Violations at 29 Ft Greene Place
Brooklyn, NY 11217 · BBL 3-02098-0013 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
The newest 50 of 319 DOB violations. The city keeps the complete history.
- High pressure boiler boiler required
Violation issued-failure to file 2023 internal hgh pressure inspection
Sep 23, 2024
Dob violation - active - High pressure boiler boiler required
Violation issued-failure to file 2023 internal hgh pressure inspection
Sep 23, 2024
Dob violation - active - High pressure boiler boiler required
Violation issued-failure to file 2023 external hgh pressure inspection
Sep 23, 2024
Dob violation - active - High pressure boiler boiler required
Violation issued-failure to file 2023 external hgh pressure inspection
Sep 23, 2024
Dob violation - active - Retaining wall none
Failed to file cycle 1 technical report by 12/31/2018 per rcny 103-09
May 1, 2024
Dob violation - active - High pressure boiler boiler required
Violation issued-failure to file 2021 internal hgh pressure inspection
Jun 30, 2023
Dob violation - dismissed - High pressure boiler boiler required
Violation issued-failure to file 2021 internal hgh pressure inspection
Jun 30, 2023
Dob violation - dismissed - High pressure boiler boiler required
Violation issued-failure to file 2021 external hgh pressure inspection
Jun 30, 2023
Dob violation - dismissed - High pressure boiler boiler required
Violation issued-failure to file 2021 external hgh pressure inspection
Jun 30, 2023
Dob violation - dismissed - High pressure boiler boiler required
Violation issued-failure to file 2020 internal hgh pressure inspection
Jun 30, 2023
Dob violation - dismissed - High pressure boiler boiler required
Violation issued-failure to file 2020 internal hgh pressure inspection
Jun 30, 2023
Dob violation - dismissed - High pressure boiler boiler required
Violation issued-failure to file 2018 internal hgh pressure inspection
Jun 20, 2023
Dob violation - dismissed - High pressure boiler boiler required
Violation issued-failure to file 2018 internal hgh pressure inspection
Jun 20, 2023
Dob violation - dismissed - High pressure boiler boiler required
Violation issued-failure to file 2018 external hgh pressure inspection
Jun 20, 2023
Dob violation - dismissed - High pressure boiler boiler required
Violation issued-failure to file 2018 external hgh pressure inspection
Jun 20, 2023
Dob violation - dismissed - High pressure boiler boiler required
Violation issued-failure to file 2022 external high pressure inspection
Apr 25, 2023
Dob violation - dismissed - High pressure boiler boiler required
Violation issued-failure to file 2022 external high pressure inspection
Apr 25, 2023
Dob violation - dismissed - High pressure boiler boiler required
Violation issued-failure to file 2022 internal high pressure inspection
Apr 25, 2023
Dob violation - dismissed - High pressure boiler boiler required
Violation issued-failure to file 2022 internal high pressure inspection
Apr 25, 2023
Dob violation - dismissed - No report and / or late filing (facade) facade required
Failed to file fisp cycle 9b technical report by 2/21/2023
Feb 22, 2023
Dob violation - active - Residential elevator periodic inspection/test elevatorrequired
Failure to perform category 5 inspection
Dec 17, 2021
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 17, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 17, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 17, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 17, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 17, 2021
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 17, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 17, 2021
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 17, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 17, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2020
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2020
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2020
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2020
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2020
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2020
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2020
Dob violation - active - High pressure boiler boiler required
Violation issued - failure to file 2017 internal high pressure boiler inspection
Mar 16, 2020
Dob violation - dismissed - High pressure boiler boiler required
Violation issued - failure to file 2017 internal high pressure boiler inspection
Mar 16, 2020
Dob violation - dismissed - High pressure boiler boiler required
Violation issued - failure to file 2017 external high pressure boiler inspection
Mar 16, 2020
Dob violation - dismissed - High pressure boiler boiler required
Violation issued - failure to file 2017 external high pressure boiler inspection
Mar 16, 2020
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 7, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 7, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 7, 2019
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 7, 2019
Dob violation - resolved
ECB violations
The newest 50 of 234 ECB violations. The city keeps the complete history.
- Class - 2
Reissue ecb #35693148z. failure to maintain building in code-compliantmanner. noted:-at(7th fl) stairs p and i(1st fl) hallway near gym stair i/j, stair d and all main entrances all doors are in disrepair/racke
Feb 4, 2026 · Penalty $1,250
Active - Class - 2
Reissue ecb #35693144l. failure to maintain building in code-compliantmanner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at(5th fl) library(1st fl) gym and audito
Feb 4, 2026 · Penalty $1,250
Active - Class - 2
Reissue ecb #35693149k. failure to maintain building in code-compliantmanner. noted: at(basement) gas meter rm with multiple storage of various items throughout pipes, ladders, etc... remedy: comply with code.
Feb 4, 2026 · Penalty $1,250
Active - Class - 2
Reissue ecb #35691975n. failure to maintain building in code-compliantmanner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted: at(7th fl) cafeteria of stairs t/u and q/r and h/g and d/c
Feb 4, 2026 · Penalty $1,250
Active - Class - 2
Reissue ecb #35691976p. exit door not self-closing. noted: at(1st fl) auditorium and all main entrances(exterior and interior) doors not close when tested. remedy: repair/replace door.
Feb 4, 2026 · Penalty $625
Active - Class - 1
Class 1: upon inspection found device to be out of service. restore to service repair immeidately as per 1rcny 11-02. when service restored contact nycdob at [email protected].
May 2, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:at basement gas meter and electric rm bw14 with storage of various items throughout as ladders,boxes pipes etc..rem:comply with code.
Mar 17, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.noted at 4th fl stair j & i.3rd fl stair c & d,1st fl gym j & i and 1st fl main entrances all doors are all indisrepair/racked.rem:repair and/or replace.
Mar 17, 2025 · Penalty $1,250
Active - Class - 2
Reissue ecb#35692243m failure to maintain building wall(s)or appurtenances.noted:at roof chiminey with horizontal/stud cracks throughout in various areas.rem:maintain exterior building wall.
Mar 17, 2025 · Penalty $2,500
Resolve - Class - 2
Reissue ecb#35692239j failure to maintain building in code compliant manner.noted:at 8th fl roof/outdoor gyms in disrepair/damaged in vaiousahead of chicken screens.rem:repair and/or replace.
Mar 17, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:at roof bulkhead stair r 8th fl gym with water penetration damage/staining to floors/walls & ceilings.reissue ecb#35692240r rem:repair and/or replace.
Mar 17, 2025 · Penalty $1,250
Resolve - Class - 2
Reissue ecb#35692242k failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at gym and auditorium em lights when tested not
Mar 17, 2025 · Penalty $1,250
Active - Class - 2
Exit door not self closing.noted:(4th fl)stair b & a(1st fl)auditoriumand all main entrances(exterior & interior)all doors not closing when tested throughout various.rem:repair/replace door.
Mar 17, 2025 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:at 8th fl dancerm e14(2nd fl)track and (1st fl)gym with door installed/equipped with
Mar 17, 2025 · Penalty $1,250
Active - Class - 2
Reissue#35673094y date of issue:03.23.2023 failure to maintain building wall(s)or appurtenances.at the time of inspection/observed & noted at roof top back chimney with approx 4'l step crack at top of chimney.r
Nov 18, 2024 · Penalty $3,125
Resolve - Class - 2
Reissue#35673089j date of issue:03.23.2023 failure to maintain building in code-compliant manner.illumination for exit,exit discharges and public corridors per bc 1006.1;27-381.at time of inspection noted & obs
Nov 18, 2024 · Penalty $1,562
Active - Class - 2
Reissue#35673090r date of issue:03.23.2023 emergency sign at elevator stations missing defective or non compliant with section requirements at the time of inspection noted & observed that at cellar level elevat
Nov 18, 2024 · Penalty $1,562
Resolve - Class - 2
Reissue#35673092k date of issue:03.23.2023 failure to maintain building in code-compliant manner.at the time of inspection observed & noted that roof leaks causing damage at 10th fl ceiling at staircase rm-10w1
Nov 18, 2024 · Penalty $1,562
Resolve - Class - 2
Reissue#35673091z date of issue:03.24.2023 failure to maintain building in code-compliant manner.at 8th fl roof top outdoor all the gyms/play area chicken screens damaged/missing sections at various locations.r
Nov 18, 2024 · Penalty $625
Resolve - Class - 2
Failure to submit an acceptable required cycle 9b report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 control#909558.rem:submit acceptable required techn
Apr 11, 2024 · Penalty $1,250
Active - Class - 2
Upon inspection of sws, premises has sidewalk shed on all exposures with no gc parapet information panel provided. bc 3301.9.2.2 requires sws parapet information panels be posted on parapet that runs along the
Mar 6, 2024
Resolve - Class - 2
Failure to file acceptable amended cycle 6, 8a, and 9a report indicating correction of unsafe conditions described in initial facades reportrequired by 28-302.5 for control #900361. remedy: file acceptable repo
Jan 16, 2024 · Penalty $1,250
Active - Class - 2
Reissue #35473485p failure to maintain building in code-compliant manner.noted:at 8th fl roof top outdoor all the gyms w/ chicken screens.remedy:comply with code.
Mar 24, 2023 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building wall(s) or appurtenances.noted:at roof top brick chimney with aprox 4'l step crack at top of chimney.remedy:make necessary repairs.
Mar 23, 2023 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:illegal storage of misc items at electrical rm at west side central west & electrical rm at bn2.remedy:remove illegal storage from electrical rms.
Mar 23, 2023 · Penalty $625
Resolve - Class - 2
Reissue #35473483l failure to maintain building in code-compliant manner.noted:roof leak causing damage at 10th fl ceiling at staircase rm 10w14,10w13,10w15.walls.remedy:make necessary repairs.
Mar 23, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue #35650675k emergency signs at elevator call stations missing defective or non compliant with section requirements.noted:at cellar elevator bank d & e missing emergency sign.remedy:install sign.
Mar 23, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue #35650897x failure to maintain building in code-compliant manner.illumination for exits,exit discharges & public corridors per 1006.1; 27-381.noted:defective emergency lighting observed at following loc
Mar 23, 2023 · Penalty $1,562
Active - Class - 2
28-301.1 reissued #35650898h failure to provide ventilation to gas meter rmper p115.6(1968 code)fgc appendix e (e4) (2014 code).noted:no ventilation provide at cellar gas meter rm.remedy:provide ventilation to
Mar 23, 2023 · Penalty $3,125
Resolve - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. remedy; file application, install dlm a
Mar 20, 2023 · Penalty $1,250
Active - Class - 2
Class 2: 11.i.11 access door damaged on car button station. replace door to secure key switches.
Nov 22, 2022 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner.use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j)noted: observed all auditorium exit doors have kick stop/door stop hardware installed on do
Mar 22, 2022 · Penalty $625
Resolve - Class - 2
28-301.1 re-issued #35557751r failure to provide ventilation to gas meter room per p115.6(1968 code)fgc appendix e(e4)(2014 code)noted:observed no fresh air vent nor mechanical vent at cellar gas meter room.rem
Mar 22, 2022 · Penalty $1,250
Resolve - Class - 2
Re-issued #35557752z failure to maintain building in code compliant manner.illumination for exit exit discharges & public corridors per bc 1006.1; 27-381 noted:existing emergency lights were not operational whe
Mar 22, 2022 · Penalty $1,562
Active - Class - 2
Re-issued#35557753k exit door not self closing noted:observed exterior exit door at exit #10(left door do not open)exit #11 doors 3 &4 do not open exit #12 both doors do not open exit #2 doors 3 & 5 do not open
Mar 22, 2022 · Penalty $1,562
Resolve - Class - 2
Emergency signs at elevator call stations missing defective or non compliant with section requirements noted:observed at basement elevator bank d & e missing emergency sign.remedy:install and/or repair signs
Mar 22, 2022 · Penalty $625
Resolve - Class - 1
Failure to notify the department of an accident/incident that resultedin a fatality or an injury.note:a worker hit his forehead on a scaffold frame and was taken to a hospital for treatment.as per check of the
Jul 15, 2021 · Penalty $12,500
Resolve - Class - 2
Exit door not selfclosing noted:on1fl 4doors on eside of bldg&3doors on wside of bldg werent opening&closing properly.repair/replace door.
Apr 21, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:thruout bldg,most of emergency lights werent working when tested.repair/replace
Apr 21, 2021 · Penalty $625
Active - Class - 2
28-301.1 reissue35422167j failure to provide ventilation to gas meter rm per p115.6(1968code),fgc appendixe(e4)(2014code).noted@cellar levelin gas meter rm,theres no fresh ventilation.comply w/notice of violati
Apr 21, 2021 · Penalty $3,125
Resolve - Class - 2
Sec. 3301.7 documents to be kept on site. at the time of my inspectioni observed supported pipe scaffold system in place on sidewalk shed installed at all perimeters of bldg upon request for loads inposed lette
Jan 25, 2021 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:at cellar at gas meter room,9 used snow blowers(gas powered)being stored.rem:comply with notice of violation.
Apr 27, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j)noted:at auditorium and at 8th fl.danceroom,exit doors have kick down door corridors attache
Apr 27, 2020 · Penalty $625
Resolve - Class - 2
Reissue#35422164y failure to maintain building in code compliant manner.noted:at 8th fl/roof top outdoor gym chicken screens damaged/missingsections at various locations.rem:repair/replace.
Apr 27, 2020 · Penalty $1,562
Resolve - Class - 2
28-301.1 reissue#35422167j failure to provide ventilation to gas meterroom per 115-6(1968 code)fgc appendix e (e4)(2014 code)noted:at cellarnew gas meter room,no fresh air ventilation provided.rem:comply with n
Apr 27, 2020 · Penalty $3,125
Resolve - Class - 2
Reissue#35422168l failure to maintain building in code compliant manner.noted:water penetration at staircase w/ roof top level causing damage to walls and staining to the ceiling.rem:make necessary repairs.
Apr 27, 2020 · Penalty $1,562
Resolve - Class - 1
97x17:97-x-17:the only elevator in a section of a building is out of service. upon inspection the device is found to be out-of-service creating a hazardous condition as per 1rcny 11-02. restore to service immed
Dec 15, 2019 · Penalty $1,250
Resolve - Class - 2
Work after hours w/o variance permit contrary to 28-105.12.5. at the time of inspection,work performed under job#302585815 was observed w/ workers installing pipe scaffolding on top of the sidewalk shed on the
Jul 29, 2019 · Penalty $1,250
Resolve - Class - 2
Reissue 35334440l failure to maintain building in code complaint manner. no fire stopping per bc 712.3; 27-345. noted: at room 7e2@7th flr and basement electric room bw14-bn2 and east landing, fire stopping mi
Apr 29, 2019
Resolve - Class - 2
Reissue 35334438m failure to maintain building in code complaint manner. noted: water penetration @staircases w/rooftop level causing damage to walls and staining to the ceiling. rmdy: repair/and/or replace.
Apr 29, 2019
Resolve