48 Park Place

Brooklyn, NY 11217BBL 3-00941-0050Map

Owner of record: NYC Department Of Education

48 Park Place is a school building built in 1908 in Brooklyn, 11217. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
46
ECB violations
100
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 46

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
Show 36 more ↓
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Construction other optional

    Work w/o a permit: noted: metal structure constructed at the roof west section center.approx. 60 ft l 15 ft w and 14ft h to create a sound b arrier for a nummber of a/c unit(liquid chiller) north & west side remedy: obtain a permit if feasible or restore the premises to legal prior condition

    Aug 29, 2000

    Vw*-violation - work w/o permit dismissed
  • Construction other optional

    C-construction other optional

    Apr 30, 1999

    Dob violation - active
  • Construction other optional

    Hazardous

    Apr 30, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 10, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 10, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1993

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1993

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1993

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1993

    Dob violation - dismissed

ECB violations · 100

  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at (1st fl)stair c, a (2nd fl)stair e, a (3rd fl) stair a, b (4th fl)stair c, b doors are indisrepair/racked. remedy: repair and/or replace.

    Apr 15, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at (1st fl)auditorium, (basement)cafeteria, gym emergency lights

    Apr 15, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissued ecb#3566333n failure to maintain building wall or appurtenances.noted:water damage to the roofs bulkhead causing spalling and peeling of walls plaster at 4 fl staircase a and 3rd fl staircase a.rem:mai

    Jul 2, 2024 · Penalty $3,125

    Resolve
  • Class - 2

    Reissued ecb#35663327r failure to maintain building in code compliant manner:noted 1st floor auditorium emergency lights not working properly when tested total#5.cellar boiler room 2 emergency lights not workin

    Jul 2, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued:ecb#35663326p exit door not self closing.noted 4th floor exitdoor not closing properly at staircase c 2nd floor exit door exit doornot closing properly at staircase a,b,c.rem:repair/replace door.

    Jul 2, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.note observed atstaircase a between 5th,4th,and bulkhead level the interior wall has bulging plaster due to water penetrations when it rains.remedy:repair a

    Mar 7, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35655052r failure to maintain building in code compliant manner:illumination for exits,exit discharges and public corridor per bc1006.1,27-381.note observed at auditorium approx 5 emergency lights are d

    Mar 7, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35655054k failure to maintain building walls or appurtenances.noted observed the exterior wall of staircase a between the 3rd,4th and bulkhead level are porous and allowing water to penetrate into the b

    Mar 7, 2023 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35655053z exit door not self-closing.note observed on 2nd floor stair c and throughout stair a and b,exit doors are not closing properly due to door frame being out of plumb.also at stair c 4th floor ha

    Mar 7, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35328649l-failure to maintain bldg in code compliant manner illumination for exits exit discharges & public corridors per bc1006.1;27-381 noted:in auditorium three emergency lights not working.remedy:c

    Apr 26, 2022 · Penalty $1,562

    Resolve
Show 40 more ↓
  • Class - 2

    Reissue #35490863h exit door not self closing noted:observed on 1st 2nd 3rd floors exit a&b not closing properly.remedy:comply with code

    Apr 26, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35561291r failure to maintain building walls or appurtenances noted staircase at 3rd floor to 4th floor has water damage,spalling.remedy:comply with code

    Apr 26, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue35490863h exit door not selfclosing observed:smoke doors@1fl exitc near rm103lcellar level exitd;2fl 2doors exita;2doors exitb 1door exite;3fl,2doors exita;4fl,exitb&exitc.dont fully close properly&also

    May 5, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s) or appurtenances observed:@staircasea,exterior walls,b/w 3fl to roof level have become porous allowing water to enter bldg causing spalling&missing plaster.maintain exterior bld

    May 5, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue35328649l failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:@1fl auditorium 3emergency lights&gym exitc,existing emergency

    May 5, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:observed:@electricalrm excessive storage of boxes,chairs,boards,paint cans,electrical material&metal ladders being stored w/i rm&close to utility boxes.repair &/

    May 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35402214p failure to maintain bldg in code compliant maintain illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: observed in the auditorium on the 1st fl the emergenc

    May 4, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self closing. noted: observed on the 1st fl,2nd fl & the3rd fl next to exit a & b the door are not closing properly. remedy: repair/replace door.

    May 4, 2020 · Penalty $625

    Resolve
  • Class - 2

    Re-issue #35328649l.failure to maintain building in code compliant manner;illumination for exits,exit discharges & public corridors per bc1006.1,27-381 in auditorium,3 of the emergency lights were not working.r

    May 9, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg i code compliant manner:illumination for exites,exit discharges and public corridors.per bc 1006.1:27-381.noted:in the auditorium three of the emergency lights were not working when tes

    Apr 26, 2018

    Resolve
  • Class - 2

    Exit door not self closing.noted exit d on sterling place the door is not closing properly,also exit c the door is hitting each other and isnot closing.rem:repair/replace door.

    Apr 26, 2018

    Resolve
  • Class - 2

    Reissue 34995639k.failure to maintain interior.spalling & cracked plaster walls &/or ceilings @ various locations & @ bulkheads a,b,c & d.rem:repair damaged plaster.

    Jul 8, 2014

    Resolve
  • Class - 2

    27-371(b),reissue 35018152m vision panels.use prohibited thermosplatic/plexiglass in various doors on 3rd,4th & 1st fl.rem:provide required glass panels.

    Jul 8, 2014

    Resolve
  • Class - 2

    Failure to maintain.storage of equipment in electrical panel room.rem:remove equipment keep panel room clear.

    Jul 8, 2014

    Resolve
  • Class - 2

    Reissue 34995641j.water penetration through roof causing water damage to ceilings & walls in various locations.roof has cracked & soggy areas.rem:repair or replace roof.

    Jul 8, 2014

    Resolve
  • Class - 2

    Failure to maintain exterior.water penetration throughout brick walls causing interior damage.rem:repair brick wall.

    Jul 8, 2014

    Resolve
  • Class - 2

    Defective doors at 4floor stairway a,c,3 floor stairway e,2 floor stairway a,doors are racked to frame - broken door closers. remedy: repair/replace doors/closers - maintain doors self closing.

    May 14, 2013

    Resolve
  • Class - 2

    Sec. 27-371(b) plexi vision panels at 4th fl various doors have plexi thermo plastic installed. remedy: replace plexi w/code compliant vision panels.

    May 14, 2013

    Resolve
  • Class - 2

    Failure to maintain emergency lights at auditorium,all emergency lights not working. remedy: repair emergency lighting system.

    May 14, 2013

    Resolve
  • Class - 2

    Reissue 34926589m water penetrating through roof causing water damage to ceilings in various locations. rem:repair or replace roof.

    Jun 29, 2012

    Resolve
  • Class - 3

    Reissue 34926593p at rm 300 window balance not working leaving window inoperatable. rem:repair window.

    Jun 29, 2012

    Resolve
  • Class - 2

    Reissue 34926592n spalling cracked plaster walls &/or ceilings at cellar rm t, vestibule at stair c, bulk heads, rms 404 & 311. rem:repair damage plaster.

    Jun 29, 2012

    Resolve
  • Class - 2

    Reissue 34926590j cracked & spalling bricks in walls of both dumb waiter shafts. rem:repair brick work.

    Jun 29, 2012

    Resolve
  • Class - 3

    Reissue #34856518y broken window balance. at room 300,the window counter balance is broken making window in operable. remedy: repair window.

    Sep 2, 2011

    Resolve
  • Class - 2

    Spalling plaster. spalling plaster ceiling &/or walls at cellar room t1,& exit vestibule stairway c on left. remedy: repair plaster surface.

    Sep 2, 2011

    Resolve
  • Class - 2

    Reissue #34856514r spalling plaster. spalling plaster ceiling &/or walls at bulkhead to stairways a,b,c,d. remedy: repair plaster surface.

    Sep 2, 2011

    Resolve
  • Class - 2

    Reissue #34846811y cracked brick masonry. cracked brick masonry at roof extension of both dumb waiter shafts. remedy: repair brick masonry.

    Sep 2, 2011

    Resolve
  • Class - 2

    Roof leak the roof has become porous allowing rain water to enter room 404. remedy: water proof roof.

    Sep 2, 2011

    Resolve
  • Class - 2

    Approved place of assembly plans not available for inspection! noted: approved plans for pa space auditorium under pa #301060477 no affixed seating. remedy: provide approved pa plan for inspection!

    Apr 15, 2010

    Resolve
  • Class - 1

    Interior : dislodged roof bulkhead walls & fl @ various locations w/ cracks @ stair (c) w/ missing mortar @ stair treads & dislodged metal nosings & metal pans. 7'-0" cracks @ ceiling public hall stair case (c)

    Apr 15, 2010

    Resolve
  • Class - 2

    Failure to maintain interior bldg wall(s) &/or appurtenances,firestairc found with dislodged metal nosings & metal pans 3rd sty to bulkhead rem:properly maintain interior stair forthwith

    Apr 15, 2010

    Resolve
  • Class - 1

    Failure to maintain interior bldg in code compliant manner!dislodged roof bulkhead wall(s) & flr @ various locations with cracks @ stair c @approx. 7'-0"@ ceiling public hall for stair c @ ceiling courtyard lev

    Apr 15, 2010

    Resolve
  • Class - 2

    Failure to maintain interior bldg in code compliant manner!defective counter balance @ window @ window room#300.rem:properly repair or replace window!

    Apr 15, 2010

    Resolve
  • Class - 2

    Failure to maintain interior bldg in code compliant manner!noted:cracked brick wall nw-section being loose above pipe 2 meter room with spalled mortar @ ceiling & cracked wall to southeast exit vestibule area,1

    Apr 15, 2010

    Resolve
  • Class - 2

    Failure to maintain interior bldg in code compliant manner!concealed waterleaks @ meter room ceiling cellar a mechanical duct classromm#305.rem:properly maintain (waterleaks)

    Apr 15, 2010

    Resolve
  • Class - 3

    Failure to maintain interior bldg in code compliant manner!noted:spalled plaster @ roof bulkhead a ceiling to stair a between 4th & 3rd flr,classroom#201.rem:properly maintain wall(s) & ceiling(s)where required

    Apr 15, 2010

    Resolve
  • Class - 2

    Failure to maintain interior bldg wall(s) &/or appurtenances.evidence of concealed waterleak @ ceiling & wall(s) girl's restroom mezzainine level stair c.rem:properly maintain wall(s) & ceiling girls restroom

    Apr 15, 2010

    Resolve
  • Class - 2

    Failure to maintain interior bldg wall(s) &/or appurtenances!evidence of concealed waterleaks @ foundation rubble wall,meter room,cellar,sterling side.rem:properly maintain rubble foundation wall with concealed

    Apr 15, 2010

    Resolve
  • Class - 2

    Failure to maintain exterior bldg wall(s) & or appurtenances!.cracked ornamental stones @ bldg wall(s0 various locations with deteriorated caulking!.rem:properly maintain exterior ornamental wall(s)firthwith!

    Apr 15, 2010

    Resolve
  • Class - 2

    Failure to maintain exterior bldg wall(s) &/or appurtenances!defectivestucco veneer @ door opening to pump rooms bulkhead leaving expose cornerbead!rem:properly maintain exterior stucco wall above roof

    Apr 15, 2010

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W8)
Year built
1908
Floors
3
Residential units
—
Building area
64,350 ft²
Lot area
22,480 ft²
Zoning
R6B
Community board
306
Council district
39
Block / lot
941 / 50
Assessed value
$4,331,250
Landmark / historic district
Park Slope Historic District Extension II

Questions about 48 Park Place

Who owns 48 Park Place?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 48 Park Place have violations?

NYC HPD has no housing violations on record for this property.

Is 48 Park Place rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 48 Park Place built?

City records list 1908 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.