roofy

Violations at 435 39 Street

Brooklyn, NY 11232 · BBL 3-00705-0061 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

8 DOB violations, newest first.

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 16, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 12, 2017

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2011 inspection/test

    Oct 1, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 3, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 22, 2008

    Dob violation - resolved
  • Construction other optional

    Failure to safeguard public and property affected by construction oper ations noted: 8' high cmu walls built under permit #302295969 for alt1 extension jobsite fence is open at front and no fence at rear patio of adjoining days inn also inadequate fence at rear yard split unsafe walk planking inside of remedy: stop all work repair and complete cons

    Apr 9, 2008

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed

ECB violations

20 ECB violations, newest first.

  • Class - 1

    Atoi observed lack of sprinkler coverage on all floors in the hallway of the elevator. contrary to bc 903.3.3 obstructed locations in automatic fire sprinkler systems. it mandates that sprinklers be positioned

    Sep 11, 2026 · Penalty $2,500

    Resolve
  • Class - 2

    Observed on the first floor in the hot water heater room exhausted discharge vent is not sealed and using incorrect fittings to connect the vent which is contrary to code section fgc 503.3, repair and/or replac

    Sep 17, 2025

    Resolve
  • Class - 2

    Class 2 items: pit light inoperative, repair. provide updated maintenance log

    Sep 17, 2025 · Penalty $655

    Resolve
  • Class - 1

    I observed the installation of wiring under the stairs, in the water heater room and the main electrical room, to install light fixtures, receptacle outlets and power to a fixed a.c. unit. this work was complet

    Oct 15, 2024 · Penalty $800

    Resolve
  • Class - 1

    I observed in the halls throughout the building the failure to install tamper resistant outlets as required for areas accessible to children as per ll 39/2015. this is an immediate shock hazard. photos taken.;

    Oct 15, 2024 · Penalty $400

    Resolve
  • Class - 1

    I observed in the water heater room the flexible cords supplying power to the water heaters not terminated with the energized conductors exposed. this is an immediate shock hazard. photos taken, comply with ec;

    Oct 15, 2024 · Penalty $400

    Resolve
  • Class - 1

    I observed in the water heater room, in a storage room under the stairs, and in the main electric (for the a.c), the unpermitted use of flexible cords as permanent wiring, also noted the conductors were exposed

    Oct 15, 2024 · Penalty $1,200

    Resolve
  • Class - 1

    I observed in the main electrical room the installation of the disconnect switch for the emergency power as per bc 2702.1.7.1 all components of the emergency systems shall not be installed in the main electrica

    Oct 15, 2024 · Penalty $625

    Resolve
  • Class - 1

    I noted the facilitation of the respondent to have unlicensed electrical work completed, in the water heater room, the main electrical room and under the stairs as no licensed contractor is on file in dob recor

    Oct 15, 2024 · Penalty $4,800

    Resolve
  • Class - 1

    I observed in the main electrical room the installation of data equipment that completely blocks the incoming electrical service and allows no access for normal or emergency repairs/maintenance. this an immedia

    Oct 15, 2024 · Penalty $250

    Resolve
  • Class - 2

    I observed defective ground fault circuit interrupter outlets on the roof (behind the door) and the food service area. all electrical devices in use shall be maintained in proper working order. photos taken., i

    Oct 15, 2024 · Penalty $1,200

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed excessive hole penetration in boiler room and water meter rooms. potenti

    Oct 15, 2024 · Penalty $2,500

    Resolve
  • Class - 1

    Excessive storage placed underneath staircase leading basement level. unsafe storage and combustible materials( torch, flammable cans , cleaning products, paint and boxes underneath staircase can lead to potent

    Oct 15, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Observed 2 painted sprinkler heads in the water heater room located on the second floor. as per 102.3 of the plumbing code maintenance. installations, both existing and new, and parts thereof shall be maintaine

    Oct 15, 2024

    Resolve
  • Class - 2

    Work w/o a permit. observed 2 illuminated accessory business signs. 1)front yard parking lot approx 15feet above ground illuminated box sign reading"days inn"& 2)above top floor attached to center of exp#1

    Nov 22, 2016

    Resolve
  • Hazardous

    Failure to safeguard public & property affected by construction operations. noted: partial cmu walls constructed under permit# 302295969 for alt 1 extension. jobsite fence is open at front and no fence at rear

    Apr 9, 2008 · Penalty $1,000

    Resolve
  • Hazardous

    Failed to post required contractor sign. noted: partial cmu walls have been built under permit # 302295969 for alt 1 extension. required contractor's sign is not posted on job fence.remedy:stop all work. post

    Apr 9, 2008 · Penalty $250

    Resolve
  • Hazardous

    Failure to post contractor's sign. at time of inspection demo was in progress and no contractor's sign posted. remedy: post contractor's sign.

    Jun 9, 2003 · Penalty $500

    Resolve
  • Hazardous

    Failure to safeguard public and property. at time of inspection demo was in process and demo site is not properly encloused. rear of demolition site is not fenced and accessible to adjecent property. remedy:

    Jun 9, 2003 · Penalty $1,500

    Resolve
  • Hazardous

    Mech. demolition without permit. at time of inspection house is under demo. excavator is being used to demolish house. remedy: stop mech. demo, remove excavator from side, obtain necessary permit.

    Jun 9, 2003 · Penalty $2,000

    Resolve