roofy

817 4 Avenue

Brooklyn, NY 11232BBL 3-00669-0001Map

Owner of record: NYC Department Of Education

817 4 Avenue is a school building built in 1920 in Brooklyn, 11232. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
27
ECB violations
71
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 27

  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2020)

    Oct 10, 2021

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2019

    Jun 29, 2020

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
Show 17 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Construction other optional

    Hazardous

    May 17, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - dismissed

ECB violations · 71

  • Class - 2

    Exit door not self closing noted:at 1st fl exit 6 door indisrepair/notclosing when tested.rem:repair/replace door.

    Jun 12, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:at entire basement installed/used kick door stopped throughout various areas.rem:prov

    Jun 12, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at basement exit 9,2,5 doors in disrepair racked when tested.rem:repair and/or replace.

    Jun 12, 2026 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 1st fl/exit 6/walkway observed egress by table,chairs etc.rem:comply with code.

    Jun 12, 2026 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-371.noted:at 1st fl auditorium emergency lights not working when tested througho

    Jun 12, 2026 · Penalty $1,250

    Resolve
  • Class - 2

    Reissued #35561236y failure to maintain building in code compliant manner. noted: at 1st floor cafeteria staircase doors are not self closing properly due to defective hardware. remedy: repair/replace door

    Jun 3, 2022 · Penalty $1,562

    Resolve
  • Class - 1

    Bc 3303.4.1.1 slipping and tripping hazard at the time of inspection of an active jobsite observed at exposure#1 sidewalk was badly broken and cracked failure to maintain sidewalk created in safe condition for

    Aug 19, 2021 · Penalty $2,500

    Resolve
  • Class - 1

    Failure to maintain/display on site document required by bc chapter 33 note at the time of my inspection of inspection of an active upon request to sec the pre shift meeting and revieiwng it observed the last

    Jun 30, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Inadequate construction superintendnet logs noted at the time of my inspection of an active jobsite upon request to see the construction superintendent logs it was provided by the competent person on site

    Jun 30, 2021 · Penalty $2,500

    Resolve
  • Class - 2

    Jobsite fence not constructed or not maintain pursuant to subsection noted at the time of my nspection fo an active jobsite observed jobsite construction fence at exp # has loose plywood splinter all over notth

    Jun 30, 2021

    Resolve
Show 40 more ↓
  • Class - 2

    Reissue#35490776j failure to maintain in code compliant manner at timeof inspection noted:cafeteria staircase 2 floor doors not self closingwhen tested.

    May 27, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35442605z(7/18/19)exit door not self closing: @ cafeteria exit9 interior & exterior door auditorium main entrances on both sides,stair e&d & 1st fl(rm 105). remedy: repair/replace door.

    May 21, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35442604r(7/18/19)failure to maintain bldg in code compliant manner @ roof level facing 30th street mechanical vent(bathroom)is deteriorated. remedy: repair & or replace.

    May 21, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35442601l(7/18/19)failure to maintain bldg in code compliant manner @ cafeteria stairway e,o. not open properly. remedy: repair &/or repairs.

    May 21, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Sec. 3301.9.1 project information panel. at time of inspection of a jobsite i observed that the information panel was not on the jobsite fence. no job information was available at time of inspection as well as

    Feb 24, 2020

    Resolve
  • Class - 2

    Sec. 28-301.1 unlawful placement of furnishings,decorations or other objects at ecxits that obstruct access to egress from or visibility thereof per fdny 2008 code;fc 1027.4. noted: at cafeteria exit 9 passagew

    Jul 18, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at the roof level,30th street side,the mechanical metal vent bathroom is completlyrotted. also at the roof level,the water tank storage room is missing

    Jul 18, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner,use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: kick down door holders installed throughout the entire bldg in various areas. remedy: pro

    Jul 18, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at cafeteriastairway e & o,doors are not working properly,not an exit. remedy: repair &/or replace.

    Jul 18, 2019

    Resolve
  • Class - 2

    Exit door not self closing. noted: at the auditorium main entrance double door on the left & a single door on the right sifde,stair e & d byroom 105,cafeteria exit 9 interior & exterior door,smoke doors at exit

    Jul 18, 2019

    Resolve
  • Class - 2

    Reissue #35267914r date of issue 05-31-2017.failure to maintain building walls or appurtenances(rear east)125 ft long cracked and missing masonry-exterior(north east corner)spalling and loose brick main entranc

    May 7, 2018

    Resolve
  • Class - 2

    Bc28-301.1.reissue #35267915z date of issue 05-31-2017.unlawful placement of furnishing decorations on other objects at exits that obstruct access to egress from or visibility there of per fdny 2008 code fc1027

    May 7, 2018

    Resolve
  • Class - 2

    Exit door not self closing in 2nd floor stair d outside two doors are not self case.2nd floor staricase 2 doors at first floor staircase "c"two doors are ton self closing.first floor exit 7 two doors are not s

    May 7, 2018

    Resolve
  • Class - 2

    Sec. 28-301.1 unlawful placement of furnshings,decorations or other obsects at exits that obstruct access to egress from or visability therof per fdny 2008 fc 1027.4 blockage of exits at following locations 1st

    May 31, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg walls or appurtenances-retaining wall(rear east)125ft long-cracked & missing masonry-exterior(north/east corner)spalling & loose brick-main entrance delamanating/spalling stucco over

    May 31, 2017

    Resolve
  • Class - 2

    Failure to provide required corridor width & storage of combustibles in the corridors.note:on all fls the corridors are obstructed by chairs,desks,cabinets,bookshelves,& other school equipment.rem:comply w/ the

    Jun 9, 2015

    Resolve
  • Class - 2

    Reissue #35095085k.failure to maintain bldg in code-compliant manner.note:evidence of water penetrating the walls & ceiling in rooms 304,202 & 201,causing the plaster to loose/spalling.rem:comply the notice of

    Jun 9, 2015

    Resolve
  • Class - 3

    Reissue #35095086m.failure to maintain bldg wall(s)or appurtenances.note:water penetration from the roof into room 304 & from the defective mortar joints on the brick facade into rooms 201 & 202.rem:comply w/ t

    Jun 9, 2015

    Resolve
  • Class - 3

    Water penetration. water penetrating into classrooms 201,202 & 304 from facade (rms 201,202) & roof (rm 304) on walls. remedy: repair water damaged areas.

    Jun 27, 2014

    Resolve
  • Class - 3

    Water penetration from roof. water penetrating from roof into room 304. remedy: repair section of roof.

    Jun 27, 2014

    Resolve
  • Class - 2

    Sec. 28-301.1 reissue 34980726r defective doors left of main entrance cafeteria entrance door,staircase b 1 floor. remedy: repair/replace doors.

    May 7, 2013

    Resolve
  • Class - 2

    Reissue 34980725p illegal hardware on 95% classroom doors,kick stops in place holding doors open preventing fire rating corridor. remedy: remove hardware.

    May 7, 2013

    Resolve
  • Class - 2

    Doors at stair b&c and door to cafeteria at left of main entrance are racked preventing them from closing properly rem: repair or replace doors

    Jun 1, 2012

    Resolve
  • Class - 2

    Loose and missing brick adjacent to 2nd floor playroof door an 29st side rem: repair replace brick

    Jun 1, 2012

    Resolve
  • Class - 2

    Opening in fence and loose section of fence to enclosure of 2nd floor roof play area above playyard rem: repair or replace replace fence

    Jun 1, 2012

    Resolve
  • Class - 2

    Kick down door stops on door at various locations throughout bldg rem: remove door steps

    Jun 1, 2012

    Resolve
  • Class - 2

    Exit 3 in cafeteria is partially obstructed by storage of garbage cans rem: remove all obstructions

    Jun 1, 2012

    Resolve
  • Class - 2

    27-348(c)(4) excessive combustibles in corridors paper are work hanging from walls and across ceilings in various locations throughout corridors rem: remove excessive combustible artwork

    Jun 1, 2012

    Resolve
  • Class - 3

    Plaster damaged walls in rooms 201 300 & 302 caused by prior water penetration rem: repair damaged walls

    Jun 1, 2012

    Resolve
  • Class - 2

    Sec. 27-371(b). failure to provide the required vision panel at classroom door. no vision panel at classroom doors throughout various areas on all flrs 1st to 3rd flrs. remedy:provide the proper fire rated door

    Mar 2, 2011

    Resolve
  • Class - 1

    Reissue: 34846367r. at the 1st flr auditorium exit doors have been obstructed due to conversion of auditorium, which is now a teachers lounge/lunch rm as well as office spaces. cubicles erected w/desks, chairs

    Mar 2, 2011

    Resolve
  • Class - 2

    Reissue: 34846366p. at 1st flr auditorium has been converted into a multi purpose rm currently being used as a teachers lounge/lunch rm & asan office space app 301389147.remedy: restore to legal prior condition

    Mar 2, 2011

    Resolve
  • Class - 1

    Reissue 34770489r.exit door total obstruction on 1st fl auditorium both sides.obstructed w/cubicles.rem:remove obstruction in front of exit doors.

    May 19, 2010 · Penalty $6,000

    Resolve
  • Class - 2

    Reissue 34770488p place of assembly contrary to approved const documents.noted on 1 fl auditorium all fixed seating removed & installation cubicles along sides of auditorium obstructing exit doors,appl 3013891

    May 19, 2010

    Resolve
  • Class - 1

    Haz. exit door total obstruction on first floor,auditorium 2 side doors totally obstructed w/cubical partitions.remedy:remove all obstructions.

    Apr 1, 2009

    Resolve
  • Class - 1

    -haz-.place of assembly contrary to approved construction documents.noted:on 1fl auditorium all fixed seating removed & installed cubicle along sides of auditorium obstructing exit doors job #301389147 issued

    Apr 1, 2009

    Resolve
  • Class - 2

    Defective doors all exit vestibule doors on 1fl also,exit door to ramp& main entry doors entire frame loose,doors hitting each other & not closing properly.remedy:repair doors.

    Apr 1, 2009

    Resolve
  • Class - 2

    Severe rotting of lintels & slight bulging & cracking of bricks aroundlintel area @ 2fl outside play ground.remedy:repair facade forthwith

    Apr 1, 2009

    Resolve
  • Class - 3

    Re:34698023l.plaster damage in rooms 201,300,301,100 & kitchen storageroom in basement.remedy:repair walls & ceiling.

    Apr 1, 2009

    Resolve
  • Class - 3

    Re:34698021h.water penetration through exterior wall at northwest corridor. remedy:seal all penetration.

    Apr 1, 2009

    Resolve

Complaints

  • Heating

    Heat related

    Nov 4, 2006 · Apt 2

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1920
Floors
4
Residential units
—
Building area
57,100 ft²
Lot area
40,066 ft²
Zoning
R6B
Community board
307
Council district
38
Block / lot
669 / 1
Assessed value
$4,155,750
Landmark / historic district
No

Questions about 817 4 Avenue

Who owns 817 4 Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 817 4 Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 817 4 Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 817 4 Avenue built?

City records list 1920 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.