Violations at 331 Marcy Avenue

Brooklyn, NY 11206 · BBL 3-02227-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

The newest 50 of 60 DOB violations. The city keeps the complete history.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 10, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 10, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 10, 2013

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2011 inspection/test

    Oct 1, 2012

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 14, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 14, 2011

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Vcat1-elevator annual inspection / test elevatorrequired

    Oct 8, 2010

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 22, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 22, 2010

    Vw*-violation - work w/o permit dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 17, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 17, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 21, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 21, 2008

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 14, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 14, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 27, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 27, 2006

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 16, 2005

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 11, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 11, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 27, 2003

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatorrequired

    3f5485

    Aug 20, 2002

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Elevator elevatorrequired

    3p6664

    Feb 3, 2000

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 6, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active

ECB violations

The newest 50 of 121 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 3rd fl stair b,d,hallway smoke door near rm 353 2nd fl stair a,b,d,hallway smoke door near stair d 1st fl stair e,c,exit 9,7/8,1/2 hallway smoke do

    Jun 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 3rd and2nd floors installed/hung non fire retarted throughout various areas of hallways/ceilings.rem:comply with code.

    Jun 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue on ecb#35717464y failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 2nd fl library 1st fl cafeteria,gym,audit

    Jun 2, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue ecb#35717465x exit door not self closing.noted:at 1st fl exit 5/6,3/4 doors are in disrepair/not closing when tested.rem:repair/replace door.

    Jun 2, 2026 · Penalty $1,562

    Active
  • Class - 2

    Exit door not self-closing properly at the time of inspection. at the time of inspection i observed near rm-353 one coridoor exit door, 3rd fl. stairway "d" one exit door, 2nd. fl. stair "b" 3 exit doors, 2nd s

    Apr 22, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compiant manner. illumination forexits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection i observed and noted at 2nd floor auditorium in

    Apr 22, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35654789r date of issue: 01-23-2023. failure to maintain building in code-compliant manner at cellar level observed at electrical room, water penetration through wall and floor creating hazardous condi

    Apr 22, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue.misc fsc appendix e(e4,2014 code)gas meter room no fresh air intake(1968 code).remedy:comply with code.

    Jan 23, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35636171x.failure to maintain building in code compliant manner.cellar level electrical room area some water penetration through wall.remedy:repair and/or replace.

    Jan 23, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue #35557748x failure to maintain provide ventilation to gas meter room per j.5.6 (1968 code) fgc appendix e(e4)(2014) code noted:observed not natural & mechanical ventilation in gas meter.remedy:comply w

    Mar 24, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:at time of inspection observed at roof level chiminey has several crack and loose bricks.rem:maintain chimney.

    Mar 24, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue #35560725k failure to maintain building in code compliant manner.illumination for exits.exit discharges & public corridors per bc 1006.1 27-381.noted:at time of inspection observed existing emergency l

    Mar 24, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue #35577189r failure to maintain building in code compliant manner.at cellar level observed at electrical room water penetrating through wall & floor creating hazardous condition.remedy:repair and/or rep

    Mar 24, 2022 · Penalty $1,562

    Resolve
  • Class - 1

    Reissue#35548147x failure to maintain bldg in code compliant manner. noted: at cellar level,observed at the electrical room water is penetrating through the walls & floor,creating an hazadous condition.

    May 21, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Reissued#35540497j. failure to maintain bldg in code compliant manner.noted: observed at cellar level,water penetrating & pooling at main electrical room & adjoining areas. remedy: repair &/or replace.

    Apr 9, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted observed: at cellar lamp storage room & boiler room areas masonry units on wall. remedy: repair &/or replace.

    Apr 9, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted observed: exesive storage of wooden,desk,card board boxes,plastic,bins,drywall sheets at gas meter room,electrical space & surrouding areas(craw spaces).

    Apr 9, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted observed: broken wire mesh glass at 3rd fl exit 4 fdsc door,2nd fl. exit 4,hallway in front of girls bathroom#218. remedy: repair &/or replace.

    Apr 9, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner,illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted observed: existing emergency light packs w/battery back up power at variou

    Apr 9, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: observed: fire proof self closing doors at vafeteria by exit e,corridor fpsc door,by 1266,next to gym,fpsc door at stair b,2nd fl do not close properly.

    Apr 9, 2021 · Penalty $625

    Resolve
  • Class - 2

    Sec. 28-301.1 failure to provide ventilation to gas meter room per j15.6(1968 code),fgc appendix e(e4)(2014 code). noted observed: no natural & mechanical ventilation in gas meter room. remedy: comply w/notice

    Apr 9, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: use oof prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted observed: key cylinder locks installed in fpsc stair doors at 3rd fl,exit 7 stair d;exit

    Apr 9, 2021 · Penalty $625

    Resolve
  • Class - 1

    Reissue#355404975 failure to maintain bldg in code compliant manner: note: observed in cellar electrical room,water penetrating through the ewalls & floors creating a hazardous condition in electrical room.

    Mar 30, 2021 · Penalty $3,125

    Resolve
  • Class - 1

    Failure to maintain building in code compliant manner. noted:observed at cellar level in the electrical room water penetrating the walls andfloors,creating a hazardous condition in the electrical room. remedy:r

    Jan 25, 2021 · Penalty $3,125

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner at cellar in electric meter room. water is penetrating floor and walls and pooling creating a dangerous condition throughout the electrical meter room and a

    Dec 4, 2020 · Penalty $3,125

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner. noted: observedat cellar level,water penetrating through floors and walls,pooling approx 3" within main electrical meter room and adjoining areas. remedy:r

    Sep 11, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: noted: observed corridors fire proof self closing door on 3rd fl next to room 353 do not self close due to defective door closer hardware. remedy: repair &/or

    Aug 26, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: use pf prohobited door &/or hardware per bc 1008.1.8;27-371(j). noted: observed(kick)stops of the following room doors,306,307,311,322,323a,324a,325b,327,333a,

    Aug 26, 2020 · Penalty $625

    Resolve
  • Class - 2

    Exit doors not self-closing.note:doors not self closing at various places throughout school.at stair b floor 1,at exit 3 floor 2,at exit 4 floor 1 and at stair c floor 1,the secondary exit door is not self clos

    Feb 5, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at cellar level in gas meter and water meter room,unlawfully using the area for storage of various boxes and items.meter rooms can not be used for sto

    Feb 5, 2020 · Penalty $625

    Resolve
  • Class - 1

    Reissue#35454650x-failure to maintain building in code-compliant manner.noted at cellar level in electrical panel room,there is standing water coming up through the floor.the presence of ongoing moisture is cau

    Feb 5, 2020 · Penalty $3,125

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner. noted:at cellarin electrical meter room water penetrating through wall and floors,saturated floors has channels cut leading to a sump pump. remedy:repair a

    Dec 19, 2019 · Penalty $3,125

    Resolve
  • Class - 1

    Noted at cellar in eletrical room water penetrating through wall and up through floor also there are channels cut out in floor bringing the water to a sump pump.remedy:repair and replace.

    Nov 14, 2019 · Penalty $3,125

    Resolve
  • Class - 1

    Noted at cellar level in electrical room water penetrating through retaining wall and up through floor making contacted with electrical cabinets and rusting the bottom of the electrical cabinets.remedy:repair a

    Sep 18, 2019 · Penalty $3,125

    Resolve
  • Class - 1

    Reissue#35379988x failure to maintain bldg in code compliant manner. noted: at cellar level electrical room water penetrating through retaining wall & ground floor in danger of contracted w/electrical panels

    Apr 23, 2019

    Resolve
  • Class - 1

    Reissue 35311707j failure to maintain building in code compliant manner.noted at cellar level, electrical room, water penetration through retaining wall, and ground floor in danger of contact with electrical pa

    Feb 5, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. noted at cellar level, electrical room and gas meter room use as a storage area, construction material like steel pipes, gypsum board, scaffolding,lamps boxes

    Jan 23, 2018

    Resolve
  • Class - 1

    Failure to maintain bldg in code-compliant manner. noted at cellar level, electrical room, water penetration through retaining wall and ground floor in danger of contact with electrical panels creating a hazard

    Jan 23, 2018

    Resolve
  • Class - 2

    Reissue #356171221h failure to maintain building in code compliant manner. note at 1st flr stair above exit 3 and 4 illuminated exit sign blocked by ceiling beam also at 3rd flr hallway near exit 5 and 6.rmdy

    Feb 23, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. note: at 1st floorat stiar b above exits 3 and 4, illuminated exit sign blocked by ceil ing beam. at 3rd flr hallway near exits 5 and 6, illuminated exit sign

    Mar 28, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliants manner.use of prohibited hardware per bc 1008.1.8;27-371(b).door stops installed on nearly all doors throughout bldg.rem:remove door stops.

    Jan 23, 2015

    Resolve
  • Class - 2

    27-371(b)vision panels:use of prohibited thermoplastic/plexiglass @ following ares/doors 311,247,245,stair,f2nd fl.,exterior exit #10,vestibule main entry & exterior doors 1&2(1stfl),1st fl exit 1/2,108a,108b,1

    Jan 23, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.smoke corridor doorsbet room 310&310 split inoperable.smoke corridor doors bet.stair 5/6(3rd fl)& room 322 split & inoperable.replace or repair doors.

    Jan 23, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.re-issue 34941031z gas meter room not vented.rem:provide ventillation.

    Jan 23, 2015

    Resolve
  • Class - 2

    Re-issue 35085205r.failure to maintain bldg wall(s)or appurtenances:water penetration into electrical room in sub cellar,excessive ponding of water.rem:seal penetrations.

    Jan 23, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s)or appurtenaces.@ roof area over gymnasiuum:water penetration around drain.rem:maintain exterior.

    Jan 23, 2015

    Resolve
  • Class - 2

    /67x10/05x10/ 67x10-repair emergency phone. 05x10-repair door zone restrictor.

    May 20, 2014

    Resolve
  • Class - 2

    Water penetration into electrical room sub cellar,excesive ponding of water noted.rem:seal penetration.

    Mar 7, 2014

    Resolve
  • Class - 2

    Defective doors no self closing. at 3rd flr story a & smoke doors adjacent to room 310,1st floor story a,gym left rear door and cafeteria door adjacent to room 159-broken door closers.rmdy:replace door closer

    Apr 22, 2013

    Resolve
  • Class - 2

    Reissue #34941032k defective windows. at various locations throughout numerous inoperative exterior windows all floors. rmdy: repair and/or replace.

    Apr 22, 2013

    Resolve