Violations at 330 Crown Street

Brooklyn, NY 11225 · BBL 3-01297-0026 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

23 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2011 inspection report

    Mar 1, 2013

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2011 inspection report

    Mar 1, 2013

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    May 19, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed

ECB violations

The newest 50 of 81 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 2nd fl stair h,i obstructed/blocked with multiple various items chairs,tableschalk pads etc.rem:comply with code.

    Jun 23, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 2nd and3rd floors hallways installed hung decorations non fire retarted to ceilings.rem:comply with code.

    Jun 23, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 1st fl exit 2,1,gym/play area 2nd fl stair h,d,c,f auditorium 4th fl stair c,b,e,g 5th fl stair f,b,doors are in disrepair/racked when tested.rem:r

    Jun 23, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self closing.noted:at 1st fl exit 7.1 doors are indisrepair/not closing when tested.rem:repair/replace door.

    Jun 23, 2026 · Penalty $625

    Active
  • Class - 2

    Reissue ecb#35717261y failure to maintain building in code-compliant manner.noted:at 1st fl boys bathroom#161 entrances/floor missing sillononeten/bowing throughout various areas.rem:repair and/or replace.

    Jun 23, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: auditorium exits by stage both have storage blocking egress. remedy: comply with code.

    May 13, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue: 35682799z-failure to maintain building in code-compliant manner: boys restroom at(101) entrance doors missing floor sill. concrete is not even causing tripping hazard. also noted: doors at auditorium s

    May 13, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35674634k failure to maintain building in code-compliant manner.at time of my inspection i observed at the 1st floor level the boys restroom (161)by the entrance door is missing the threshold has crack

    Jun 13, 2024 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 1st floor level boys restroom(161)by the entrance door is missing the threshold has cracks broken/missing tiles and uneven area throughout.rem:repa

    Apr 11, 2023 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 3rd floor em#a by 304,em#b by stair e,2nd floor em by 204,1st floor

    Apr 11, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35643591h failure to maintain building in code-compliant manner.noted:at 5th floor stair b,f,4th floor b,c,g,2nd floor stair c,f,corridor by stair e,1st floor stair d by exit 6,smoke by exit 1,2,cafeter

    Apr 11, 2023 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing.noted:the exterior door at exit 1 and bulkheads are not working properly.rem:repair/replace door.

    Apr 11, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. at time of inspection observed roof level all 3 bulkhead stucco,ganding and painting are missing,and also found crack at various location on bricks. ceilin

    Jun 6, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. at time of inspection observed at 2nd,3rd and 4th fl corridor/smoke door are not working properly and 1st fl exit door next to gym are also not working. re

    Jun 6, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner noted: rear wall at playground area bricks/mortar missing/none. rmdy: repair and/or replace.

    Apr 12, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner no fire stoppingper bc 712.3.27-345 noted: at cellar level electrical room fire stopping missing none at various locations. rmdy: provide/maintain fire stop

    Apr 12, 2018

    Resolve
  • Class - 3

    Failure to maintain building in code compliant manner noted: cellar (non-public) staircase to rear playtround in disrepair/unattached at bottom landing. rmdy: repair and/or replace.

    Apr 12, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner use of prohibited door and/or hardware per bc 1008.1.8 27-371 (j) noted; at first flcafeteria exit door installed latch bolt lock. rmdy: provide legal har

    Apr 12, 2018

    Resolve
  • Class - 3

    Failure to maintain building in code compliant manner noted: at 2nd floor stairway d door racked/rubbing in disrepair. rmdy: repair and/or replace.

    Apr 12, 2018

    Resolve
  • Class - 2

    Exit door not self closing noted at 4th floor stairway f and 3rd floorstairway g exit door no self closing missing/none. rmdy: repair/ replace door.

    Apr 12, 2018

    Resolve
  • Class - 2

    Reissue#35216196l failure to maintain bldg walls or appurtenances. water penetration at cellar level foundation wall has become porous & allowing rain water into the cellar. remedy: water proof foundation wall.

    May 8, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. lack of emergency lighting for exits. audi has emergency lights on 1 unit and unit out in hallway bx 109, lunch room has 1 unit out above door 1 nit out in the

    Oct 13, 2016

    Resolve
  • Class - 3

    Reissue 35198205m failure to maintain bldg wall(s) or appurtenances (exterior) ongoing water penetation of cellar (during heavy rainfall) rmdy: maintain exterior building wall.

    Oct 13, 2016

    Resolve
  • Class - 3

    Reissue#35146832m failure to maintain bldg in code compliant manner.note ongoing water penetration of cellar (during heavy rain fall).rem comply w/ nov

    Oct 23, 2015

    Resolve
  • Class - 2

    27-misc. misc. violations. noted: at time of inspection at school entrance on crown st sidewalk multiply tripping hazards - approx 2"-5"vertical uplifting. rmdy: comply w/notice of violation.

    Jul 30, 2015

    Resolve
  • Class - 1

    Violation #35099641k issued on 7/16/14 failure to maintain building wall(s) or appurtenances. water penetration at cellar level foundationwall has become porous and allowing rainwater nto the cellar level and

    Jul 30, 2015

    Resolve
  • Class - 2

    Exit door defective.@ 2nd fl auditorium stairway'i'&'e'door is racked to fl & do not self close requiring extreme force to close.rem:replacedoor.

    Jul 16, 2014

    Resolve
  • Class - 2

    Reissue #35019159j water penetration.@ cellar lvl foundation wall has become porous & allowing rainwater into the cellar lvl & causing waterto pond adjacent to the gas meter room.rem:waterproof foundation wall

    Jul 16, 2014

    Resolve
  • Class - 2

    There is a 4'feet vertical crack at the staircase "e"at roof bulkhead.rmdy: repair and/or replace crack in wall.

    May 24, 2013

    Resolve
  • Class - 2

    Reissue: 3493323k foundation wall has become porous and allowing rainwater into the cellar level & causing water to pond adjacent to the g as meter room. rmdy: water proof foundation wall.

    May 24, 2013

    Resolve
  • Class - 2

    Interior exit doors on the staircase d,e,f & g on floors 2nd,3rd & 4th is defective. noted: exit door are dragging on the floor causing doors not to be self closing. remedy: repair and/or replace exit doors.

    Feb 15, 2012

    Resolve
  • Class - 2

    Reissue # 34908806k. the foundation wall has become porous & allowing rain water into the cellar level causing interior damage located adjacent to the gas & electrical room. remedy: water proof exterior founda

    Feb 15, 2012

    Resolve
  • Class - 2

    At the cellar level foundation walls have become porous allowing waterpenetration throughout entire cellar gas meter rm, electric panel rm, open space boiler rm. water & moisture present on walls & flrs.

    Apr 12, 2011

    Resolve
  • Class - 3

    Reissue: 34742637l. defective doors all corridor doors 1-5 flrs also 5th flr stair c, 4 flr stair e,3 flr stair e,f, 2flr stair b. all doorsnot closing proerly. also gate to roof severely damaged not keeping

    May 20, 2009

    Resolve
  • Class - 2

    Exterior perimeter chainlink fence leaning and loose at rear school yard (west side). remedy: secure fence forthwith.

    Dec 12, 2008

    Resolve
  • Class - 3

    Defective doors. all corridor doors (1-5) 5th fl stair c, 4th fl staire, 3rd fl stair e,f, 2nd fl stair b, all doors are not closing properly. remedy: replace doors.

    Dec 12, 2008

    Resolve
  • Hazardous

    Re-issue # 34295276n. windows are inoperatable/broken located through-out the school (1st floor - 5th floor). remedy: replace windows.

    Mar 27, 2007

    Resolve
  • Hazardous

    Re-issue # 34509724z. roof flashing is missing on roof level above boys bathroom at 1st floor extension at rear. remedy: install missing flashing.

    Mar 27, 2007

    Resolve
  • Hazardous

    Re-issue # 34509722p. exterior foundation wall has become porous and allowing water to enter the building located at cellar level at all exterior walls. remedy: water-proof walls.

    Mar 27, 2007

    Resolve
  • Hazardous

    Re-issue # 34509721n (partial). exit door missing door check at 5th floor exit "b". remedy: install door check.

    Mar 27, 2007

    Resolve
  • Hazardous

    Reissue #34312629l there are cracked walls in the gas meter room. and old coal incineration storage rm. (basement). remedy: repair the wall at above location.

    Feb 14, 2006

    Resolve
  • Hazardous

    Reissue #34312634x there are missing flushing located: over 1st floor extension at rear of premises over boys toilet. remedy: install missing flashing.

    Feb 14, 2006

    Resolve
  • Hazardous

    Reissued #34467190k leak from drain pippe elbow at room 509. remedy: repair drain pipe.

    Feb 14, 2006

    Resolve
  • Hazardous

    Reissue #34467191m water penetration through foundation walls into cellar at all sides. remedy: stop water penetration.

    Feb 14, 2006

    Resolve
  • Hazardous

    Missing door closers in 5fl exit b door, and 4 fl stair g exit door. remedy: install door closers.

    Feb 14, 2006

    Resolve
  • Non-hazardous

    Water penetration through foundation walls into cellar at all sides.remedy:stop water penetration/make all necessary repairs.

    Mar 16, 2005

    Resolve
  • Non-hazardous

    Reissue 34412691k.leak from drain pipe from roof at 5th floor inside classroom.remedy:repair drain/stop leak make all repairs.

    Mar 16, 2005

    Resolve
  • Non-hazardous

    Reissue 34412692m.concrete slab ceiling in cellar is missing,cracked spalling & exposed rebar at hoist room and work shop in cellar.remedy:repair concrete slab/ceiling in cellar.

    Mar 16, 2005

    Resolve
  • Non-hazardous

    "reissue" failure to maintain. defects are. in cellar south side. hoist room and work shop room cement ceilings are crack,loose,hanging and missing sections exposing steel. remedy: repair ceilings.

    Jan 16, 2004

    Resolve
  • Non-hazardous

    "reissue" failure to maintain. defect is. on 5th floor in room #509 roof leaks around drain pipe. remedy: repair roof.

    Jan 16, 2004

    Resolve