1339 Herkimer Street

Brooklyn, NY 11233BBL 3-01552-0043Map

Owner of record: NYC Department Of Education

1339 Herkimer Street is a school building built in 1908 in Brooklyn, 11233. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
27
ECB violations
99
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 27

  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
Show 17 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1993

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1993

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1993

    Dob violation - dismissed

ECB violations · 99

  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at (basement)exit d, a, b, cafeteria/auditorium/play area/gym (1st fl)stair a,d (3rd fl)stair a all doors are in disrepair/racked when tested. remed

    May 27, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at (roof/4th fl) bulkhead/stair b (1st fl)near rm 112, (2nd fl)near rm 212, (3rd fl)near rm 312, (4th fl)near rm 412 water damage to ceilings/walls

    May 27, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at (1st fl)hallway installed/hung non fire-retardent decorations to ceilings. remedy: comply with code.

    May 27, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:in the gymnasium six lights and in the cafeteria twelve lights.all the

    Apr 28, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Exit door not self-closing.noted:stair d kitchen exit the door on the right is not closing properly.rem:repair/replace door.

    Apr 28, 2025 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35672681y. failure to maintain building in code-compliant manner. at time of my inspection i observed the foundation wall at the cellar level has become porous allowing water when it rains. rain penetr

    May 16, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35650975m. failure to maintain building in code-compliant manner. at time of my inspection i observed at exposure #3 facade in state of disrepair with several section of bricks the spalling falling out

    May 16, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35650979j. failure to maintain building in code-compliant manner. at time of my inspection at the roof level rusted/electric rated damage of the outdoor hvac unit and broken/damaged back concrete pad o

    May 16, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.no fire stoppingper bc712.3;27-345.noted at cellar gas meter room,big hole around the pipe with no fire stopping.remedy:provide/maintain fire stopping.

    Apr 12, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc1006.1;27-381.noted defective emergency exit lighting observed at cafeteria em#6,7,3.remedy

    Apr 12, 2023 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Reissue#35650977x failure to maintain building in code compliant manner.noted at multi-purpose room,2 windows have been sealed to prevent natural light and ventilation.remedy:comply with notice of violation.

    Apr 12, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35650976y failure to maintain building in code compliant manner.noted at gas meter room at basement,rusted/deteriorated gas lines fitting caused by water penetration.remedy:make necessary repairs.

    Apr 12, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35644299p failure to maintain building in code compliant manner.noted foundation wall at cellar level has become porous allowing water the rain water in the cellar electrical gas meter room and water pu

    Apr 12, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Work contrary to after hrs variance/work w/o variance.@time of inspection,i observed workers@exp1 performing excavation&shoring which is contrary to ahv permit#01066459.obtain after hrs permit.

    Dec 2, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Work after hours w/o variance permit.note:at time of inspection observed workers at exp #1 performing excavation & shoring w/o after hour permit.in connection with job #b00767418-i1-se.remedy:obtain after hours

    Dec 2, 2022 · Penalty $1,250

    Active
  • Class - 2

    At the time of my inspection observed storage area at exp#1 adjacent to the sidewalk shed closed with 8 feet high solid fence which create an unsafe condition ( mugging) for pedestrians.provide wire screen comp

    Oct 18, 2022 · Penalty $2,400

    Resolve
  • Class - 2

    Reissued35635800p failure to maintain bldg in codecompliant manner:noted:@entire bsmt level (including electrical&gasmeterrms) water penetration thruout foundation wall causing water puddle (water standing .5"

    Apr 22, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:noted:@bsmt level gasmeterrm rusted/deteriorated gas lines fitting caused by water damage repair &or replace fitting

    Apr 22, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:no firestopping per bc712.3;27-345.noted:@bsmt level gasmeterrm missing firestopping aroundpipe which penetrating thru cmu wall.provide/maintain firestopping.

    Apr 22, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Reissued35554098j exit door not selfclosing.noted:@1fl exit door to outside loading from kitchen isnt selfclosing properly due to defective hardware.repair /or replace door.

    Apr 22, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued35554094m failure to maintain bldg in codecompliant manner:noted:@roof level rusted/electric rated damage of outdoor hvac units&broken/damaged base concrete pad of damage pole.repair &or repair

    Apr 22, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued35554095y failure to maintain bldg in codecompliant manner:noted:@exp3 facade in state of disrepair w/several secs of bricks spalling in various locations.repair &or replace

    Apr 22, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued35554092z failure to maintain bldg in codecompliant manner.noted:@multipurposerm 2windows have been sealed prevented natural light&[email protected] &or replace

    Apr 22, 2022 · Penalty $1,562

    Resolve
  • Class - 1

    Reissued 35584463x failure to maintain building in code compliant manner. note at basement level water penetration through foundation walls in electrical and gas meter rooms,causing puddles in rooms. remedy:rep

    Nov 18, 2021 · Penalty $3,125

    Resolve
  • Class - 1

    Reissued 35519749r failure to maintain building in code compliant manner. note at basement level in electrical and gas meter rooms water penetration through foundation walls causing water to puddle in rooms. re

    Nov 18, 2021 · Penalty $3,125

    Resolve
  • Class - 1

    Re-issue #35554091r failure to maintain building in code compliant manner.noted:at basement level (electrical room, gas meter room, boiler room, utilities room)water leakage(standing/spilled)water creating haza

    Sep 3, 2021 · Penalty $3,125

    Resolve
  • Class - 1

    Re-issued #35560709k.failure to maintain building in code compliant manner.noted:entire cellar level including electrical room and gas meter room foundation walls damaged due to water leakage.observed cellar ce

    Aug 17, 2021 · Penalty $3,125

    Resolve
  • Class - 1

    Reissued#35555633r.failure to maintain building in code compliant manner.noted:observed during inspection of cellar level(gas,electical,boiler room)utilities rooms and entire basement has standing water.walls h

    May 26, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35401702j.failure to maintain building in code compliant manner.noted:observed auditorium 2 windows sealed,force air unit not operating at time of inspeciton,space deprived of natural light and ventilat

    May 26, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:observed during inspection of exposure 4 the fence retaining wall base is missing section of concrete,seperating from itself and has cracks throughout

    May 26, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.illuminations for exits,exits discharge and public corridors per bc 1006.1;27-381.noted:observed during inspection of emergenry lights in gym(by custodian r

    May 26, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissued#35490994h.failre to maintain building in code compliant manner.noted:observed two windows at basement level have been sealed,with brick/drywall preventing natural light/ventilation.remedy:repair and/or

    May 26, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted:observed during inspection of roof hvac unit damage base deteriorated/crumbling.remedy:repair and/or replace.

    May 26, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted:observed during inspection of exposure#3 masonry spalling throught facade.remedyrepair and/or replace.

    May 26, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing.noted:observed exit doors leading out of kitchen were not self closing at time of inspection.remedy:repair/replace door.

    May 26, 2021 · Penalty $625

    Resolve
  • Class - 1

    Failure to maintain bldg in codecompliant manner.noted:@cellar level electrical,gas&boilerrm;foundation walls have become porous&is allowingwater to enter rms.repair &/or replace.

    Apr 28, 2021 · Penalty $3,125

    Resolve
  • Class - 1

    Reissue#35542702z failure to maintain bldg code compliant manner: cellar level in several location water penetration through foundation walls at cellar w/custodian & staff.

    Mar 5, 2021 · Penalty $3,125

    Resolve
  • Class - 1

    Reissue to 35490993x issued on 4/20/2020. failure to maintain buildingin code-compliant manner:at cellar level in several location,water penetration through foundation walls. at cellar w/ custodian and staffs t

    Oct 21, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35401702j failure to maintain bldg in code compliant manner. noted: observed at basement level 2 windows have been sealed w/bricks &drywall preventing natural light & ventilation. remedy: repair & or re

    Apr 20, 2020 · Penalty $1,562

    Resolve
  • Class - 1

    Reissue#35461269m failure to maintain bldg in code compliant manner. noted: observed at cellar level throughout there is water penetration from foundation wall. remedy: repair &/or replace.

    Apr 20, 2020 · Penalty $3,125

    Resolve
  • Class - 1

    #35455030j failure to maintain building in code compliant manner. noted:at cellar,in electrical room,gas meter room and throughout the cellar active water penetration observed w/ puddles at various locations. a

    Dec 17, 2019 · Penalty $3,125

    Resolve
  • Class - 1

    Reissue#35401700x noted:at the subcellar level,water penetration on the walls and ceiling in the gas and electrical meter rooms and throughout the entire cellar in various areas.remedy:make neccessary repairs.

    Oct 21, 2019 · Penalty $3,125

    Resolve
  • Class - 1

    Failure to maintain building in code compliant manner.noted:throughoutentire sub cellar water penetration/seeping in through foundation brick mortar wall creating puddling/standing water with water damage to wa

    Sep 23, 2019 · Penalty $3,125

    Resolve
  • Class - 2

    35147441j failure to maintain building in code compliant manner. notedauditorium forced air ventilation system inoperative depriving space of fresh air(noted windows removed from space. remedy:provide adequate

    May 20, 2019

    Resolve
  • Class - 1

    Reissue 35381330m failure to maintain building in code compliant manner. note at sub cellar throughout the whole sub basement water penetrating through the walls in rooms gas meter rm,electrical rm,paint rm,boi

    May 20, 2019

    Resolve
  • Class - 2

    Reissue 35324802k failure to maintain building in code compliant manner. noted basement in auditorium 2 windows have been sealed up w/ bricks and drywall preventing natural light and ventilation. remedy:repair

    May 20, 2019

    Resolve
  • Class - 1

    Reissue #35334135p failure to maintain building in code compliant manner: note at sub cellar electrical room water seeping throughout wall standing water in room apprx 1/2",water also standing in boiler room i

    Jan 18, 2019

    Resolve
  • Class - 1

    Re-issue #353475566x failure to maintain building in code compliant manner.noted:@sub cellar of building water 2 bioler fl and electrical room.water is seeping through wall,when it rains.rem:repair and replace.

    Nov 3, 2018

    Resolve
  • Class - 1

    Reissue viol #35342466j. failure to maintain building in code-compli ant manner. noted: at subcellar of building water at boiler meter roomand humidity in the electrical meter room, water seeped through the wa

    Sep 7, 2018

    Resolve
  • Class - 1

    Reissue #35334135p failure to maintain building ina a code compliant manner. noted: electric meter room and boiler meter room at subcellar and other locations at subcellar have stand water appprx 1"deep which

    Jul 25, 2018

    Resolve

Complaints

  • Water leak

    Slow leak

    Aug 24, 2015 · Apt SCHOOL

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1908
Floors
5
Residential units
—
Building area
75,000 ft²
Lot area
30,000 ft²
Zoning
R6
Community board
316
Council district
37
Block / lot
1552 / 43
Assessed value
$2,881,350
Landmark / historic district
No

Questions about 1339 Herkimer Street

Who owns 1339 Herkimer Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 1339 Herkimer Street have violations?

NYC HPD has no housing violations on record for this property.

Is 1339 Herkimer Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 1339 Herkimer Street built?

City records list 1908 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.