Violations at 61 St Nicholas Avenue

Brooklyn, NY 11237 · BBL 3-03212-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

29 DOB violations, newest first.

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 18, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 18, 2021

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 12, 2020

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 27, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 27, 2019

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 13, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 22, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 1, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 29, 2015

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 7, 2011

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed

ECB violations

The newest 50 of 77 ECB violations. The city keeps the complete history.

  • Class - 2

    Stair and/or floor identification signs missing and/or defective:-at the time of inspection, the following exit discharges door did not havedesignation:-#6, #4, #5. remedy: install and/or repair signs.

    Apr 30, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. at the time of inspection, stair "g" and "f" swings against the path egression the 1st floor, storage in electrical meter room, cracks in stone retaining w

    Apr 30, 2026 · Penalty $1,250

    Active
  • Class - 2

    Re-issue 35719729j. at the time of inspection, the following emergencylights were inoperable:-illuminated exit sign at stair "d" on 4th floor, a missing buld from (2)emergency light 3rd floor gym box #15, #16 h

    Apr 30, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. at the time of inspection, the following doors were not self-closing:-stair "g" on 4th floor, stair "g" 2nd floor, stair "f" on 1st floor, exit #2 vestibul

    Apr 30, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35677509p failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.observed at auditorium,cafeteria and several location thr

    May 9, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35672827h failure to mintain building in code-compliant mannerillumination for exits,exit discharges and public corridors per bc 1006.1;27-381.at time of my inspection i observed at the 1st floor 17 sta

    Apr 29, 2024 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.noted:at 1st fl box 17 by stair a,auditorium box 21,basement cafeteria box 8

    Mar 9, 2023 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing.noted:the exterior doors at exit 2,and 9 are not working properly.rem:repair/replace door.

    Mar 9, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at auditorium front right and rear, basement slop sink corridor by stair d,girlsrestroom(005),and smoke by exit 2 and smoke by exit 2 and 3,the doors

    Mar 9, 2023 · Penalty $625

    Resolve
  • Class - 1

    Fail to communicate&maintain record of orientation [email protected]:ato my insp of 4stybldg const work in progress i observed approx8workers on jobsite.upon request for sitesafety orientation to be perform@

    Aug 23, 2021 · Penalty $2,500

    Resolve
  • Class - 2

    Const super fail to perform his duties.note:ato my insp of 4stybldg const super fail to perform his duties preshift safety meeting missing alot of days,no site safety orientation for workers on jobsite presentl

    Aug 23, 2021 · Penalty $2,500

    Resolve
  • Class - 2

    Reissue#35321694z at corridor exit 8h wall/ceiling damaged due to ongoing water penatration at ceiling. remedy: comply w/code/maintain bldg.

    Apr 9, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    02x10,23b10,39b10. 02x10-repair emergency phone; 23b10-replace n/g bulbs on the hall button station (bsmt); 39b10-repair top of the car light.

    Nov 1, 2018

    Resolve
  • Class - 2

    Failure to post or properly post permit for work at premises upon inspection of complaint #3669655 i noticed there wasn't a permit posted for the sidewalk shed on site. i checked the dob system and there isnt

    Oct 23, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1; 27-542. noted: at auditorium, cafeteria and gym

    Feb 28, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: water damaged to walls due to water penetration at boiler area, corridor of exit 8h and bulkhead staircase 6f. rem: comply with code/repair the wall

    Feb 28, 2018

    Resolve
  • Class - 2

    Exit door not self closing. noted: exit doors of auditorium and exit door #9i and teacher lunch room at 2nd floor, the doors have defectivein the top hinge and not operate properly. rmdy:comply with code/repai

    Feb 28, 2018

    Resolve
  • Class - 2

    Reissue 35094357k emergency signs elevator call stations missing defective, non-compliant. emergency signs at elevator call stations missing at all levels. rmdy: install signs at all levels.

    May 29, 2015

    Resolve
  • Class - 2

    Emergency signs at elevator call stations missing. elevator signage missing at all levels. remedy: install signs at all levels.

    Apr 30, 2014

    Resolve
  • Class - 2

    Re-issue # 35015955m. electrical panel room has been obstructed by installation of 5'-0" high telecommunications tower. remedy: remove telecommunications tower or relocate.

    Apr 30, 2014

    Resolve
  • Class - 2

    Re-issue # 35015959j. doors racked at stair "d" 2nd floor, stair "g" 1st floor from auditorium, exit 7, exit e 1st floor & door at exit 9. remedy: repair or replace doors.

    Apr 30, 2014

    Resolve
  • Class - 2

    Re-issue # 35015957x. no fire stopping in wall openings of rooms b-52 & in electrical panel room on 1st floor next to custodians office. remedy: provide fire stopping.

    Apr 30, 2014

    Resolve
  • Class - 2

    Re-issue # 35015956y. interior stairs treads deteriorating & cracked in stairways b,c,d,e, & f creating uneven tread surface & tripping hazards from 1st floor to 4th floor. remedy: replace/repair stair treads.

    Apr 30, 2014

    Resolve
  • Class - 2

    41b07/48y13/70y13/99bb11/40bb11/29d06/ 41b-provide code compliant sign. 48y,70y-seal all leaks. 99bb-provide current cat 1 tag. 40bb-fire extinguisher. 29d-greenfield.

    Mar 28, 2014

    Resolve
  • Class - 2

    Missing mortar at mortar joints and cracked coping at parapet at various locations. remedy:make necessary repairs.

    Apr 17, 2013

    Resolve
  • Class - 2

    Plaster damage walls @ doors of exits 899. remedy: make necessary repairs.

    Apr 17, 2013

    Resolve
  • Class - 2

    Door racked at stair d 2 floor, stair g 1st floor from auditorium and door at exit 9. remedy:repair or replace doors.

    Apr 17, 2013

    Resolve
  • Class - 2

    Cracks in walls of main electric. panel room at various locations. remedy:make necessary repairs.

    Apr 17, 2013

    Resolve
  • Class - 2

    Opening in walls of electric rooms with no fire stopping. remedy: provide fire stopping.

    Apr 17, 2013

    Resolve
  • Class - 2

    Reissue 34942511m.interior stairs @ stsair b&d basement thru 3rd floorstairs e&f 1st thru.4 floors & stair b basement to 1st fl have cracked& deteriorating treads,leaving uneven tread surface causing unsafe con

    Apr 17, 2013

    Resolve
  • Class - 2

    Reissue 34958525j. telecommunication tower installed in electrical subpanel room obstruction elect panels. remedy:remove tower.

    Apr 17, 2013

    Resolve
  • Class - 2

    Reissue: 34901963m. the electrical room has a 5' high tele-communication tower installed in the passaeway leading to electrical panels. (noted: passageway decreased towards the electrical panels). remedy:remove

    Apr 13, 2012

    Resolve
  • Class - 2

    Reissue 34901964y interior staircase #6 btwn 3rd and 4th floor lvl is crumbing and cracked causing a tripping hazard noted stairs was patched but starting to crumble again rem: repair and/or replace staircase #

    Apr 13, 2012

    Resolve
  • Class - 2

    1)at staircase #6 rear of building between the 3rd and 4th floors steps are severely defective causing trip hazard.2)at the cellar level cafeteria floor is severely defective at various areas throughout w/deter

    Feb 10, 2011

    Resolve
  • Class - 2

    At the cellar level in the electrical panel room. telecommunication equipment has been installed. (potential hazard). remedy: remove telecommunications equipment from electrical panel room.

    Feb 10, 2011

    Resolve
  • Class - 2

    Reissue # 34742838h illegal installed combustible tele-communication equipment inside electrical panel room in basement.

    Apr 15, 2010

    Resolve
  • Class - 2

    Reissue 34742837x interior stairs crumbling with severe rust damage spalling steps concrete missing. remedy: make safe !!

    Apr 15, 2010

    Resolve
  • Class - 2

    Water penetration into rooms 312, 212, 112, causing pieces of ceiling to fall remedy: seal penetration

    Apr 15, 2010

    Resolve
  • Class - 1

    Failure to safeguard all persons and property affected by constructionoperations. appl #302108369. noted: exit staircase (c) between 1st flr& basement closed off, approx 18 months. remedy: make safe! open

    Apr 15, 2010 · Penalty $12,000

    Resolve
  • Class - 1

    Sec. 28-105.12.8. work contrary to site safety plan drafted by lic #1052 stating no obstruction to means of egress w/o written permission from dob. noted staircase (c) closed between flrs 1 & basement level.

    Apr 15, 2010 · Penalty $8,000

    Resolve
  • Class - 2

    The electrical room as basement level has installed a tele-communication/phone tower with 2 addition towers right in front of the electricalunits. rem: remove tele-communication/phone tower out of the electrica

    Apr 1, 2009

    Resolve
  • Class - 2

    Interior stairs & landing is cracked & rotten creating a trapping hazard located at staircase #6 between 3rd & 4th floor. rem: repair/replace stairs

    Apr 1, 2009

    Resolve
  • Class - 2

    Reissue:34657963k the plaster is spalling off the walls & ceiling located in room 202 2nd floor & ceiling located in room 202 2nd floor & room 302 3rd floor & both side exit in the auditorium. rem: repair/rep

    Apr 1, 2009 · Penalty $2,500

    Resolve
  • Non-hazardous

    Reissue 34560419x.plaster damage at room 302,202 & rear exits both sides of auditorium vestibule. remedy:replace plaster.

    Jun 27, 2008

    Resolve
  • Hazardous

    Re-issue:34510264p. missing two vestibule doors at each exit 6 & 7. remedy: install doors at above location.

    Feb 22, 2007

    Resolve
  • Hazardous

    Re-issue:34510258z. handrails missing at stairs outside of playground and next to stair #8 (both side missing). remedy: replace handrails.

    Feb 22, 2007

    Resolve
  • Hazardous

    Re-issue:34510257r. missing handrails on stairwell 3-5 on 2fl level also in subfloor by exit 4. remedy: install handrails.

    Feb 22, 2007

    Resolve
  • Hazardous

    Re-issue:34510255n. defective plaster in ceiling in room 202 & 302 andon wall of rear exit both side of 2 exits auditorium. remedy: repair defective plaster at above location.

    Feb 22, 2007

    Resolve
  • Non-hazardous

    There are missing 2 vestibule doors at each exit 6 and 7. remedy: install doors.

    Feb 2, 2006

    Resolve
  • Non-hazardous

    There are total closed gates (chain and padlock) leading to willoughbyand sydam st during school operations. remedy: remove all obstructionsimmediately.

    Feb 2, 2006

    Resolve