Violations at 544 7 Avenue

Brooklyn, NY 11215 · BBL 3-00880-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

The newest 50 of 62 DOB violations. The city keeps the complete history.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2020

    Jun 20, 2021

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2013 inspection report

    Mar 3, 2015

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2013 inspection report

    Mar 3, 2015

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2013 inspection report

    Mar 3, 2015

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 26, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 4, 2010

    Dob violation - resolved
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 1, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 22, 2004

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Elevator elevatorrequired

    3p7770

    Jan 23, 2003

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 26, 2002

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Elevator elevatorrequired

    3p7770

    Mar 2, 2001

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Elevator elevatorrequired

    3p7770

    Jan 4, 2000

    Dob violation - resolved
  • Construction other optional

    C-construction other optional

    May 17, 1999

    Dob violation - dismissed
  • Construction other optional

    Hazardous

    May 10, 1999

    Dob violation - dismissed
  • Construction other optional

    Hazardous

    May 10, 1999

    Dob violation - active

ECB violations

The newest 50 of 156 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.noted:at basement gas meter rm b5 and electric meter rm b59 inadequate/missing firestopping throughout various areas.rem

    Jun 18, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at stair abetween 1st and basement behind metal staircase cracked/rotted.rem:repair and/or replace.

    Jun 18, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at basement exit 7 ceiling damage missing/exposed a hole without plaster/paint.rem:repair and/or replace.

    Jun 18, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 1st fl gym basement cafeteria emergency lights not working when tes

    Jun 18, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:1st fl exit e,d basement cafeteria doors in disrepair/racked when tested.rem:repair and/or replace.

    Jun 18, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.lack of emergency lighting for exits,exit discharges and public corridors per bc 1006.1;27-542.noted:at ground fl gym rm b107 basement auditorium /stage beh

    Jun 18, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at roof bulkhead water/damage/cracks with spalling plaster/paint/mortar throughout ceilings/walls areas.rem:repairs and/or replace.

    Jun 18, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at basement stair g,h,c,auditorium doors are in disrepair/racked when tested.remrepair and/or replace.

    Jun 18, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue ecb#35717578m failure to maintain building in code-compliant manner.noted:at facade windows/lintels rusted/corrodes throughout various areas.rem:maintain exterior building walls.

    Jun 18, 2026 · Penalty $6,250

    Active
  • Class - 2

    Reissue ecb#35717579y failure to maintain building in code-compliant manner.noted:at roof parapet/stone detoriating/cracked/missing sectionsthroughout various areas.rem:repair and/or replace.

    Jun 18, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue ecb#35717580l failure to maintain building in code compliant manner.noted:at exit 3/floor marble cracked/lifting creating trip/falling hazard.rem:repair and/or replace.

    Jun 18, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: the flagpole is non usable caused by broken parts/pulley. no flag is flying. additionally the trees at flagpole area need to be trimmed and cut back

    May 22, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Re-issue #35684838l. failure to maintain building in code-compliant manner. noted: at staircase a and b there are door frames broken on 1st and 3rd floor. the steel nosing also cracked, needs to be replaced. re

    May 22, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Re-issue #35684835x. failure to maintain building in code-compliant manner. noted: at exit #3 on the 1st floor @ 19th street, the marble is cracked and uneven surface is causing a trip hazard. remedy: repair/re

    May 22, 2025 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35684836h. failure to maintain building in code-compliant manner. noted: the copping stone at parapet and other decorative stone are cracked, broken, missing sections. remedy: repair/replace.

    May 22, 2025 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35684837j. failure to maintain building wall and/or appurtenances. noted: at exp #1 especially, and all over the building, the steel lintels @ windows are rusted, corroded and need to be replaced. rem

    May 22, 2025 · Penalty $6,250

    Active
  • Class - 2

    Reissue# failure to maintain building wall and/or appurtenances.at time of my inspection i observed at exposure#1 over the courtyard table window lintels rusting/corroded,missing mortar section throughout the b

    Sep 12, 2024 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35655582x failure to maintain building in code-compliant manner.at time of my inspection i observed at the exterior of exposure#1 facade zapping stone missing section throughout it cracked and crumble d

    Sep 12, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35663 failure to maintain building in code-compliant manner.attime of my inspection i observed at marble staircase by exit 1 floor by 19 street cracked at the top of the landing and sinking down causing

    Sep 12, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue 35655526j failure to maintain building in code compliant manner. marble staircase by exit 1 fl (by 19st) cracked @ top of landing and sinking down causing trip hazard. remedy: repair and/or replace

    Jun 13, 2023 · Penalty $1,562

    Active
  • Class - 2

    Re-issue 35655527l failure to maintain building in code compliant manner. self closing door near dance studio 103 on both ends of hallway, doors in disrepair not closing. remedy: repair and/or replace

    Jun 13, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. staircase b 3rd fl frame broken, staircase a ground level door broken frame and staircase rex steel cracked. remedy: repair and/or replace.

    Jun 13, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:observed duringinsp of 1fl boys bathrm partition in disrepair,doors not closing missing broken hardware.repair &or replace

    Jun 10, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:observed duringinsp of exterior of exp1 facade.capping stone missing secs thruout,itscracked&crumbling.decorative stone on facade cracked has multiple open

    Jun 10, 2022 · Penalty $625

    Active
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:observed duringinsp of roof level,roofing paper torn/open up,bubbling out&seams split.trim flashing missing thruout.repair &or replace

    Jun 10, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:observed duringinsp of roof level chimney,parapet walls&capping stone missing mortar thruout also staircases in brick parapet walls.repair &or replace

    Jun 10, 2022 · Penalty $625

    Active
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:observed duringinsp of 3fl (rm319) bathrm&bulkhead@stairg peeling/spalling plaster&damage to area.repair &or replace

    Jun 10, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:observed duringinsp of 3fl (rm319) bathrm water has penetrated into ceiling causing damage to ceiling&sec aprx8"x8" missing@roof level bulkhead stairg wate

    Jun 10, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:observed duringinsp of fireproof selfclosing doors near dance studio103 on both ends of hallway doors in disrepair not closing&missing secs repair &or repl

    Jun 10, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:observed duringinsp of marble staircase by exit3 1fl (by 19st) cracked@top landing&sinking down causing trip hazard.repair &or replace

    Jun 10, 2022 · Penalty $625

    Active
  • Class - 2

    Reissue35360358l failure to maintain bldg walls or appurtenances noted:observed during insp of exp1 over courtyd tables window lintels rusting/corroded,missing mortar secs thruout.maintain exterior bldg wall.

    Jun 10, 2022 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code manner illumination for exits exit discharges & public corridors per bc 1006.1;27-381 noted:at 1st floor gym 3 emergency lights above exit doors at auditorium all emergency

    Jun 10, 2022 · Penalty $625

    Resolve
  • Class - 1

    Sec. bc 3304.4.4 failure to provide 3'6" guardrail system or solid enclosure around open & accessible sides of excavation. at the time of myinspection of an active jobsite,i observed that there was excavated

    Nov 16, 2021

    Resolve
  • Class - 2

    Failure to designate and provide competent person for job site. at time of inspection at active job site excavation stages with concrete box pit installation request for designated competent person for construc

    Nov 16, 2021

    Resolve
  • Class - 2

    Failure to provide superintendent job site logs as required (construction0at time of inspection of active job site with 3 workers request for construction superintendent eneoent daily logs none was provided or

    Nov 16, 2021

    Resolve
  • Class - 2

    Exit door not self-closing.note at cellar level courtyard exit door not self closing when tested due to hardware.remedy:repair/replace door

    Oct 3, 2019 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.note:at cellar level directly above courtyard exit (19th street)there is a hole in the ceiling approximately 15"x15.remedy:repair and/or replace.

    Oct 3, 2019 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35260422z failure to maintain building in code compliant manner. noted: signs of water damage and water penetration at various locations throughout the cellar. rmdy: replace and/or replace.rmdy: maint

    Sep 26, 2018

    Resolve
  • Class - 2

    Reissue #35260423k failure to maintain building walls or appurtenances. noted: auditorium windows well wall by 19 street are in a state of disrepair with multiple crack and pcs of concrete missing. rmdy: maint

    Sep 26, 2018

    Resolve
  • Class - 2

    Reissue #35260424m failure to maintain building walls or appurtenancesnoed: windows lintel at exp 1 rooms 101,201,301,111,211,311,112,212,and 312 are rusty and in disrepair conditions. rmdy: repair and/or replc

    Sep 26, 2018

    Active
  • Class - 2

    Temporary construction equipment on site-expired permit. noted: at time of inspection sidewalk shed on site with expired permit. shed permit#302573604 expired on 3/17/18 no new permit. rmdy: renew permit.

    May 18, 2018 · Penalty $625

    Active
  • Class - 2

    Work does not conform to approved construction docs and /or approved amendments.premises under alt2 job#320704288loc folder. at time of inspection found (1)plan indicated boiler rm at cellar level.found no boil

    Jun 1, 2017 · Penalty $500

    Resolve
  • Class - 2

    Reissue#35101793j failure to maintain bldg walls or appurtenances. noted: windows lintel at exp#1 for room 101,201,301,111,211,311,112,212,312 are rusty & in a disrepair condition. remedy: comply w/summons. rep

    May 26, 2017

    Active
  • Class - 2

    Reissue#35214336p failure to maintain bldg walls or appurtenances. noted: auditorium windows well walls by 19 street are in a serious state of disrepair w/multiple cracks & concrete pieces missing. remedy: comp

    May 26, 2017

    Resolve
  • Class - 2

    Reissue#35214337r failure to maintain bldg in a code compliant manner.noted: signs of water damage & water penetration at various locations throughout the entire cellar such as: auditorium by 19 street wall,oil

    May 26, 2017

    Resolve
  • Class - 2

    Reissue#3510795n.failure to maintain building in code compliant manner.noted:water penetration in various rooms in basement such as auditorium fuel tank room gas meter water meter room and electric from foundat

    Oct 28, 2016

    Resolve
  • Class - 2

    Reissued #35101794l failure to maintain building wall(s)or appurtenances.noted:the window well is cracked at basement auditorium on 19th street side,window ,well exterior concrete walls cracked and spalling re

    Oct 28, 2016

    Resolve
  • Class - 2

    Failure to maintain bilding in code-compliant manner.use of prohibited door and hardware per bc1008.1.8;27-371(j):observed at roof #b61,b1(at boiler room)padlocks.remedy:provide legal hardware.

    Oct 27, 2016

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.lack of frequency lighting for exits,exit discharges and public corridors per bc100.6727-542;observed defective lights at library (2pcs)exit b inside corrid

    Oct 27, 2016

    Resolve
  • Class - 2

    Exit door not self closing.noted:exit c&d at first fl right side door delivery door @ cellar need to be repaired.remedy:repair/replace door.

    Oct 27, 2016

    Resolve