roofy

822 4 Avenue

Brooklyn, NY 11232BBL 3-00664-0037Map

Owner of record: Signature Management Enterprises LLC

822 4 Avenue is a hotel built in 2019 in Brooklyn, 11232. The owner of record is Signature Management Enterprises LLC. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
7
ECB violations
31
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 7

  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Feb 3, 2021

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 2, 2020

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 2, 2020

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Nov 27, 2019

    Dob violation - dismissed
  • Construction other optional

    Foundation not complete pursuant to nb appl#321190000 before effective date of zoning amendment 12/20/18/percentage of foundation complete 25%/stop all work immediately

    Apr 18, 2019

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    May 6, 2002

    Vw*-violation - work w/o permit dismissed
  • Construction other optional

    . having installed a sign without a permit 2. having signage (double faced) projecting more than 18inch across the street line remedy: illegal work signage

    May 6, 2002

    Vw*-violation - work w/o permit dismissed

ECB violations · 31

  • Class - 2

    The use of emergency vent device shall be prohibited as per mc-1305.8.1. missing required documents as per mc-106.2; mc-misc, comply with notice of violation

    Oct 29, 2021

    Resolve
  • Class - 1

    Unlawfully continued work while on notice of a stop work order at time of inspection on an active 8 story nb construction site notice the removal and completion of all exterior work all white the contractor

    Nov 20, 2020 · Penalty $5,000

    Resolve
  • Class - 1

    Bc-3314.4.1.2 failure to provide supervision of supported scaffold installation and removal. at time of inspection of the removal of supported scaffold at exposures 1/2 w/ 8 workers. upon request for the design

    Sep 28, 2020 · Penalty $2,500

    Resolve
  • Class - 1

    Permit holder failed to ensure workers receive site safety orientation. at time of inspection of an 8 story new building of an active job site w/ 30 workers of various trades. upon request for site safety orien

    Sep 28, 2020 · Penalty $1,250

    Resolve
  • Class - 1

    Unlawfully continued work while on notice of a stop work order. note at the time of my inspection of a 8 sty new bldg construction work in progress. i observed work being done on supported scaffold(stucco opear

    May 19, 2020

    Resolve
  • Class - 1

    Work does not conform to approved construction documents &/or approvedamendments. note: at the time of inspection of a 8 sty new bldg construction in progress i observed supported pipe scaffold on top of needle

    May 19, 2020 · Penalty $625

    Resolve
  • Class - 1

    Sec. 3313.1 at the time of my inspection of a 8 sty new bldg construction in progress,i observed workers on roof level 1)i observed workers mishanding the containers w/contained gas carrying 2 at a time creates

    May 19, 2020

    Resolve
  • Class - 2

    Sec. 3303.8 standpipe not in a state of readiness. at time of inspection on an active jobsite of a 8 sty bldg(currently) at roof level obserrved that standpipe was not paint red to indicate that is in a state

    May 12, 2020

    Resolve
  • Class - 1

    Sec. 3303.12 hoist not in a state of readiness. at time of inspection on an active jobsite of an 8 sty bldg currently at roof level,observedthat hoist/elevator was not active &/or in a state of readiness. failu

    May 12, 2020 · Penalty $2,530

    Resolve
  • Class - 1

    Sec. 3314.4.8 failure to maintain scaffold as per code subsection. at time of inspection on an active jobsite,observed pipe scaffold erected at all exposures approx 100 feet in height. work in progress w/approx

    May 12, 2020 · Penalty $2,530

    Resolve
Show 21 more ↓
  • Class - 1

    Owner (failed) to ensue each construction or demolition worker successfully completed th erequired trianing under bc3321.1 observed worker recinos perez aron aurelio id #377436309 at the buidling site for which

    Dec 28, 2019

    Resolve
  • Class - 1

    Permit holder failed to ensure eahc construction or demolition worker successfully completed the required training under bc 3321.1 observed at a jobsite worker recinos pegeg aron aurelio id#37743639 has no osh

    Dec 28, 2019

    Resolve
  • Class - 1

    Permit holder (failure) to produce for inspection teh daily log that is required by bc 3321.1 item3 at time of inspection on an active jobsite i asked the superintendent for his log book at which point he state

    Dec 28, 2019 · Penalty $6,250

    Resolve
  • Class - 2

    After house work without permit out of permit at time of inspection observed at a active jobsite workers erecting scaffold.working open elevator shaft at 8 story without after hour owkr after without a variance

    Dec 28, 2019 · Penalty $625

    Resolve
  • Class - 1

    Failure to safeguard all persons and property affected by construction operations at time of inspection observed workers worker at the jobsite in an open levator shaf at 8th story frop without and full protecti

    Dec 28, 2019 · Penalty $12,500

    Resolve
  • Class - 2

    Bc 3301.7 failure to provide p.e approved drawing and means and method. as noted:at time of my inspection at an active job site observed on 4th,5th fl and bulkhead expose rebar and cut out in shear wall no mean

    Dec 10, 2019 · Penalty $625

    Resolve
  • Class - 1

    Bc1905.6.3.2.failure to remove strength test cylinder stored for a period up to 48 hours. as noted:at time of inspection on an active construciton site building up to 7 stories, strength test cylinders was mold

    Aug 27, 2019

    Resolve
  • Class - 1

    Working against stop order. at apprx 7am observed formwork being conducted on 8th floor. multiple workers on working deck. on 7/11 a stop order was issued stating no work above 2nd flr, no work loft from lead

    Jul 12, 2019

    Resolve
  • Class - 1

    Sec. 3303.9 inadequate egress. permanent stairs have temporary shoringin place from 4th fl to 5th fl shoring for form work of stairs leading to 6th. shoring is in center of stairs & does not provide 3ft of path

    Jul 11, 2019 · Penalty $2,500

    Resolve
  • Class - 1

    Sec. 3309.10 roof protection. at time of inspection observed nb @ 6th sty(working deck)concrete work being conducted @ exp#4. upon further inspection observed no roof protection on adj bldg exp#4. tarp & debris

    Jul 11, 2019 · Penalty $625

    Resolve
  • Class - 1

    Guardrail/netting. at time of inspection observed 8 sty new @ 6th fl,work being conducted on 6th guardrail system is airline cable,inadequate missing netting reshores being used as posts,& netting not secure.

    Jul 11, 2019

    Resolve
  • Class - 1

    Safeguard. no ohp or central access provided to prevent workers from accessing areas were overhead hazards exist. guardrail systems inadequate & do not meet code requirements guardrails missing toeboards,nettin

    Jul 11, 2019

    Resolve
  • Class - 1

    Sec. 3301.6 design drawings. temporary platforms for temp ladders installed on 4th leading to 6th fl. no design drawings for platform embedded straps on all floors do not have drawings from engineer. only docum

    Jul 11, 2019 · Penalty $650

    Resolve
  • Class - 1

    3308.1 vertical safety netting.at time of inspection,observed an 8 storied nb,@6th floor working deck already stripped.according to the azimuth of elevation & curb level is at 23ft.elevation which would leave f

    Jul 11, 2019 · Penalty $625

    Resolve
  • Class - 1

    Failure to comply w/an order to stop work by the commissioner:full stop work order issued on 4/18/19 was in effect @time of insp,complaint #3700382.the violation issued on 4/18/19 stated 25% of foundation was c

    Jun 20, 2019

    Resolve
  • Class - 1

    Failure to safeguard/failure to maintain safety operations.(uncapped rebar). at time of inspection i observed proposed 8 sty new bldg currently at street level w/ongoing work present. i also observe no rebar

    Apr 25, 2019 · Penalty $625

    Resolve
  • Class - 2

    Job site fence not in place,maintained or inadequate. at time of inspection i observed proposed 8 sty bldg currently at street level w/work currently present. i also observed contractor failed to install all

    Apr 25, 2019

    Resolve
  • Class - 2

    Condition of fence(protruding screws & graffiti)at time of inspection i observed proposed 8 sty new bldg currently at the street level w/on going work present. i also observed job site fence has protruding nail

    Apr 25, 2019

    Resolve
  • Class - 1

    Housekeeping(trip hazards). at time of inspection i observed proposed 8 sty new bldg currently at the street level,w/ongoing work currently present. i also observe excessive debris & piles of materials througho

    Apr 25, 2019 · Penalty $625

    Resolve
  • Class - 1

    Failure to provide protection at side of excavation as noted, at time of my inspection on an active construction site observed one worker leave the site also the gate on exposure #2 open and unsecure, the site

    Jan 11, 2019 · Penalty $5,000

    Resolve
  • Class - 2

    Work w/o a permit.noted: at demolition site signed off 9-17-13 jobsitefence is still in place fence not painted hunter green,and is missing information panel as required in ll47/13. rmdy:obtain required permit

    Oct 31, 2013

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Nov 19, 2017 · Apt BLDG

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Hotel (H2)
Year built
2019
Floors
8
Residential units
—
Building area
41,245 ft²
Lot area
9,015 ft²
Zoning
M1-2D
Community board
307
Council district
38
Block / lot
664 / 37
Assessed value
$5,566,050
Landmark / historic district
No

HPD registration #390098, last renewed Aug 25, 2025.

Questions about 822 4 Avenue

Who owns 822 4 Avenue?

The owner of record in NYC Department of City Planning PLUTO data is Signature Management Enterprises LLC.

Does 822 4 Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 822 4 Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 822 4 Avenue built?

City records list 2019 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.