Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 28

  • Construction other optional

    Emergency work order-at time of insp feu obsvd the to be in a state of disrepair w/the wall leaning 4' @exp2 and 6' @ exp3.this wall is struct compromised & at risk of collapse.owner to immed engage nyspe w/o diciplinary action & demo endorsed cont'r to immed,fully demolish the compromised wall

    Jul 22, 2025

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 17, 2021

    Dob violation - resolved
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2020

    Jun 20, 2021

    Dob violation - active
  • Failure to post energy grade/score none

    Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3

    Apr 29, 2021

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 9, 2020

    Dob violation - resolved
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Aug 2, 2020

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 2, 2020

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - active
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 3, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - active
Show 18 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 18, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 2, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 1, 2015

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 10, 2013

    Dob violation - resolved
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Jan 1, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 9, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 30, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 12, 2007

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 2, 2007

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Construction other optional

    Hazardous

    Aug 7, 2001

    Dob violation - active
  • Public assembly none

    Pa-public assembly none

    Aug 7, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Oct 19, 2000

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 10, 2000

    Dob violation - dismissed
  • Elevator elevatorrequired

    3p10299

    Feb 7, 2000

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed

ECB violations · 44

  • Class - 2

    Reissue#35721205l exit door not self closing.noted at 2 floor stair a 1st 136,electrical room exit#5 door's are not self closing.rem:comply with code.

    May 6, 2026 · Penalty $1,562

    Active
  • Class - 1

    Failure to maintain building in code compliant manner. at exposures 2(left driveway south side) and 3(backyard) cmu block wall approx. 16'hx100'l, in disrepair wall is angled, shifted blocks and bulging, step,

    Jul 22, 2025 · Penalty $6,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1(2014 code)27-381,bc 1008.1(2022 code).noted throughout entire building no emergency

    Jul 22, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. no fire stopping per bc 712.3(2014 code); 27-345; bc 711.2.4(2022 code). noted at electrical room multiple areas missing firestopping at pipes at ceiling.

    Jul 22, 2025 · Penalty $1,250

    Active
  • Class - 2

    28-301.1. failure to provide ventilation to gas meter room per p115.6(1968 code), fg appendix e(e4)(2014 code). remedy: provide ventilation in gas room.

    Jul 22, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at 4 floor 431, stair b amd 3 fl. 315 water penetration at ceiling and spalling. remedy: repair and/or replace.

    Jul 22, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Exit door not self closing.noted at 2 floor smoke stair a,1 fl 136,electrical room exit 5 main doors are not self closing.rem:repair/replacedoor.

    Jul 22, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code compliant manner. at exposures 1(front), 2(left), 3(back), 4(right) at 1st,2nd and 3rd floors and parapet(inside roof), bulging, running, step cracks, loose masonry througho

    Jul 22, 2025 · Penalty $620

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:observed during inspection of exterior exp #1 & both corners are showing signs of stair cracks/movement/water penetration throughout.remedy:repair and

    Mar 21, 2023 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing.noted:observed during inspection of exterior exit doors electrical rm,generator rm & double wood doors.they were not operational & in disrepair at time of testing.remedy:repair/replac

    Mar 21, 2023 · Penalty $625

    Resolve
Show 34 more ↓
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:observed during inspection of cafeteria kitchen sink not operational at time of inspection.remedy:repair and/or replace.

    Mar 21, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:observed during inspection of electrical meter rm storage of boxes, supplies & cleaning products.remedy:repair and/or replace.

    Mar 21, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35553935n failure to maintain building in code compliant manner.noted:observed gas meter room being used as storage room for building supplies.remedy:comply with code.

    Apr 12, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner at time of inspection. noted: gas meter room being used for storage of bldg maintenance supplies. remedy: comply w/code.

    Apr 9, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain build walls and appurtenances. a front facade stucco cracked at parapet corners also along sides and rear spalling throughout. remedy: maintain exterior building wall

    Mar 20, 2019

    Resolve
  • Class - 2

    Exit door not self closing. noted: at 1st fl cross corridor doors adjacent to rm#106 ¬ #121 & staircase'b'at 3rd fl & stair'a'at 2nd fl,the doors have defective in the top hinges & not close completely.

    Feb 26, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code cokplaint manner. noted: at 1st fl mechanical room,leak in water pipe due to a broken. remedy: comply w/code/replace the pipe.

    Feb 26, 2018

    Resolve
  • Class - 2

    39-b-10;39-b-10;39-b-11;67-b-10:39-b-10-top of car sun station down direction inoperative not working.39-b-10- top of car exhaust fan inoperative not working.39-b-11-replace plastic light guard on top of car.67

    Sep 11, 2017 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner ;illumination for exits,exit discharges &public corridors per bc 1006.1,27-381.@1st flr library,2double doors do not have illuminated exit signs to show exits i

    Jul 7, 2016

    Resolve
  • Class - 2

    27-371(b) vision panel. no vision panel in holding room 241 on 2nd flrrmdy: provide required glass panel.

    May 20, 2015

    Resolve
  • Class - 2

    Emergency signs at elevator call stations missing. emergency sign missing at 1st fl.

    Apr 30, 2014

    Resolve
  • Class - 2

    Exit doors not self closing. smoke corridor doors (3) at main entry exit 1 are racked and do not close. remedy: repair or replace doors.

    Apr 30, 2014

    Resolve
  • Class - 2

    Reissue:3465796417 (partial) the electrical panel rooms is lacking fore-stopping located at rooms 312,318 & 418. rem: provide fire -stopping at open gaps

    Apr 1, 2009

    Resolve
  • Non-hazardous

    Black top at north side of building sinking around drain.remedy:repairsurface.

    Jun 27, 2008

    Resolve
  • Hazardous

    Place of assembly contrary to approved plans. plans show 176 persons permitted.at time of inspection noted seating for approx 299 persons (pa 300740143 - 3fl).remedy:conform to approved plans.

    Jun 27, 2008

    Resolve
  • Hazardous

    Reissue 34560424k. no fire stopping in walls & ceiling room 101a, 101b,103, 110, 114, 312,m 318, 418.remedy:provide fire stopping in all openings.

    Jun 27, 2008

    Resolve
  • Hazardous

    Re-issue:34510229j. no fire stop in wall and ceilings room 101a,101b, 103,119a,118,114,110,218,318,418,112,212,312. remedy: provide fire stops.

    Feb 22, 2007

    Resolve
  • Hazardous

    Re-issue:34510228h. roof leaks into room's 138,337,315,229,239 by window. remedy: repair roof.

    Feb 22, 2007

    Resolve
  • Non-hazardous

    Re-issue:34510230r. vertical cracks from 4th fl to 2nd fl, exit b from4th fl by same corner minor cracks in front of building by handicap, also cracks in perimeter wall by a.c. units. remedy: repair/replace.

    Feb 22, 2007

    Resolve
  • Non-hazardous

    Reissue #34466559r. roof leaks to rooms 138,337,315 from duct work rm 229,239 by windows. remedy: repair roof, and duct work.

    Feb 1, 2006

    Resolve
  • Non-hazardous

    No fire stops in wall and ceilings in rooms #101a,101b,103,119a,118,114,110,218,318,418,112,212,312. remedy: provide fire stops.

    Feb 1, 2006

    Resolve
  • Non-hazardous

    There are vertical cracks from 4th flr to 2nd flr exit b; from 4th flrto 1 flr by same side corner; minor cracks in front of the bldg by handy camp, also cracks in perimeter wall by a.c. units. remedy: repair/r

    Feb 1, 2006

    Resolve
  • Non-hazardous

    Reissue #34440479l roof leaking into interior locations:gymnasium,and auditorium.remedy:repair roof leaks.

    Mar 23, 2005

    Resolve
  • Non-hazardous

    Failure to maintain-defect is large hole and unevens asphalt surface at west side of bldg.remedy:repair surface

    Jun 10, 2004

    Resolve
  • Non-hazardous

    Failure to maintain.defect is.girls bathroom #344 partition wall is missing.remedy:replace wall

    Jun 10, 2004

    Resolve
  • Non-hazardous

    Failure to maintain.defect is auditorium sheet rock wall and ceiling are loose and bulging.remedy:repair sheetrock wall.

    Jun 10, 2004

    Resolve
  • Non-hazardous

    Failure to maintain.defect are roof leaks at various locations.locations are (1) first floor corridor next to room #138 (2)gym (3)room #337(4)auditorium #315.remedy:repair roof

    Jun 10, 2004

    Resolve
  • Non-hazardous

    Failure to maintain. defect is 1st floor boys bathroom # 124 partition door is missing. remedy: replace bathroom partition door.

    Mar 24, 2003

    Resolve
  • Non-hazardous

    Peration of a place of assembly without a current permit pa#. no pa for 1st floor lunch room. no pa for 3rd floor multi purpose room. obtain: obtain pa permit.

    Aug 7, 2001 · Penalty $500

    Resolve
  • Non-hazardous

    Altered building occupied without a valid certificate of occupancy alt building under alt#300658535. remedy: obtain a valid c of o.

    Aug 7, 2001

    Resolve
  • Non-hazardous

    Failure to maintain.defect is as follows.1-stress crack in brick wall (east) in gymnasium remedy:make all repairs

    May 31, 2001

    Resolve
  • Non-hazardous

    Failure to maintain.defects are as follows 1-water penetration thru roof into gymnasium remedy:make all repairs t

    May 31, 2001

    Resolve
  • Non-hazardous

    Failure to maintain.defects are as follows.1-roof-parapet walls on north,east and south walls have stress cracks in them 3'-4' long 2-exterior walls at ladder leading to upper roof has stress crack in cement wa

    May 31, 2001

    Resolve
  • Non-hazardous

    Altered building occupied without a valid c of o.temporary c of o #300658535 expired on 8-11-00.rem:obtain valid c of o.

    Oct 19, 2000

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W9)
Year built
1931
Floors
4
Residential units
—
Building area
67,000 ft²
Lot area
22,588 ft²
Zoning
R6
Community board
304
Council district
34
Block / lot
3230 / 27
Assessed value
$3,456,900
Landmark / historic district
No

Questions about 1155 Dekalb Avenue

Who owns 1155 Dekalb Avenue?

The owner of record in NYC Department of City Planning PLUTO data is 1155 Dhs L.l.c..

Does 1155 Dekalb Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 1155 Dekalb Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 1155 Dekalb Avenue built?

City records list 1931 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.