Violations at 245 Sumpter Street

Brooklyn, NY 11233 · BBL 3-01528-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

39 DOB violations, newest first.

  • Construction other optional

    C-construction other optional

    Apr 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active

ECB violations

The newest 50 of 52 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006,1; 27-381.-noted: first floor auditorium six lights cellar cafeteria e two lights,

    Apr 25, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: second floor staircase e/h both doors. first floor staircase e/h one door, auditorium right side of the stage one door. all these doors were not clo

    Apr 25, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Re-issue #35675040h. exit door not self-closing.-noted: exit 5 one door, exit 7 one door. all these doors were not closing properly. remedy:repair/replace door.

    Apr 25, 2025 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35675042l. failure to maintain building in code-compliant manner. at time of my inspection i observed at classroom door #204. smokedoor next to 207 and smoke door by room 205 not close properly when te

    May 20, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.no fire stopping per gc 712.3; 27-345.noted:at cellar electrical rm big holes around conduits with no fire stopping.remedy:provide/maintain fire stopping.

    Apr 19, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:class room door #204,smoke door next to 207 & smoke door by 205 do not close properly.remedy:repair/replace door.

    Apr 19, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.9; 27-371(j)noted:kick stops are attached to classroom doors & exit doors throughout building.remedy:re

    Apr 19, 2023 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing.noted:at auditorium at front 3 exit door do not close properly.remedy:repair/replace door

    Apr 19, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissued35557921k failure to maintain bldg in codecompliant manner.noted:observed during insp of bsmt sprinkler/utilityrm.sprinkler shutoffs&electrical panels blocked by storage of wire racks/shelves filled w/c

    Apr 21, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue35557918j exit door not selfclosing.noted:observed during insp of exterior exit doors exit door19,18,8,2,5,6,4,1 werent op atoi repair/replace doors

    Apr 21, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:observed in bsmt utilityrm baker scfs/shelfs w/cardboard boxes stored on them,blocking shutoff to water supply&blocking electrical panel&electrical shutoff

    Apr 28, 2021 · Penalty $625

    Resolve
  • Class - 2

    Stair &/or fl id signs missing &/or defective noted:observed stair &/or fl id sign were missing thruout entire school@various locations.intasll &/or repair signs.

    Apr 28, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:observed boilerrm,water pooling due to water pipe leak.repair &/or replace.

    Apr 28, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not selfclosing.noted:observed exterior exit doors exit19,exit18,exit8,exit2,exit5,exit6 werent operating@time of insp.repair/replace door.

    Apr 28, 2021 · Penalty $625

    Resolve
  • Class - 2

    28-201.1 failure to maintain bldg in codecompliant manner.noted:observed doors@2fl staire exit8,stairh exit8,exit9 (by rm201b) rm113,bsmt-kitchen door,exit5 staire,auditorium door werent selfclosing due to miss

    Apr 28, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissues35990995j failure to maintain bldg in codecompliant manner.illumination for exits,exit discharges&public corridors bc1006.1;27-381 noted:observed emergency lights@auditorium(front),gym,exit4 std werent

    Apr 28, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: observed in the auditorium 4 of the emergency lights were not working

    Apr 20, 2020 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing. noted: @ 3rd flr exit staircase(8), rm#304, exit#5,@ 2nd flr rm#213,@ 1st flr rm#116, the doors have defective in the hinges & closers. rem: comply w/ code.

    Sep 16, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: no fire stopping per bc 712.3, 27-345. noted: @ basement, electrical room, missing fire stopping on ceiling (hole approx 1' x 1'). rem: comply w/ code.

    Sep 16, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: @ basement, @ gas meter room, penetration through the retaining wall w/ water damage the wall, collecting the water on the ground flr (height approx 0.5

    Sep 16, 2016

    Resolve
  • Class - 2

    Pedestrian protection does not meet code specification.note:observed sidewalk shed erected at exp#1,2,3 sidewalk shed lights at exp #1(macdougal st)are not operating.that does not meet code specification 3307.6

    Feb 16, 2016

    Resolve
  • Class - 2

    3307.6.5 fail to maintain adequate illumination beneath sidewalk shed as req by code.note:sidewalk shed erected under job #302570581 along exp #1,2,3 has inoperable bulbs rendering affected area visibly dark

    Jan 9, 2016

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances.at the time of ispection observed water penetrating the roof flashing/bricks around the bulkhead and causing the interior walls to damage (spalling plaster)

    Sep 18, 2015

    Resolve
  • Class - 3

    Failure to maintain building in a code compliant manner.at the time ofinspection observed spalling,loose,cracked plaster at the bulkhead on the walls and ceiliing.remedy:comply with the notice of violation.

    Sep 18, 2015

    Resolve
  • Class - 2

    At exit doors adjacent auditorium stage, interior exit doors (exits 18 & 19) doors rub against floor, will not fully open. remedy: maintain building.

    May 29, 2014

    Resolve
  • Class - 2

    Paper display hanging from ceiling in corridor outside room 207 partially obstructing view of exti sign. remedy: remove displays, provide unobstructed egress.

    May 29, 2014

    Resolve
  • Class - 2

    Water penetration into corridor from around roof access hatch near room 315. remedy: maintain building.

    May 29, 2014

    Resolve
  • Class - 3

    Spalling plaster on corridor wall opposite room 315. remedy: maintain building.

    May 29, 2014

    Resolve
  • Class - 2

    At roof above 3rd floor approx 25 long feet roofing flashing either missing or partially detached from parapet. remedy: maintain building.

    May 29, 2014

    Resolve
  • Class - 2

    Reissue: nov #34941531p. down spouts/leaders cracked and split at various locations throughout run from 3rd to 1st flr at #2 exit. remedy: repair defects noted.

    Apr 5, 2013

    Resolve
  • Class - 2

    Reissue nov #34941532r cracked open joints located @ south elevation (mcdougal st) roof drain pan leaking in various location. rem: repair defects noted.

    Apr 5, 2013

    Resolve
  • Class - 2

    Fire proofing material displaced/missing. at boiler room concrete encased steel column in front of #2 boiler at base of column concrete fireproofing displaced exposing steel. remedy: provide/maintain fire

    Feb 8, 2012

    Resolve
  • Class - 2

    Cracked/open solder joints. at south elevation (mcdougal st) roof copper drain pan leaking various locations. remedy: repair defect noted.

    Feb 8, 2012

    Resolve
  • Class - 2

    Down spouts/leaders cracked/split. at: exit 2 exterior leaders cracked/split various locations flrs 1-3. remedy: repair/replace downspouts/leaders.

    Feb 8, 2012

    Resolve
  • Class - 2

    Doors not closing. at 1st sty stair e, cross corridor #8, cross corridor near rm 104. at 3rd sty stair h cross corridor doors #5 & 8 door for room 302 missing hardware (knob set). remedy: repair/replace doors

    Feb 8, 2012

    Resolve
  • Class - 3

    Reissue: fail to maintain bldg walls or appurtenances. noted: at staircase # 10. extending from 3rd floor to cellar- spalling of inner wallsdue to water penetration. remedy: repair/water proof as necessary.

    Jun 23, 2010

    Resolve
  • Class - 3

    Fail to maintain exterior bldg wall. noted: exterior brick wall enclosing stair case "h", extending from 3rd floor to basement by water affecting inner walls. remedy: repair exterior brick wall

    Jun 23, 2010

    Resolve
  • Class - 2

    Fail to maintain bldg in code compliant manner. noted: extensive spalling of wall & ceiling due to stair case bulk head. remedy: maintain bldg wall

    Jun 23, 2010

    Resolve
  • Class - 2

    Fail to maintain bldg walls or appurtenances. noted: cracks observed in exterior bldg wall (bricks) located at (kitchen locker room) also evidence of cracks & missing mortar. thru out section of brick facade.

    Jun 23, 2010

    Resolve
  • Class - 2

    Fail to maintain bldg in code compliant manner. noted: foundation walls at cellar level (boiler room) in dive with missing, loose bricks, evidence of extensive water penetration at said locations. missing morta

    Jun 23, 2010

    Resolve
  • Class - 2

    Fail to maintain bldg in code compliant manner. provide required corridor width per bc 1016.2;27-369. noted: deck & chair used by security personnel obstructing 2/3 the width of corridor at 1st floor. remedy:

    Jun 23, 2010

    Resolve
  • Class - 3

    Failure to maintain. at stair 10 from 3flr to cellar brick exterior wall has become porous. allowing precipitation to spall interior plasterremedy: waterproof brick repair plaster.

    May 19, 2009

    Resolve
  • Class - 1

    Failure to maintain hazardous fireproofing on electric room ceiling was removed (abatement) and not replaced, exposing wood joists and sub flooring to fire hazard. remedy: replace firestopping.

    May 19, 2009

    Resolve
  • Class - 3

    Reissue: 34711398l plaster spalling and water stained on wall girls bath by room 301, above toilets. remedy: repair walls.

    May 19, 2009

    Resolve
  • Class - 3

    Reissue: 34711399n exterior bricks around staircase "h" porous allowing precipitation to spall plaster inside stairwell 3 flr to basement. remedy: repair brick and plaster.

    May 19, 2009

    Resolve
  • Class - 2

    Exterior brick facade and foundation wall has become porous and allowing rain water into the bldg causing interior damages by exit "h" 3rd fl down to the basement. remedy: water-proof exterior brick wall and

    Nov 19, 2008

    Resolve
  • Class - 2

    Plaster is spalling off the wall located in the girls bathroom next toroom 301 on the 3rd fl level. remedy: repair/replace plaster on walls.

    Nov 19, 2008

    Resolve
  • Class - 2

    Concrete ceiling is spalling located under the public side (waxhead) w/exposed rebars on the boiler room level. remedy: repair/replace boiler rm concrete ceiling.

    Nov 19, 2008

    Resolve
  • Hazardous

    Failure to maintain exterior. defect noted: water penetration from exterior brick into interior. defect location next to staircase #9 & #8 and next to windows in room 219. noted: mortar joints are washed at

    Feb 8, 2007

    Resolve
  • Hazardous

    Re-issue:34510348m. interior staircase #9 is spalling plaster from 3rdfloor to bulkhead. also noted: room #219 spalling plaster corner next to windows and staircase #8 spalling plaster. remedy: repair plaster

    Feb 8, 2007

    Resolve