Violations at 190 Manhattan Avenue
Brooklyn, NY 11206 · BBL 3-03025-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
26 DOB violations, newest first.
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active
ECB violations
The newest 50 of 83 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 1st fl auditorium 2nd fl cafeteria 3rd fl gym emergency lights not
Jun 8, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at 1st fl exit 1/main entrance,stair a 2nd fl stair a,hallway smoke door near rm205 3rd fl hallway smoke near rm 353 doors are in disrepair/racked whe
Jun 8, 2026 · Penalty $1,250
Active - Class - 2
Reissue #35557708l failure to maintain building wall(s) or appurtenances.noted:observed at exp #1 stone steps missing mortar at various locations also at exp #4 next to exit "8" same violation condition.remedy:
Apr 11, 2022 · Penalty $3,125
Resolve - Class - 2
Reissue #35557709n failure to maintain building in code compliant manner use of prohibited door and/or hardware per bc1008.18;27-371(j) noted:observed at gymnasium at all doors hoycylindars installed or the ins
Apr 11, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue #35557710l failure to maintain building in code compliant manner illumination for exits exit discharges & public corridors per bc1006.1;27-381.noted:observed at gymnasium & auditorium emergnecy light no
Apr 11, 2022 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: observed transparent thermoplastic sheet being used for vision panel on corridors fire proof self closing door next to "pod 1203". remedy: repair &/or r
Mar 30, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.noted: observed existing emergency lights w/battery back up power at 3rd fl stai
Mar 30, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: observed at gymnasium,all exit doors have key cylinders installed on the insterior side
Mar 30, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg walls or appurtenances. noted: observed at exp#1,stone steps are missing mortar at various locations. remedy: maintain exterior bldg wall.
Mar 30, 2021 · Penalty $1,250
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at 3rd flr, adjacent to room 332 in the corridor, vertical masonry crack with missing bricks in the wall. rmdy: comply w/code/repair the wall.
Feb 16, 2018
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner: lack of emergency lighting fo rexits, exit discharges and public corridors per bc 1006.1;27-542. noted: at auditorium and gym area, inoperative emergency light
Feb 16, 2018
Resolve - Class - 2
Exit door not self closing. noted: at gym area defective door left entrance door & the door not close completely. also,room#338 was a broken closer. exit door at cafeteria area has a broken closer & not close
Feb 16, 2018
Resolve - Class - 2
Failure to maintain building in code-compliant manner. use of prohibited door hardware per bc 1008-1-8; 27-371(j) use of prohibited attacheddoor stops at rooms 101,113,116,121,133,144,148,150,156,159,174,178,20
Feb 6, 2015
Resolve - Class - 2
Exit doors not self closing. the following doors are defective or havedefective closures/hardware: stair "f" at 1st and 3rd flr, stair e at 1nd flr stair "d" 2st floor vestibule door and smoke corridor door bet
Feb 6, 2015
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.no fire stopping perbc 712.3; 27-345. missing fire stopping at basement level stair b,pipepenetrations missing fire stopping in room 122 per previously issued
Feb 6, 2015
Resolve - Class - 2
Stair indentification signs missing and/or defective.stair exit # designation at each level throughout. exit number should be at exits to exterior. rmdy: correct signage remove/replace signs where necessar
Feb 6, 2015
Resolve - Class - 2
Missing fire stopping on all floors pipe penetration through walls.rem:provide fire stopping.
Feb 28, 2014
Resolve - Class - 2
Reissue 35003655m.occupancy contrary to cert of occupancy.noted @ left& right side parking in side yards.multiple cars.rem:remove all cars.
Feb 28, 2014
Resolve - Class - 2
Cracked exterior brick masonry. at small set back left of front main entry, approx 10'vertical carck in exterior brick masonry facade from 3rd floor to parapet wall. rmdy: repair brick facade.
Feb 14, 2013
Resolve - Class - 2
Exit signs not illuminated. at main entry, 3 exit signs are not illuminated and are not on 24 hr circuit. exit lights appear to be on a switch or service brearker that serves other thatn emer.lighting.rmdy:comp
Feb 14, 2013
Resolve - Class - 2
Missing fire stopping. at room 170, approx 1/2 sq ft ceiling opening and room 122 approx 2'x2' wall opening to concealed space. remedy: provide fire stop, seal all openings.
Feb 14, 2013
Resolve - Class - 2
Roof penetration. at 3rd floor gym a (boys), moisture penetration fromroof. remedy: water proof roof.
Feb 14, 2013
Resolve - Class - 2
Missing doors. at rooms 180 and 222, interior fireproof door missing inside room to concealed space. rmdy: replace doors
Feb 14, 2013
Resolve - Class - 2
Reissue #34940692l defective wood flooring. at 3rd flr gym and room331buckling of wood flooring creating a trip condition. rmdy: repair flooring.
Feb 14, 2013
Resolve - Class - 2
Reissue #34940693n occupancy contrary. 23 cars parked at left side areaway and 25 cars parked at right side areaway.these cars partially obstruct fdny access.rmdy: remove all vehicles or amend dob records-disco
Feb 14, 2013
Resolve - Class - 2
Reissue #34940694p defective exterior iron fence gate. at front left fence gates broken with iron hinges snapped off, gate are not workableremedy: repair iron fence gates
Feb 14, 2013
Resolve - Class - 2
Reissue #34940697k. roof ponding. ponding of water on roof leak roof drain. remedy: remove ponding water.
Feb 14, 2013
Resolve - Class - 2
Water penetration brick facade at various locations throughout. remedy: maintain weather proof integrity of facade.
Jan 12, 2012
Resolve - Class - 2
Water pooling/discharging thru drains at: roof near exit 7 water pooling around roof drain, at: foundation (cellar) various drains water pooling/discharging onto floor. remedy: repair drains.
Jan 12, 2012
Resolve - Class - 2
Doors not closing at: 1st story exit 5, 2nd story cross corridor doors near rm 213, 3rd story cross corridor doors near rm 303, 3rd story girls gym door to public corridor. remedy: replace doors.
Jan 12, 2012
Resolve - Class - 2
Plaster ceiling water damaged/spalling at: girls gym & room 323 3rd story. remedy: repair and/or replace defects noted.
Jan 12, 2012
Resolve - Class - 2
Reissue # 34934252r. broken hinge welds at: wrought iron gate on graham avenue front of premises (2 hinges disconnected). remedy: repair gate.
Jan 12, 2012
Resolve - Class - 2
Reissue # 34934253z. vehicles jumping curb & parking on public sidewalk & garden area at school property & driving on sidewalk to adjacent property curb cut (195 graham ave). remedy: remove illegally parked car
Jan 12, 2012
Resolve - Class - 2
Reissue # 34934254k. wood flooring buckling at: 3rd story room 331 and 3rd floor gym. remedy: repair and/or replace flooring.
Jan 12, 2012
Resolve - Class - 2
Reissue # 34934256y. water fountain cover plate displaced at: gym "a" (boys) steel cover plate for water fountain dislodged/displaced. remedy: repair and/or replace fountain cover.
Jan 12, 2012
Resolve - Class - 2
Interior drinking water fountain metal base cover is not attached located in the 3rd fl gym "a" remedy: re-attached metal base cover
Oct 5, 2011
Resolve - Class - 2
The plaster on the ceiling is spalling located in the gym on the 3rd fl remedy: repair and / or replace plaster
Oct 5, 2011
Resolve - Class - 2
Interior wooden floors are rotten & rising causing a tripping hazard located in room 331 & 3rd fl gym. remedy: repair wooden fl
Oct 5, 2011
Resolve - Class - 2
Vehicles jumping the curb ( w/o a curb cut ) and parking on public sidewalk and garden area at school property. ( noted : no curb cut provided on graham ave & manhattan ave ) remedy: remove illegally parked veh
Oct 5, 2011
Resolve - Class - 2
Exterior wrought iron gate is rusted and not fully attached to the post located on graham ave. remedy: repair iron gate
Oct 5, 2011
Resolve - Class - 2
Defective doors on 3fl exit 3 & 4 & 7 3fl gym exit door,room 301,room 179 2fl exit 7 & 4,1fl exit 3,4 reissue 34770483x.remedy:repair & or replace doors.
Jan 28, 2010
Resolve - Class - 1
Use of supported scaffold w/o a scaffold user certificate.observe at school room 349 (lab) according to foreman on site.carlos a siteman from lasardo const worker fell from baker scaffold foreman did not provid
Sep 3, 2009 · Penalty $800
Resolve - Class - 1
Failure to institute maintain safety equipment measures no guardrails observed at school room 349 (cab) a baker scaffold 12ft ht w/ working platform at 8ft w/o guardrails on fl after worker fell from it with
Sep 3, 2009 · Penalty $25,000
Resolve - Class - 3
Defective stairway door:noted at 3fl stair a,e,f, 2fl a,b,c,e. remedy:replace doors.
Apr 1, 2009
Resolve - Class - 2
Re:34692284m.cellar electrical panel room missing fire stopping above door frame.wire mesh not fire rated.remedy:fire rate above door frame.
Apr 1, 2009
Resolve - Class - 2
Reissue 34505488h cellar electrical room over entry door open wire mesh missing fire stopping. remedy: provide fire stopping.
Aug 13, 2008
Resolve - Non-hazardous
Re-issue # 34505487x. door hinge is broken located at the corridor smoke doors on the 2nd floor adjacent to room 241. remedy: replace or repair broken hinge.
Apr 11, 2007
Resolve - Non-hazardous
Re-issue # 34505984k. door check is missing located at stairway "f" onthe 3rd floor. remedy: install door check.
Apr 11, 2007
Resolve - Non-hazardous
Re-issue # 34505482r. corridor doors are not self-closing located at exit 9 on the 1st floor. remedy: repair or replace doors.
Apr 11, 2007
Resolve - Non-hazardous
Re-issue # 34505488h. missing firestopping around pipe penetration located in the electrical room on cellar level. remedy: provide fire stopping.
Apr 11, 2007
Resolve