Violations at 227 7 Avenue
Brooklyn, NY 11215 · BBL 3-01082-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
The newest 50 of 72 DOB violations. The city keeps the complete history.
- Elevator elevatorrequired
E-elevator elevatorrequired
Dec 4, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 4, 2019
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - active - Elevator annual inspection / test elevatorrequired
Violation issued to elevator - failure to file category 1 2017 inspection/test
Apr 5, 2019
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator - failure to file category 1 2017 inspection/test
Apr 5, 2019
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator - failure to file category 1 2017 inspection/test
Apr 5, 2019
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator - failure to file category 1 2017 inspection/test
Apr 5, 2019
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 19, 2018
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 22, 2017
Dob violation - active - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 27, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 27, 2016
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2010 inspection/test
Dec 13, 2011
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 3, 2011
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Vcat1-elevator annual inspection / test elevatorrequired
Oct 8, 2010
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 1, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 1, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 24, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 24, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 30, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 12, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 4, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 4, 2007
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 2, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 6, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 6, 2006
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 5, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 5, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 11, 2004
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 11, 2004
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 28, 2003
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 28, 2003
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 19, 2002
Dob violation - dismissed - Elevator elevatorrequired
3p6289
Aug 15, 2001
Dob violation - resolved - Elevator elevatorrequired
3f5413
Jul 21, 2000
Dob violation - resolved - Elevator elevatorrequired
3p6289
Jul 21, 2000
Dob violation - resolved - Construction other optional
C-construction other optional
May 28, 1999
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed
ECB violations
The newest 50 of 247 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.at the time of inspection,there were multiple through floor penetration open.application for work types are renew but fi
Apr 3, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.the following rooms with 2nd exit doors from classrooms were blocked/nailed shut:302,300,320,324,328,234,240,241,245,247,251,208,204,209,214,211,216,218,229
Apr 3, 2026 · Penalty $3,125
Active - Class - 2
Stair and/or floor identification signs missing and/or defective.at the time of inspection multiple exit discharge doors do not have designation,these include discharge door off cafeteria exit#14 vestibule/disc
Apr 3, 2026 · Penalty $625
Active - Class - 2
Exit door not self-closing.at the time of inspection,the following exit discharge doors were not self-closing:exit#14,discharge door off cafeteria,exit 11/13.rem:repair/replace door.
Apr 3, 2026 · Penalty $625
Active - Class - 2
Reissue#35691958l failure to maintain building in code-compliant manner.at the time of inspection,the marble flooring at exit discharge 7 and 9 were cracked/shattered window panel next to exit 17 stair on 4th f
Apr 3, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35655082h at the time of inspection,the following room/spaces had efflorescence/spalling/leaks/buldging staircase l bulkhead,room 404,410,424,staircase 2/exit 4 on 4th fl,438,443,445,460,336,348,302,314
Apr 3, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35691959n at the time of inspection,the commercial gas stove used in cafeteria was not equipped with an ansul system.rem:repair and/or replace.
Apr 3, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.at thetime of inspection,emergency light in corridor next to 1st floor gym w
Apr 3, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).at the time of inspection,the following doors had turn knob handles-401,403,405,411,416,,ki
Apr 3, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.at the time of inspection,the following doors were not self-closing corridor door nextto 408,staircase 11 on 4th floor 402,416 corridor doors next to 414,44
Apr 3, 2026 · Penalty $1,250
Active - Class - 2
Failure to comply with the commissioner's order to file a certificate of correction with the department of buildings. no certificate of correction on file for vio#39095380z as of 1/16/26.., file a certificate o
Jan 16, 2026 · Penalty $6,250
Active - Class - 2
Failure to certify for certificate of corrections for summons #39095380z., file a certificate of correction
May 8, 2025 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: a leak from the roof above is causing water damage a mold to grow on the wallsat room #424. remedy: repair/replace.
Apr 11, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: the poollocker room has peeling, chipping and mold developing through out the ceiling and walls. remedy: repair/replace.
Apr 11, 2025 · Penalty $1,250
Resolve - Class - 2
Re-issue #35657643h. failure to maintain building in code-compliant manner. noted: at t. o. i. the commercial gas stove in the kitchen does not have the ansul. remedy: comply with notice of the violation.
Apr 11, 2025 · Penalty $3,125
Active - Class - 2
Re-issue #35657644j. failure to maintain building in code-compliant manner. noted: the marble flooring at exit 7 on first fl. and at exit 9 on the first floor is cracked, chipped with holes all over the floor.
Apr 11, 2025 · Penalty $3,125
Active - Class - 2
Observed debris chute attached to existing supported pipe scaffold. debris chute height approximately 55ft high. upon review the department records ( bis & dob now) did not observe any active permit to install
Mar 15, 2025
Resolve - Class - 2
A8-i observed 2 workers moving 2 vertical sws supports at the corner of 5th st & 7th avenue, approx 12" apart from their original location, contrary to the approved sca drawings page eq-003.00 & eq-006.00 for s
Sep 20, 2023 · Penalty $3,125
Resolve - Class - 1
I observed 2 workers moving 2 vertical sws supports at the corner of 5th st & 7th avenue, approx 12" apart from their original location. upon dob research, this work was outside the description of work on the a
Sep 20, 2023 · Penalty $6,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner:noted:on 1st fl next to room 145, 150 on second floor next to room 210,208,248 on 3rd fl next to room 312, on 4th fl next to room 462.all doors not closing
Feb 14, 2023 · Penalty $625
Resolve - Class - 2
Reissue #35655086p failure to maintain building in code compliant manner.noted:observed on 1st fl at exit 7 & 9 floor has cracks & holes at various locations throughout.remedy:repair and/or replace.
Feb 14, 2023 · Penalty $1,562
Active - Class - 2
Reissue #35655085n failure to maintain building in code-compliant manner.noted:at cafeteria kitchen commerical gas stove does not have ansul system.remedy:repair and/or replace
Feb 13, 2023 · Penalty $1,562
Active - Class - 2
Reissue #35561282p(4/30/21)failure to maintain building in code compliant manner no fire stopping per bc 7123;27-345 at cellar pipes cable penetrated through walls foundation without fireproofing.remedy:mainta
Apr 21, 2022 · Penalty $3,125
Resolve - Class - 2
Reissue #35561275r(4/30/21)failure to maintain building in code compliant manner at 1st floor exit 7,9 marble floor cracked with holes plus defective.remedy:repair/replace
Apr 21, 2022 · Penalty $1,562
Active - Class - 2
Reissue #35561276z(4/30/21)failure to maintain building in code compliant manner at cafeteria kitchen commercial stove does not have ansul systems.remedy:repair/replace & comply with notice of violations.
Apr 21, 2022 · Penalty $1,562
Active - Class - 2
Reissue #35561277k(4/30/21)failure to maintain building in code complaint manner at cellar water penetration floods in several areas deteriorated foundation walls.remedy:repair/replace & comply with notice of v
Apr 21, 2022 · Penalty $1,562
Resolve - Class - 2
Reissued #35561278m(4/30/21)failure to maintain building in code compliant manner illumination for exits exit discharges & public corridors per bc 1006.1;27-381 emergency lights are not operational when tested
Apr 21, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue #35561279y(4/30/21)failure to maintain building in code compliant manner at 4th, 3rd, 2nd & 1st floors water damage to walls & ceilings due to water penetration through pipes.remedy:repair and/or replac
Apr 21, 2022 · Penalty $1,562
Active - Class - 2
Reissue #35561280l(4/30/21)failure to maintain building(in code compliant)walls or appurtenances at courtyards/school yard detaining walls stones & mortars detachment plus bulging outward.remedy:maintain exteri
Apr 21, 2022 · Penalty $3,125
Active - Class - 2
Reissue #35561281n(4/30/21)exit door not self closing at 5th street sides(exp #4)not close properly dut to deteriorated conditions from elements including hinges & hardware plus bottom doors several smoke doors
Apr 21, 2022 · Penalty $1,562
Resolve - Class - 2
Failure to obtain temp permit prior to installation/use of temp equipment observed sws erected@exp2 no active permit issued on bis/dobnow for sws obtain temp const permit
Mar 24, 2022 · Penalty $1,250
Active - Class - 2
Failure to maintain bldg in code compliant manner: no fire stopping per bc 712.3;27-345. noted: at cellar level,pipes,cables penetrating through block wall on different locationon. remedy: provide/maintain fire
Apr 30, 2021 · Penalty $1,250
Resolve - Class - 2
Exit door not self closing. noted: at exp#4(5th street)existing emergency exit doors not closing properly,sheet metal detachment & corrision due to flooding & maintenance,also smoke doors on different locations
Apr 30, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg walls or appurtenances. noted: at exp#4(5th st)retaining wall in stone has bulging,detachment of stones & mortar,generating instability to the metal fence & emergency staircase supporte
Apr 30, 2021 · Penalty $1,250
Active - Class - 2
Failure to maintain bldg in code compliant manner: noted: damage to walls,ceiling & pipe insulation due to water penetration at 4th fl(rm 416,418,420);3rd fl(rm 322,320,318)2nd fl(rm 220 next to rm 218)1st floo
Apr 30, 2021 · Penalty $625
Active - Class - 2
Reissue#35495118k failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: at the cafeteria,hallways,stairs;existing emergency li
Apr 30, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue35495119m failure to maintain bldg in codecompliant manner:noted:@cellar level,flooding in diff storage rms&bathrm due to water leaksor water penetration thru foundation walls,causing deterioration in ma
Apr 30, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue35495116r failure to maintain bldg in codecompliant manner:noted:@1fl level,kitchen rear commercial gas dont have ansul system.repair&/or replace.
Apr 30, 2021 · Penalty $1,562
Active - Class - 2
Reissue35495117z failure to maintain bldg in codecompliant manner:noted:@exp3 interior facade:on diff level fls,cornice&stone lintels have cracks,detachment,holes in diff location.repair &/or replace.
Apr 30, 2021 · Penalty $1,562
Active - Class - 2
Reissue#35422484n failure to maintain bldg in code compliant manner. noted: at cellar level there's water on the floor due to a leaking bathroom drain pipe. remedy: repair &/or replace.
Apr 29, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue#35422480x failure to maintain bldg in a code compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: the emergency light throughout the bldg were not work
Apr 29, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue#35422481h failure to maintain bldg in code compliant manner: noted: on the 1st fl at exit#7 & 9 the marble floor is cracked. remedy:repair &/or replace.
Apr 29, 2020 · Penalty $1,562
Active - Class - 2
Reissue#35422483l failure to maintain bldg in code compliant manner. noted: at 1st fl kitchen rear(10)carrier commercial gas store do not have an ansul system. remedy: provide ansal system.
Apr 29, 2020 · Penalty $1,562
Active - Class - 2
Restore service to device
Jan 14, 2020 · Penalty $625
Resolve - Class - 2
Restore service to device
Jan 14, 2020 · Penalty $625
Resolve - Class - 2
Restore service to device
Jan 14, 2020 · Penalty $625
Active - Class - 1
Cease use item: damaged disc brake monitor class 2 items: replace worn hoistway door gibs where needed. secure hoistway door gibs where needed. replace car door gibs where needed. unguarded cab lighting. worn c
Jan 14, 2020 · Penalty $1,250
Resolve - Class - 2
Restore service to device
Jan 14, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner use of prohibited door and or hardware per bc 1008.1-8 27-371(j) noted at auditorium al th emain doors are attached with kick down door holders.provide lega
May 6, 2019 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:@cellar standing water due to bathrom drain pipe leak.rem: repair/replace.
May 6, 2019