roofy

417 6 Avenue

Brooklyn, NY 11215BBL 3-01000-0001Map

Owner of record: NYC Department Of Education

417 6 Avenue is a school building built in 1877 in Brooklyn, 11215. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
12
ECB violations
69
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 12

  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    May 5, 1999

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    May 5, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
Show 2 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Aug 3, 1992

    Vp*-violation unserved ecb- dismissed

ECB violations · 69

  • Class - 2

    Reissued 35322243y exit door not self closing note at 1st floor room 108 door closing (door is on site to be replaced) repair or replace door

    May 2, 2019

    Resolve
  • Class - 2

    Reissued 35322246j failure to maintain building in code compliant manner illumination for eixts eixt discharges and public corridors per bc 1006.1;27-381 .per bc 1006.1;27-381.note exit lights not owkring throu

    May 2, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliance manner. use of prohibited door and/or hardware per bc 1008.1.9 27-37. locking devices that require a key to operate on door at following locations 108,102.rmdy:provid

    Mar 19, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. illumination for exits, exti discharges and public corridors per bc 1006.1; 27-381 noted exit light not working outside room 100. rdy: repair or replace ligh

    Mar 19, 2018

    Resolve
  • Class - 2

    Exit door not self closing. noted cafeteria exiot door f not closing. rmdy: repair and or replace.

    Mar 19, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. at cellar electrical room storage of metal lockers. rmdy: repair or replace.

    Mar 19, 2018

    Resolve
  • Class - 2

    Reissue #35260482k exit door not self closing. noted the door not closing at 1st floor room 1008 door exit c and f and 2nd. rmdy: repair or replace door.

    Mar 19, 2018

    Resolve
  • Class - 2

    Reissue of nov#35260480r failure to maintain bldg in code compliant manner: noted: basement boiler room and gas meter room stucco w/speaker in the walls due to the steam of boiler at various location. rmdy:

    Mar 19, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: @ basement level, electrical room, observed chairs, plastic boxes, cabinets, microwave, refrigerator & cleaning tools. rem: comply w/ code/remove all ma

    May 3, 2017

    Resolve
  • Class - 2

    Failure to naintain bldg in code compliant manner.noted:water damage to ceiling due to water penetration through roof at rm #200b,203.rem:comply w/code repair and install.

    May 3, 2017

    Resolve
Show 40 more ↓
  • Class - 2

    Exit door not self-closing.noted:the doors have defective at the top hinge.the screw hole is loose and the door not close properly after use at the following locateions:at 1st fl,rm#100b, door exit #c,f and 2nd

    May 3, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.noted:at bsmt level,boiler rm and gas meter rm, stucco w/spalling in the walls due to the steam of boiler at various locations.rem:comply w/code repair the wall

    May 3, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner:floor numbering signs missing.noted:at stairway a,b,e,f,missing floor numbering signs @ 1st,2nd,and 3rd floors.rem:comply w/code/install floor signs.

    May 3, 2017

    Resolve
  • Class - 2

    Failure to provide unobstructed exit passageway. noted: at basement level observed tables,chairs,boxes & cabinets being stored through hallways & exit passageways. also at stairway'f',3rd sty landing,tables and

    Sep 22, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. egress doors in room #s 300 (book room) and 302 computer lab) obstructed with book shelves, ta bles and chairs.all rooms throughout the bldg are arranged as a

    May 4, 2015

    Resolve
  • Class - 2

    B254,32a,15,50a,50b,50c,50d,50e. 50a-king valve leaking; 50b-emergenceswitch at second door entrance missing; 50c-spill switch missing on f lue damper; 50d-boiler room not a storage room; 50e-fresh air intake

    Nov 7, 2014 · Penalty $500

    Active
  • Class - 2

    Re-issue 35018168r exit doors not self closing numerous doors throughout have defective / inadequate door closures installed which pull hinges, rack doors and require force to open. remedy: repair or replace do

    Jul 3, 2014

    Resolve
  • Class - 2

    Reissue #34981695h defective doors at numerous locations throughout,previous repairs & replacements are inadequate,installed door closers are sized wrong or installed wrong & pull hinges & rack doors & are not

    May 17, 2013

    Resolve
  • Class - 2

    Reissue 34927513k doors racked preventing them from closing properly at various locations throughout bldg rem: repair or replace doors

    Jun 1, 2012

    Resolve
  • Class - 2

    Missing fire stop. at cellar electric room,no fire stop at conduit penetration of ceiling & behind service box at ceiling corner. remedy: provide fire stop.

    Sep 8, 2011

    Resolve
  • Class - 2

    Defective doors. the fire self closing exit doors are racked to frame requiring extreme force to open,at both exit doors from stairway e. remedy: repair doors to properly open.

    Sep 8, 2011

    Resolve
  • Class - 2

    Failure to maintain interior bldg in code-compliant manner. missing bricks @ north wall,ne-section,cafeteria adjacent to mechanical blower. remedy: property maintain interior building in code-compliant manner.

    May 13, 2010

    Resolve
  • Class - 2

    Failure to maintain exterior bldg walls & or appurtenances. broken & defective,rotten/drain leader/with opening @ east. remedy: properly maintain exterior drain leader.

    May 13, 2010

    Resolve
  • Class - 2

    Improper exhaust improper (exhaust) ventilation/at hot water holding tank which is being exhaust to electrical room occupied as locker room. remedy: provide or install/the proper exhaust for hot water holding

    May 13, 2010

    Resolve
  • Class - 2

    Sec. 28-301.1 inadequate exhaust & gas vent. no ventilation fresh air intake at gas meter room. remedy: provide proper gas vent & exhaust for equipment.

    May 13, 2010

    Resolve
  • Class - 2

    Doors not self-closing. classroom doors found to be not self-closing with doors stops mechanism installed at bottom. remedy: remove door stops mechanism to make doors to class rooms self-closing.

    May 13, 2010

    Resolve
  • Class - 1

    Occupancy contrary to that allowed by c of o or dept records. gas meter room is arranged & occupied as storage room. contrary to dob code. (basement level). remedy: discontinue illegal use forthwith.

    May 13, 2010

    Resolve
  • Class - 1

    Occupancy contrary to that allowed by c of o or dept records. at northwest section of front yard & side yard setback found with the parking of 3 motor vehicles with nys plates #aed 3522,ara 8018 & eeo 9110.

    May 13, 2010

    Resolve
  • Class - 2

    No fire stopping per bc 712.3. girls restroom found with opening @ ceiling,pipe area. remedy: properly maintain the required fire stopping.

    May 13, 2010

    Resolve
  • Class - 2

    No fire stopping per bc 712.3. metal ceiling found with opening @ cafeteria basement level. remedy: provide & maintain the required fire stopping.

    May 13, 2010

    Resolve
  • Class - 2

    No fire stopping per bc 712.3. missing fire separation partition @ cafeteria & public hall southwest basement level. remedy: provide & maintain the required fire stopping.

    May 13, 2010

    Resolve
  • Class - 1

    Failure to maintain exterior bldg (in code-compliant) walls & or appurtenances. broken,defective,cracked,leaned & loose brick wall with dislodged coping stone above at east of properly line,ne-section of playgr

    May 13, 2010

    Resolve
  • Class - 2

    Failure to maintain exterior bldg in code-compliant manner. step crack @ brick wall above arch to window,east elevation,se-section. remedy: properly maintain exterior building forthwith.

    May 13, 2010

    Resolve
  • Class - 2

    Prohibited hardwares in used per bc 1008.1.8. diamond gate found installed @ exit (h) used for boiler room (and in front of said exit) with mechanism to receive a padlock. remedy: provide legal hardware.

    May 13, 2010

    Resolve
  • Class - 1

    Failure to provide unobstructed exit passageway. the storage of a-frame ladder & wooden closet @ fire stair f. remedy: remove all obstructions forthwith.

    May 13, 2010

    Resolve
  • Class - 1

    Failure to provide unobstructed exit passageway. the storage of closets @ 2nd & 3rd fl stairs 6 & f public hall landing. remedy: remove all obstruction forthwith.

    May 13, 2010

    Resolve
  • Class - 1

    Failure to provide unobstructed exit passageway. the storage of metal closets,chairs,etal,at fire stair public hall 3rd sty. remedy: remove all obstruction forthwith.

    May 13, 2010

    Resolve
  • Class - 1

    Failure to provide unobstructed exit passageway. improper storage of combustible cardboard boxes above platform,refrigerator,food cart trays/items on wheels,etal,at cafeteria's public halls. remedy: remove obst

    May 13, 2010

    Resolve
  • Class - 1

    Failure to provide unobstructed exit passageway. noted: landing beyondexit door (g) @ basement level found with the storage of folding tables. remedy: properly remove obstruction forthwith.

    May 13, 2010

    Resolve
  • Class - 2

    Failure to maintain exterior bldg in code-compliant manner. improperlycompleted drain/leaders w/o the required connection to storm drain at ,building front yard set back,west. remedy: properly maintain exterior

    May 13, 2010

    Resolve
  • Class - 2

    Failure to maintain adequate housekeeping. the storage of combustible material at exit 6 & f stair landing above radiators. remedy: remove combustible materials stored above radiators. remedy: remove combustibl

    May 13, 2010

    Resolve
  • Class - 2

    Failure to maintain interior bldg in code-compliant manner. spalled bricks @ wall to stair f/g. remedy: property maintain interior building in code-compliant manner.

    May 13, 2010

    Resolve
  • Class - 2

    Failure to maintain interior bldg in code-compliant manner. spalled brick walls @ gas meter room. remedy: property maintain interior building forthwith.

    May 13, 2010

    Resolve
  • Class - 2

    Door not self closing. iron door to closet which swung egress to fire stair landing found to be not self-closing. at primary means of egress from 1st fl to basement level. remedy: properly repair or replace or

    May 13, 2010

    Resolve
  • Class - 2

    Inadequate exit signs with direction/ac arrows. note: inadequate exit signs with directional arrows @ cafeteria,basement level. remedy: install adequate exit signs with directional arrows forthwith.

    May 13, 2010

    Resolve
  • Class - 2

    Failure to maintain: inadequate exit signs with directional arrows. noted: inadequate exit signs with directional arrows at classrooms showing the locations of fire stairs from classrooms. remedy: install adequ

    May 13, 2010

    Resolve
  • Class - 1

    Occupancy contrary to that allowed by c of o or dept records. electrical room is arranged & occupied as locker room contrary to dept records or code. (basement level). remedy: discontinue illegal use forthwith.

    May 13, 2010

    Resolve
  • Class - 2

    Exterior sidewalk is cracked and lifting causing a tripping hazard w/a3" lip on 8th st. remedy: repair public sidewalk.

    May 22, 2009

    Resolve
  • Class - 2

    Exterior "no parking" sign on 6th ave on public sidewalk is loose. remedy: repair/replace "no parking" sign.

    May 22, 2009

    Resolve
  • Hazardous

    Noted: water penetration throughout (wall) mortar joints at exit #2a exit #5 & #6 and exit #1a at 1st flr. remedy: make all repairs to brickwalls.

    Feb 17, 2006

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Feb 1, 2024 · Apt BLDG

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1877
Floors
4
Residential units
—
Building area
28,000 ft²
Lot area
17,283 ft²
Zoning
R6B
Community board
306
Council district
39
Block / lot
1000 / 1
Assessed value
$2,134,800
Landmark / historic district
INDIVIDUAL LANDMARK

Questions about 417 6 Avenue

Who owns 417 6 Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 417 6 Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 417 6 Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 417 6 Avenue built?

City records list 1877 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.