Mar 28, 2012

    Resolve
  • Class - 2

    At the cellar level foundation wall has become porous w/water penetration present at the gas meter & fan room. remedy: restore weather proofing to exterior foundation wall.

    Feb 14, 2011

    Resolve
  • Class - 1

    Exit passageway obstructed on 3 flr corridor security desk blocking 80% of corridor. remedy: remove security desk.

    Mar 30, 2010 · Penalty $6,000

    Active
  • Class - 2

    Water penetration into gym, rms 317,327a, staircase & ceiling, staircase f 3l, stair h 3fl and front of room 333 in corridor. remedy: seal penetration!

    Mar 30, 2010

    Resolve
  • Class - 2

    Exterior brick facade is bulging located at above exit "c" between 2nd & 3rd flr level. remedy: repair/replace brick facade.

    Apr 8, 2009

    Resolve
  • Class - 2

    Reissue: 34657726r metal door frame is rotten & bulging located at stairway "f" 3rd flr level. remedy: replace door frame.

    Apr 8, 2009

    Resolve
  • Hazardous

    Reissue 34390790l defective doors 3 flr stairway c,f 2nd flr b,c,e,g corridor door near rm 250, 1st flr stair b. remedy: repair/replace doors.

    Jun 12, 2008

    Resolve
  • Non-hazardous

    Third floor library, pa posted for 108 person, exit door screwed shut with piece of plywood and drywall screws at top of door. remedy: remove obstruction.

    Feb 3, 2006

    Resolve