1300 Greene Avenue
Brooklyn, NY 11237BBL 3-03298-0001Map
Owner of record: NYC Department Of Education
1300 Greene Avenue is a school building built in 1976 in Brooklyn, 11237. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 47
- ECB violations
- 90
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 47
- Elevator elevatorrequired
E-elevator elevatorrequired
Oct 19, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 7, 2019
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 20, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 26, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 12, 2014
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2012 inspection report
May 15, 2014
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2012 inspection report
May 15, 2014
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2012 inspection report
May 15, 2014
Dob violation - dismissed
Show 37 more ↓
- Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 5, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 24, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 24, 2009
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 22, 2007
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 30, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 14, 2005
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 19, 2002
Dob violation - dismissed - Construction other optional
Failure to maintain building defect waste line back ups in basement cause flooding in boiler room. remedy: maintain building make repair as nended
Jun 13, 2001
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Elevator elevatorrequired
3p7251
Aug 4, 2000
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Elevator elevatorrequired
3p7251
Dec 7, 1998
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 17, 1995
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
May 31, 1994
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 28, 1993
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 7, 1992
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 25, 1991
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 29, 1990
Dob violation - dismissed - Elevator elevatoroptional
1
Oct 12, 1989
Dob violation - dismissed
ECB violations · 90
- Class - 2
Reissue#35072839p at the time of inspection,the following doors were not self-closing corridor doors next staircase h on 4th floor,457,401,409,351,333,corridor door next to 248,253,209 door from 2nd floor gym s
Apr 28, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35717407h at the time of inspection,the following emergency lights were inoperable light in stairwell h by 3rd floor lights in stairwell a on 3rd/2nd floor light in stairwell 4 on 2nd floor all emergenc
Apr 28, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35717408j at the time of inspection,the following electrical meter room has opening at ceiling/wall were the cluster of pipes are thgas meter room had penetration open at ceiling.both electrical meter r
Apr 28, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35717410z at the time of inspection,the following exit discharge doors were not self-closing #9,#5 frame was falling off.rem:repair/replace door.
Apr 28, 2026 · Penalty $1,562
Active - Class - 2
28-301.1 unlawful display of artwork in corridors greater than 20% perfdny 2008 code;fc 803.3.2.at the time of inspection,6th floor corridornear room 443 had excessive artwork in excess of 20% as permitted.rem:
Apr 28, 2026 · Penalty $1,250
Active - Class - 2
Reissue#35717409l at the time of inspection cracks were on corridor wall at room 315,there was efflorescence in staircase h on 4th floor room 301 has water stain in ceiling room 259 had broken glass panel 2nd,3
Apr 28, 2026 · Penalty $3,125
Active - Class - 2
Reissue #35677520x: failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per 1006,1; 27-381. existing emergency light(s) are not operational when t
May 1, 2025 · Penalty $3,125
Active - Class - 2
Reissue #35672837l: failure to maintain building in code-compliant manner: no fire-stopping for bc 712.3; 27-543. at electrical room in cellar level rear entrance door large opening surrounding conduit pipes wi
May 1, 2025 · Penalty $3,125
Active - Class - 2
Reissue #35672840m: exit door not self-closing at main exit 7, exit 8(kitchen) not close properly when tested. remedy: repair and/or replacedoor(s).
May 1, 2025 · Penalty $1,562
Active - Class - 2
Reissue #35672843h; failure to maintain building in code-compliant manner: at 3rd floor less of room horizontal cracks with loose/missing mortar are glaze surface cmu interior block walls. remedy: repair and/or
May 1, 2025 · Penalty $1,250
Active
Show 40 more ↓
- Class - 2
Reissue#35672841y failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.at time of my inspection i observed at 3rd floor stairwel
May 3, 2024 · Penalty $1,562
Active - Class - 2
Exit door not self-closing.noted:exterior door at main entrance to building exit 7, & kitchen exit 8 not working properly.remedy:repair/replace door
Mar 14, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner.illumination for exit,exit discharges & public corridors per bc 1006.1; 27-381.noted:at 3rd fl stairwell a, 2nd fl gynasium,stairwell b, h, 1st fl stairwell
Mar 14, 2023 · Penalty $625
Active - Class - 2
Reissue #35650743n noted:at 3rd fl corridor by rm 315, right side of stair h & 2nd fl adjacent to rm 228*(white cmu blockwall) all have cracks and/or step cracks in various areas.remedy:repair and/or replace.
Mar 14, 2023 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at 4th fl corridor by stair h,room 449, 3rd fl corridor by stair f,g & h, room 307,309,322(library)entrance,right room inside 322,2nd fl room 205,209
Mar 14, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner.noted:at right side of exp #2 near 3rd fl level has loose & missing mortar in various areas throughout.brick missing at ground level outside exit 4.remedy:r
Mar 14, 2023 · Penalty $625
Active - Class - 2
Reissue #35650744p noted:at cellar level electrical meter room,large holes above entrance door from conduits in various areas.remedy:provide/mainatain fire stopping.
Mar 14, 2023 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at 3rd fl hallway by stair g large hole in ceiling.at room 322 rear left reference room large area of ceilingg is sagging in middle.light fixtures ins
Mar 14, 2023 · Penalty $625
Resolve - Class - 2
Reissue#35557930m 4/12/2021.failure to maintain building in code compliant manner.no fire stopping pre bc712.3;27-345 at electrical room in basement emergency light conduit penetrated wall with no fire stopping
Apr 14, 2022 · Penalty $3,125
Active - Class - 2
Reissue#35557931y 4/12/2021.failure to maintain building in code compliant manner.at 3rd floor corridor by room 315,4th floor by room 424 large step pattern cracks on cmu block walls.remedy:comply with code.
Apr 14, 2022 · Penalty $1,562
Active - Class - 2
Reissue#35486744n failure to maintain bldg in code compliant manner. at time of inspection noted: at 3rd fl corridor outside of room#315,12 foot step crack in c.m.u. block wall. remedy: comply with code.
Apr 12, 2021 · Penalty $1,562
Active - Class - 2
Reissue#35486745p failure to maintain bldg in code compliant manner missing emergency lighting at 1st fl exits also pipe pentration at basement electrical room does not have adequate fire stopping.
Apr 12, 2021 · Penalty $3,125
Active - Class - 2
Failure to maintain bldg in code compliant manner at time of inspection. noted: at auditorium automatic partition doors not operational when tested. remedy: comply with code.
Apr 12, 2021 · Penalty $625
Resolve - Class - 2
Reissue#35235629l failure to maintain building walls/or appuretnances rm 315 horizontal crack on wall corridor maintain building walls
Mar 27, 2020 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code compliant manner lack of emergency lighting for exits ,exit discharges and publci corridor per bc 7.2.3;27-345 electrical has pipes penetratubf wall with no firestopping rep
Mar 27, 2020 · Penalty $1,250
Active - Class - 2
Reissue 35200740j failure to maintain building in code compliant manner. noted observed step cracks and cracked blocks next to water fountains at 2nd and 4th fl outside stair f observed step cracks at 2nd 3rd a
Apr 1, 2019
Resolve - Class - 2
Reissue 35322042h failure to maintain building walls and appurtenances. noted step cracks in the wall at 3rd fl outside rm 315 & at 4th fl adjacent to rm 424 at corridor. remedy: repair and or replace
Apr 1, 2019
Resolve - Class - 2
Reissue 35322047r exit doors not self closing. noted defective hardware making the exit doors&classrooms not operate properly at 2nd,3rd&4thfl at the following location at stair f at 2nd&3rd fl&gym area&rm 245,
Apr 1, 2019
Resolve - Class - 2
Reissue 35322046p failure to maintain building in code compliant manner. noted missing ceiling tiles at corridors at the following locationscorridors adjacent to rm 242,414,445 staircase h at 4 fl,staircase h a
Apr 1, 2019
Resolve - Class - 2
Failure to maintain bldg in code complaint manner. noted: missing ceiling tiles at corridors at the following locations;corridor adjacent torm#242,414,445,staircase'h'at 4th fl,staircase'g'at 4th fl & corridor
Mar 8, 2018
Resolve - Class - 2
Reissue#35235629l failure to maintain bldg walls or appurtenances. noted: steps crack in the wall at 3rd fl outside rm#315 & at 4th fl adjacent to rm#424 at corridor. remedy: comply w/code/repair the walls.
Mar 8, 2018
Active - Class - 2
Reissue#35235628j failure to maintain bldg in code complaint manner: lack of emergency lighting for exits,exit discharges & public corridors per bc 1006.1;27-542. noted: at gym area & cafeteria,inoperative emer
Mar 8, 2018
Resolve - Class - 2
Reissue#35235627h failure to maintain bldg in code complaint manner. no fire stopping per bc 712.3;27-345. noted: at cellar level,electrical room,missing fire stopping around pipes in the wall approx 1'x2'.
Mar 8, 2018
Resolve - Class - 2
Exit door not self closing. noted: defective hardware make the exit doors & classrooms not operate properly at 2nd,3rd & 4th fl at the following locations at stair'f'at 2nd & 3rd fl & gym area & rm#245,255,259,
Mar 8, 2018
Resolve - Class - 2
Failure to maintain bldg in code complaint manner. noted: illegal storage of materials such as tables,chairs in the gas meter room at cellar level. remedy: comply w/code/keep the room clean.
Mar 8, 2018
Resolve - Class - 2
Failure to maintain buuilding wlls or appurtenances.noted at 3rd flr rear of room 315 horizontal crack on wall 1/4"gap.rem:maintain buildingwalls(exterior-interior).
Apr 5, 2017
Active - Class - 2
Failuer to maintain building in code compliant manner:no fire stopping per bc712.3;27-345.noted:at closet on 2nd,3rd & 4th flr on front of aexit;and rear of slump sink,also at electrical room at cellar.rem:prov
Apr 5, 2017
Resolve - Class - 2
Failure to maintain building in code compliant manner.lack of emergency lighting for exits exit discharged and public ocrridors per bc1006.1-27-542:note.at gym 2nd flr emergency lights doesnt work(all).rem:repa
Apr 5, 2017
Resolve - Class - 3
Failure to provide circuit directory/identification. did not install any circuit directory/id on 2 circuit breaker panels located inside of the auditirium.(nb)no lighting over circuit breaker panels in electric
Dec 13, 2016 · Penalty $500
Resolve - Class - 2
Reissue: #35120374z failure to maintain building in code-compliant manner. observed step cracks and cracked blocks next to water fountains at 2nd and 4th flrs outside star f. observed step cracks at 2nd,3rd
Jun 29, 2016
Resolve - Class - 2
Re-issue 35093680x failure to maintain bldg in code-compliant manner:no fire stopping per bc 712.3;27-345.no fire stopping observed @penetrations @cellar level in electrical panel rm c2,@stairway f cellar level
May 19, 2015
Resolve - Class - 2
Re-issue 35093683l.failure to maintain bldg wall(s) or appurtenances.@play yard side of bldg,@exterior of stairs c,d & store rm,lighting has been removed.rem:replace lighting @school yard.
May 19, 2015
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner observed step cracks& cracked blocks next to water fountains @2nd,3rd & 4th fls outside stair f.observed step cracks @2ns,3rd & 4th fls @halllway "runways".
May 19, 2015
Resolve - Class - 2
27-371(b) re-issue 35093679z vision panels failure to provide requiredglass panels in the following doors:rms 433,429,353 (both doors),359,304,308,309,313 & 323.rem:provide required glass panels.
May 19, 2015
Resolve - Class - 2
Failure to maintain bldg walls or appurtenances.re-issue 35093682j failure to maintain bulkheads @stair a,f & g causing water penetration.rem:maintain exterior.
May 19, 2015
Resolve - Class - 2
Exit doors not self closing the following doors are missing racked,notclosing or missing closures stair "f" 4th fl missing door;smoke corridor doors 309 & 209; stair "h" @3rd & 2nd fl missing closures,stair h @
May 19, 2015
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner.handicapped bathrm (rm 127) does not provide adequate turning diameter per 27.292.5 of ll 58/87.rem:comply w/code.
May 19, 2015
Resolve - Class - 2
Failure to maintain interior. water penetration into bulkhead at stair a causing concrete spalling & exposure of rusting wire mesh. at bulkhead of stair h water penetration causing spalling. at bulkhead of sta
May 8, 2014
Resolve - Class - 2
27-371(b). vision panel. use of plexiglass in the following doors: rooms 409,420,418,353,304 & 308. remedy: provide required glass panels.
May 8, 2014
Resolve - Class - 2
Failure to maintain exterior. bulkheads at stair a,f,g & h have water penetration. remedy: maintain exterior walls.
May 8, 2014
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1976
- Floors
- 4
- Residential units
- —
- Building area
- 165,620 ft²
- Lot area
- 97,500 ft²
- Zoning
- R6
- Community board
- 304
- Council district
- 37
- Block / lot
- 3298 / 1
- Assessed value
- $18,707,850
- Landmark / historic district
- No
Questions about 1300 Greene Avenue
Who owns 1300 Greene Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 1300 Greene Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 1300 Greene Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 1300 Greene Avenue built?
City records list 1976 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.