Violations at 40 Beaver Street
Brooklyn, NY 11206 · BBL 3-03137-0026 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
12 DOB violations, newest first.
- Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed
ECB violations
The newest 50 of 82 ECB violations. The city keeps the complete history.
- Class - 2
Reissue ecb #35692096l. failure to maintain building in code-compliantmanner. noted: at (basement)electric meter rm with large vertical/horizontal cracks throughout various areas. remedy: repair and/or replace.
Apr 24, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: at (3rd fl) hallways installed/hung of non fire retardant decorations to ceilings throughout. remedy: comply with code.
Apr 24, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted: at (2nd fl)stair b, d (3rd fl)stair d, a installed/used of key locking devices. r
Apr 24, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at (basement)cafeteria, gym, auditorium emergency lights not wor
Apr 24, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: at (basement)electric meter rm with storage of multiple items, boxes, pipes, carts etc...remedy: comply with code.
Apr 24, 2026 · Penalty $1,250
Active - Class - 2
Reissue ecb #35692095j. failure to maintain building in code-compliantmanner. noted: at (basement)exit 6, gym auditorium, stair c(1st fl), stair c(3rd fl) hallway smoke door near rm 306 doors are in disrepair/r
Apr 24, 2026 · Penalty $3,125
Active - Class - 2
Reissue #35677511y: failure to maintain building in code-compliant manner: at cellar/bsmt level in electrical meter room as large cracks in vertically and horizontally on wall. remedy: repair and/or replace.
Apr 24, 2025 · Penalty $3,125
Active - Class - 2
Reissue #35677512x: failure to maintain building in code-compliant manner: smoke doors, corridor doors by rm 307, 2nd floor by rm 206, 1st floor smoke door @ rm 150, 104, 106, cafeteria gymnasium and cellar lev
Apr 24, 2025 · Penalty $3,125
Active - Class - 2
Reissue#35672482l failure to maintain building in code-compliant manner.at time of my inspection i observed at the 3rd floor corridor by 307and 2nd floor corridor by room 206 1st floor smoke door at room 100,10
Apr 30, 2024 · Penalty $1,562
Active - Class - 2
Reissue#35672484p failure to maintain building in code-compliant manner.at time of my inspection i observed at the basement level the boilerroom and the electrical meter room has a large running step cracks in
Apr 30, 2024 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code compliant manner.noted:at basement level,the boiler room electrical meter room has large running step cracks in various areas throughout the cmu block walls.rem:repair and/o
Mar 7, 2023 · Penalty $625
Active - Class - 2
Exit door not self-closing.noted:the exterior door at exit 10 and boiler room is defective.rem:repair/replace door.
Mar 7, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:at 3rd floor corridor by 307,2nd floor corridor by 206,1st floor smoke door at room 100,102,104 and 106,cafeteria by kitchen,basement stair c,gymnasiu
Mar 7, 2023 · Penalty $625
Active - Class - 2
Reissue#35654826r noted:at 3rd floor stair d by 300,2nd floor stair a by 215,corridor by 206,1st floor stair d by 100,corridor by 105,106 and 142,cafeteria by exit 6,gymnasium by exit 6,auditorium,basement,box
Mar 7, 2023 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.at time of inspection observed at 1st,2nd,auditorium and gymnasium emergency
Apr 7, 2022 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner note@rof level on various roofs roofing material in disrepair w/cracks along parapet walls&hole thruout w/leaks causing damage to ceilings below.mainly in gym&au
Jun 16, 2021 · Penalty $625
Resolve - Class - 2
28-301.1 unlawful display of artwork in corridors greater than 20% perfdny 2008 code fc 803.3.2. noted on 1st and 2nd floor artwork display on walls and door in various location. remedy: comply w/ nov
Mar 18, 2019
Resolve - Class - 2
Exit door not self closing. 3rd floor exit 9 door not self closing. remedy: repair or replace
Mar 18, 2019
Resolve - Class - 2
Exit door not self-closing. noted: at 1st floor staircase (a)&(d) & room #152 & at 2nd floor staircase (d) & at 3rd floor, room #352. the doors have defective in the top hinge and not close completely. rem: com
Feb 28, 2018
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: at auditorium area, water damaged to ceiling at various places due to water penetration through roof. rem: comply with code/repair or replace.
Feb 28, 2018
Resolve - Class - 2
Failure to maintain in code compliant manner.fail to provide wired vision panel as required per 27-371(6) @ time of inspection i observed nowired glass on doors @ rooms 249,341,302,exit6 in cafeteria,all 4 exit
Sep 30, 2015
Resolve - Class - 2
Reissue#35015975j failure to maintain bldg in code compliant manner.noted plaster damaged & spalling @ ceiling of auditorium.rem repair ceiling
Sep 30, 2015
Resolve - Class - 2
Reissue#35015976l failure to maintain bldg walls or appurtenances.noted water penetrating through roof causing ceiling damage in auditorium.rem repair or replace roof
Sep 30, 2015
Resolve - Class - 2
Reissue#35094209z failure to maintain bldg in code compliant manner.noted in staircase a,b & c bulkheads have hairline cracks.rem repair defects noted.
Sep 30, 2015
Resolve - Class - 2
27-mis 28xbc reissue#35094210x.miscellaneous violations:playground rubber matting has separated & is curling in several locations creating tripping hazard.rem repair or replace matting
Sep 30, 2015
Resolve - Class - 2
Playground rubber matting has separated & is curling in several locations creating tripping hazard. remedy: repair or replace matting.
Apr 23, 2014
Resolve - Class - 2
Failure to maintain building in code-compliant manner. in staircase a,b & c bulkheads have hairline cracks. remedy: repair walls in staircase bulkheads.
Apr 23, 2014
Resolve - Class - 2
27-371(b). use of plexiglass or thermoplastic. at rooms 249,341 & 302 used plexiglass in doors. all 4 exit door next to room b33, at rear of kitchen exit door & at exit #6 in cafeteria. remedy: provide require
Apr 23, 2014
Resolve - Class - 2
Re-issue # 35015976l. water penetrating through roof causing ceiling damage in auditorium & 3rd floor hallway. remedy: repair/replace roof.
Apr 23, 2014
Resolve - Class - 2
Re-issue # 35015978p. openings in wall of electrical room with no fire stopping. remedy: provide fire stopping in electrical room.
Apr 23, 2014
Resolve - Class - 2
Excessive combustibles on walls of corridors at 1st & 2nd flrs, also light of 115,215 & 147. remedy: remove combustibles.
Apr 1, 2013
Resolve - Class - 2
Openings in walls of elect rm w/no fire stopping. remedy: provide firestopping.
Apr 1, 2013
Resolve - Class - 2
Doors racked at exit 9 & exit 5, closer missing at gym door. remedy: repair/replace door. replace closer.
Apr 1, 2013
Resolve - Class - 2
Water penetrating through roof causing ceiling damage in auditorium. remedy: repair/replace roof.
Apr 1, 2013
Resolve - Class - 2
Plaster damaged & spalling at ceiling of auditorium. remedy: repair ceiling.
Apr 1, 2013
Resolve - Class - 1
Fail to comply w.comm order. noted: fail to comply w. swo 3798 viol # 34815252p, 34815253r, for no outrigger beams notification, work w.o a permit for facade work. equipment was removed off job site w/o notice
May 24, 2010 · Penalty $12,000
Active - Class - 3
Occupancy contrary to bldg dept records room 303 converted to gym. remedy: discontinue illegal use
Mar 24, 2010
Resolve - Class - 2
Water penetration into auditorium. remedy: seal penetration
Mar 24, 2010
Resolve - Class - 3
Reissue 34742834k warping gym floor near water fountain remedy: repairfloor
Mar 24, 2010
Resolve - Class - 3
Reissue 34510187k, 34742831p masonry block wall in kitchen storage room is cracked vertically. remedy: repair wall
Mar 24, 2010
Resolve - Class - 1
Work w/o a permit noted no permit filed for demo or replacement of brick work at all exposures at roof lvl of school history of noncompliance rem: obtain permit
Dec 3, 2009 · Penalty $25,000
Active - Class - 2
Failed to provide approved accepted plans at job site at time of insp noted no approved cd-5 on site for installation of outrigger beams rem: history on none compliance provide plans
Dec 3, 2009 · Penalty $10,000
Active - Class - 2
Failed to notify dept obtain permit prior to use installation off outrigger beams in connection w/ suspended scaffolds noted no outrigger beams notification for installation of equipment at exp#4 rem: history o
Dec 3, 2009 · Penalty $10,000
Active - Class - 2
Cement above the glazed block wall is bulging opposite side wall of the kitchen/storage by exit 5 at basement level. rem: repair bulging cement wall.
Mar 31, 2009
Resolve - Class - 2
Gymnasium wooden floor is damaged caused by water by the water fountain at basement level rem: repair/replace gynasium floor.
Mar 31, 2009
Resolve - Class - 2
Roof level above the fan room has become porous and allowing rain into the building porous and allowing rain into the building causing interior damages. rem: water proof above fan room.
Mar 31, 2009
Resolve - Class - 2
Exterior slate floor by exit 7 is loose on 1st floor level. rem: repair slate floor.
Mar 31, 2009
Resolve - Class - 2
Reissue: 34510187k masonry blockwall in the kitchen/ storage at basement level is cracked vertically from ceiling to floor. rem: repair/replace cracked wall.
Mar 31, 2009
Resolve - Class - 2
Reissue: 3467951n floor tiles at stair "b" is loose & missing between 2nd & 3rd floor. rem: replace tiles.
Mar 31, 2009
Resolve - Hazardous
Missing floor tiles stairway b between 3, 2 floor landing (possible acm)9" tiles. remedy:replace tiles.
Jun 26, 2008
Resolve