Violations at 525 Bedford Avenue
Brooklyn, NY 11211 · BBL 3-02177-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
36 DOB violations, newest first.
- Construction other optional
Borough commissioner has ordered all work stopped under permit# 302585067 due to superintendant withdrawal.
Mar 24, 2020
Dob violation - active - Construction other optional
Borough commissioner has ordered all work stopped under permit#302585067 due to construction superintendant withdrawal.
Mar 24, 2020
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 23, 2008
Vw*-violation - work w/o permit dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 2, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 22, 2006
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Nov 19, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 21, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Elevator elevatorrequired
3f1837
Mar 26, 2002
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 19, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 17, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jul 25, 1994
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
May 31, 1994
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 28, 1993
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 7, 1992
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 25, 1991
Dob violation - dismissed - Elevator elevatorrequired
Device #3f1837
Feb 28, 1991
Vpw*-violation unserved ecb-work without permit-dismissed - Elevator elevatoroptional
1
Jun 29, 1990
Dob violation - dismissed - Elevator elevatoroptional
1
Oct 12, 1989
Dob violation - dismissed - Elevator elevatorrequired
(51)file with this dept for the removed of the 5w elevator
Mar 2, 1989
Dob violation - resolved
ECB violations
The newest 50 of 73 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.at thetime of inspection observed and noted at 3rd fl stairway e 1 emer exit
May 29, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.at the time of inspection observed and noted for difective hardware door closure or difective hinge doors are not closing properly at 1st fl auditorium 2 ex
May 29, 2026 · Penalty $1,250
Active - Class - 2
Reissue:35717431h date of issue:04.22.2025 failure to maintain building in code compliant manner.at the time of inspection observed and noted 5th floor room-519 and wilson street side all rooms throughout has w
May 29, 2026 · Penalty $3,125
Active - Class - 2
Reissue:35717432j date of issue:04.22.2025 exit door not self-closing properly at the time of inspection at first floor auditorium near stage two main exit doors exit-7 and exit 6,two outside main exit not self
May 29, 2026 · Penalty $1,562
Active - Class - 2
28-301.1. unlawful placement of furnshings, decorations on other objects at exits that obstruct access to egress from visibility there of per fdny 2008 code fc 1027.4 at gym area rear stage exit have storage by
Apr 22, 2025 · Penalty $1,250
Resolve - Class - 2
Exit door not self-closing. exit door throughout corridors not self-closing. remedy: comply with code.
Apr 22, 2025 · Penalty $625
Active - Class - 2
Reissue: 35679050j-failure to maintain building in code-compliant manner: 5th floor classroom throughout has water damage to ceilings. remedy: comply with code.
Apr 22, 2025 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.5th floor classrooms throughout has water damage to ceilings.rem:comply with code.
Apr 3, 2024 · Penalty $625
Active - Class - 2
Reissue #35475882h exit door not self closing noted:observed at 2nd fl 3rd fl double swing door next room 220, 320 not properly closing also staircase c not self closing.remedy:repair/replace doors
Apr 7, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35475883j-failure to maintain building in code-compliant manner:illumination for exit,exit discharges and public corridors per bc1006.1;27-381.emergency lights at rear of and 3 sets of lights not workin
Apr 13, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner.illumination forexits.ext discharges and public corridors per bc 1006.1;27-381.noted:observed on the first floor throughout most of the emergency lights wer
Feb 28, 2020 · Penalty $625
Resolve - Class - 2
Re-issue#35297375y exit door not self-closing.noted:observed on the second floor staircase c near room 220 and third floor near room 301,thedoors are not closing properly,doors are hitting on the door frame.rem
Feb 28, 2020 · Penalty $1,562
Resolve - Class - 1
Reissue #35422512l date of issue 06-04-2019 failure to maintain building walls or appurtenances at the time of my inspection an dobserved at exp #3 rear of the building four workers ship/quality on ashphalt shi
Feb 15, 2020
Resolve - Class - 1
Construction super.failed to perform duties.no logbook.at time of inspection on an active site of a 5 story alt-3,i observed on-going construction operations with various trades on-site,upon requesting super's
Jul 22, 2019 · Penalty $10,000
Resolve - Class - 1
Failed to notify the department of an incident that resulted in a fatality or injury .one worker was struck by the arm of the excounteor andtaken by ambulance to the hospital.as per the department within 3 busi
Jul 17, 2019
Resolve - Class - 1
Failure to safeguard all persons & property affected by construction operations. noted: @ front of school on the fenced in sidewalk while digging the(bone)test w/a small excavation the workers disconnected the
Jul 17, 2019
Resolve - Class - 2
Bc28-301.1/unlawful display of art work in corridors greater than 20% per fdny 2008 code,fc803.3.3.2.at the time of inspection outside of classroom #311 and approx. 2' x 30' of 11' x 17' papers art displays mou
Jan 19, 2018
Resolve - Class - 2
Failure to maintain building in code compliant manner.at the time of inspection ,at cellar area by exhaust fan switches above ceiling plaster/cement is crumbling approx 3' x 4' falls onto flr.rem:repair and or
Jan 19, 2018
Resolve - Class - 2
Bc28-301.1/unlawful placement of furnishings,decorations or other objects at exits that obstruct access to,egress from or visibility there of per fdny 2008 code;fc803.3.2.at the time of inspection 3rd flr outsi
Jan 19, 2018
Resolve - Class - 2
At the time of inspection,exit door nor self-closing at outside of room 534 to stair #e(5fl),outside of room 525 double-swing out doors nor close properly,outside of room 301 staircase 13(3rd flr)2 doors nor cl
Jan 19, 2018
Resolve - Class - 2
Reissue #356177415n failure to maintain building wall(s) or appurtenances: noted: water penetration into cellar above machine electrical panel at wilson st site. rmdy: maintain exterior building wall(s)
Feb 22, 2017
Resolve - Class - 2
Reissue: 35119123x failure to maintain bldg wall(s) or appurtenances.maintain exterior building wall. noted: water penetration into cellar above machine electrical panel at wilson st side.
Apr 6, 2016
Resolve - Class - 2
Exit door not self closing. noted: at second flr at staircase 2c. exitdoor is not self closing.door closer is defective and need to be repair or replaced. rmdy: comply with code make necessary repair.
Apr 6, 2016
Resolve - Class - 2
27-371(b)vision panels.the following classroom doors have plexiglass vision panels:rooms 333,328,326,418,419,427,424&433.rem:provide required glass panels.
Jan 21, 2015
Resolve - Class - 2
Failure to maintain bldg in code-complaint manner:exterior water penetration into cellar above machine electrical panel @ wilson street side.rem:
Jan 21, 2015
Resolve - Class - 2
Combustible materials in cooridors:& in fire staits.@ charter school:excessive paperwork along walls on 4th & 5th fl & in fire stairs "e" from gumnasium to 5th fl not an bulletin boards.rem:remove excessive com
Jan 21, 2015
Resolve - Class - 2
Missing fire stopping. at room 316, no firestop with penetration in ceiling for telecommunication wires. remedy:fire stop all penetrationsmaintain fire stopping.
Apr 17, 2013
Resolve - Class - 2
Excessive combustible decorations @ stairway e,combustible decorations& artwork hung in fire stairway-all floors. remedy:remove all items.
Apr 17, 2013
Resolve - Class - 2
Partial corridor obstruction.at 4th floor,tables & crates, 3rd fl gym rear exit stairway with equipment and tables. remedy:remove all items/maintain corridor width clear.
Apr 17, 2013
Resolve - Class - 2
Defective doors. at stairway e, 3rd & 2nd fl, 3e not self cloosing and2e with broken top hinge. remedy:repair doors to properly self close.
Apr 17, 2013
Resolve - Class - 2
Spalling plaster. ceiling damage at rooms 533,527,520,518,517,311,304,and wall at 447. remedy:repair plaster surface.
Apr 17, 2013
Resolve - Class - 2
Doors not closing at: 1st story main entry interior vestibule doors not closing. remedy: repair or replace doors.
Jan 3, 2012
Resolve - Class - 2
Water damage/penetration at: 4th story room 417 south wall. cellar: sidewalk vault and coal elevator area's. remedy: repair defects noted.
Jan 3, 2012
Resolve - Class - 2
Roof leaks/water penetrating above rooms, 311,304,533,527,520,518 & 517 and stair d 5th floor. remedy: repair roof.
Jan 3, 2012
Resolve - Class - 2
Roof has become porous & allowing rain into the bldg causing interior damages in room 409 on the 4th flr level.rem:waterproof roof
Jun 22, 2011
Resolve - Class - 2
The corridor hallway is partial obstructed by piles of boxes & tables located by room 424 & staircase "e"on the 4th flr level.rem:remove obstruction.
Jun 22, 2011
Resolve - Class - 2
Failure to provide fire-stopping around the pipe penetration at the electrical room at cellar level. remedy: provide fire-stopping around pipe penetration in electrical room.
Jan 12, 2010
Resolve - Class - 2
The gas meter room at cellar level does not have fresh air ventilationremedy: provide fresh air ventilation in the gas meter room.
Jan 12, 2010
Resolve - Class - 2
The concrete on the ceiling is cracked located in the electrical room at cellar level. remedy: repair/replace concrete ceiling.
Jan 12, 2010
Resolve - Class - 2
The plaster on the ceiling is spalling located in room 307 (3rd flr) &room 503 (5th flr). remedy: repair/replace plaster on ceiling.
Jan 12, 2010
Resolve - Class - 2
Sec. 1017.1;27-369. exit passageway partially obstructed on 5th flr stair c inside stairwell. noted: computer bean bags, chairs and one on one teacher/student interviewing. also 5 & 4 flrs obstructions in
Mar 18, 2009
Resolve - Class - 3
Defective doors. noted: corridor smoke doors on 5,4,3,2 flrs. also stairway doors on 5,4,3,2,1 flrs d and c stairway all doors dragging and not closing properly. remedy: repair doors.
Mar 18, 2009
Resolve - Class - 3
Reissue 34563940k vertical crack in glazed block wall in gym adjacent to occupancy sign (3 flr) approx 7' long from ground up. remedy: repair/replace glazed block.
Aug 7, 2008
Resolve - Non-hazardous
Re-issue:34504990z (partial). vertical crack in the tile wall located adjacent to the windows by the occupancy sign located in the gym (3rd floor level). remedy: repair cracked tile wall.
Mar 15, 2007
Resolve - Non-hazardous
Cellar main electrical room is missing fire stopping above entry door.remedy: provide/maintain fire stopping.
Jan 19, 2006
Resolve - Non-hazardous
Cellar gas meter room has no ventilation as required. remedy: provide/maintain ventilation.
Jan 19, 2006
Resolve - Non-hazardous
First floor main entry. middle door saddle is cracked/split. remedy: replace saddle.
Jan 19, 2006
Resolve - Non-hazardous
First floor cafeteria at stairwell #4 exit door from cafeteria is defective, falling apart, hitting floor and jamb. remedy: replace door.
Jan 19, 2006
Resolve - Non-hazardous
Third floor gymnasium, glazed wall tiles has a vertical crack at window near occupancy sign and vertical crack near drinking fountain. also noted: cracked mortar joints above entry door near stairwell #5.remedy
Jan 19, 2006
Resolve - Non-hazardous
Missing door checks at: fifth floor exit 4 two doors and first floor cafeteria exit 3 door. remedy: install checks. (fpsc)
Jan 19, 2006
Resolve