Violations at 261 Court Street
Brooklyn, NY 11201 · BBL 3-00402-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
The newest 50 of 52 DOB violations. The city keeps the complete history.
- Elevator elevatorrequired
E-elevator elevatorrequired
Apr 24, 2013
Dob violation - active - Elevator elevatorrequired
Removed
Feb 23, 2009
Vw*-violation - work w/o permit dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 30, 2008
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 1, 2007
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 2, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 8, 2006
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 4, 2005
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Nov 19, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 21, 2004
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 10, 2004
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 27, 2003
Vw*-violation - work w/o permit dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 19, 2002
Dob violation - dismissed - Elevator elevatorrequired
3s5450
Aug 15, 2001
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 10, 2000
Dob violation - dismissed - Construction other optional
C-construction other optional
Apr 29, 1999
Dob violation - dismissed - Construction other optional
C-construction other optional
Apr 29, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 20, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 17, 1995
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
May 31, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Elevator elevatoroptional
1
Jun 28, 1993
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 26, 1993
Vp*-violation unserved ecb- dismissed - Elevator elevatoroptional
1
Apr 7, 1992
Dob violation - dismissed
ECB violations
The newest 50 of 120 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner. at the time of inspection, the following classroom doors 2nd means of egress were blocked:-b26, b28, b30, b34, b31, b33-classoom light had broken mirrors.
Apr 7, 2026 · Penalty $1,250
Active - Class - 2
Re-issue 35693212y. at the time of inspection, the following emergencylights were inoperable:-emergency light at exit #8 vestibule; emergency light 1-4, 1-5, 2 emergency lights in auditorium, box #1-15, 1-21, 1
Apr 7, 2026 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). at the time of inspection, the following doors had turn knob handle:-321, 212, 167. reme
Apr 7, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. at the time of inspection, the following doors were not self-closing properly:-325, 338 staircase "b' on 3rd floor, staircase "c" on 2nd floor, 163b, 161a,
Apr 7, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. observed several emergency lights scatter through the school that were
Apr 23, 2025 · Penalty $1,250
Resolve - Class - 2
Re-issue #35561118n(5/4/21)exit door not self closing exit 2 at 1st floor exit 3 at 2nd floor exit 5 & 6 at 3rd floor not closing properly.remedy:repair/replace doors
Apr 26, 2022 · Penalty $1,562
Resolve - Class - 2
Re-issue #35561119p failure to maintain building in code compliant manner-illumination of exits exit discharges and public corridors per bc 1006.1;27-381 at first floor several locations exit illuminated lights
Apr 26, 2022 · Penalty $1,562
Resolve - Class - 1
At time of inspection, drains obstructed by yard paving material installed at schoolyard at exposure 2 of premises, causing water runoff to commercial space at first floor of adjacent occupied premises 206 smit
Nov 22, 2021 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:observed existing emergency lights with battery back-up power throughout 1st
May 4, 2021 · Penalty $625
Resolve - Class - 2
Reissued #35423115m.exit door not self-closing.noted:observed stair fireproof self closing doors at 3rd floor exit 5&6,2nd floor exit 2,5 and 6, first floor exit 2 are racked and not fully closing properly.reme
May 4, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381. noted:in the auditorium 4 of the emergency lights were not working when tes
May 19, 2020 · Penalty $625
Resolve - Class - 1
Bc3307.2.4/pswo-required means of egress.at time of inspection at a 4 story building under construction i observed excavation work at expo 3with out proper means of egress not fully complete stairs dipper than
Dec 11, 2019 · Penalty $12,500
Active - Class - 2
Bc3309.4/failure to perform inspection and document condition of existing building.adjoining property-excavation.at time of inspection at a 4 story building under construction i observed damaged adjoining prope
Dec 11, 2019 · Penalty $6,250
Active - Class - 1
Work does not conform to approved plans.at time of inspection at a 4sty building under construction i observed at expo 3 structural foundation work upon request for approved detailed drawing for all the work th
Dec 11, 2019 · Penalty $12,500
Active - Class - 2
Failure to maintain building in code-compliant manner:no fire stoppingper bc 712.3;27-345. noted:at the cellar level,smoke wall by electrical room,above exit doors,penetration in wall from plumbing pipes,#6 no
May 6, 2019
Resolve - Class - 2
28-301.1 unlawful display of artwork in corridors greater than 20% perfdny 2008 code;fc 803.3.2. noted:at the basement level,decorations hanging from the ceiling throughout the entire hallway. remedy:comply w/
May 6, 2019
Resolve - Class - 2
Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381. noted:at the gymnasium(all),cafeteria,main entrance and rear left,the kitch
May 6, 2019
Resolve - Class - 2
Exit door not self closing. noted: at the 1st floor, exit 2, 2nd floor, exit 3, and 3rd floor, exit 5 and 6, not working properly due to defective hardware. remedy: repair/replace door
May 6, 2019
Resolve - Class - 2
Failure to maintain building code-compliant manner. noted: at the mainentrance, by the stairs (both), and the doors by room 62b, not closingproperly due to defective hardware. remedy: repair and/or replace
May 6, 2019
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.note:at cellar level in cafeteria on wall in front of kitchen electrical outlet broken and hanging off wall wires exposed.rem:repair and or replace
Mar 21, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.note:at exit 7 and 2the middle of the door buck is missing on 1st fl. rem:repair and or replace
Mar 21, 2018
Resolve - Class - 2
Bc 28-301.1:unlawful placemeent of furnishings,decorations or other objects at exits that obstruct access to egress from or visibility thereof per fdny 2008 cide;fc 1027.4.note:at the following locations the ex
Mar 21, 2018
Resolve - Class - 2
Unlawful display of artwork in corridors greater than 20% per fdny 2008 code fc 803.3.2.note:on corridors walls on 1st and 2nd fl aryeork displayed also at cellar level on walls and from ceilings.rem:comply w/n
Mar 21, 2018
Resolve - Class - 2
Exit door not self-closing.note:at following locations near rm 221,cafeteria exit f door not self closing at rm 221 closure is broken and cafeteria exit f door drags on floor.rem.repair and or replace
Mar 21, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant mannet.note at rm 131 roof leaks over blackboards.rem:repair and or replace
Mar 21, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.note:at roof level roof fan vent covers off and loose(2)fans on upper roof covers are not screwed on and were off brackets.rem:repair and replace
Mar 21, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.note:at main entrance way entrance way left hand side of stairs handrail is missing from wall.rem:repair and replace.
Mar 21, 2018
Resolve - Class - 2
Re issued-35253407p.failure to maintain bldg in code compliant manner;illumination for exits,exit discharges and public corridors per bc1006.1;27-381.note:at gym and cafeteria emergency lights not operational
Mar 21, 2018
Resolve - Class - 1
Work no permit- observed in gas meter cellar. room- house gas meter piping, fitting, being disassembled & being tested for house leaks by contractor. photo provided. public school is 293. rem: obtain a permit.
Apr 27, 2017
Resolve - Class - 1
Work no permit-observed at is293 school-plumbers of above company-disconnected gas house piping meter,piping,fittings & testing for house leaks-no emergency work notification or dob permit on file at time of in
Apr 27, 2017
Resolve - Class - 2
Sec: 28-303.1. unlawful placement of furnishing, decorative etc @ exits that obstruct access to egress from or visibility there of per fdny 2008 code, fc 1027.4. noted: both exits/door @ rear of auditorium/back
Apr 25, 2017
Resolve - Class - 2
Failure to maintain bldg in code complaint manner: no fire stopping per bc 712.3: 27-345. noted: missing fire stopping in wall above entry door to electric meter room. metal conduits traverse wall, leaving hole
Apr 25, 2017
Resolve - Class - 2
Exit door not self closing noted: exit door(s)(exit 5) on third floor opposite room 318 not properly closing du to defective door closer arm.also,cafeteria entrance door next to room b 145 not properly closing.
Apr 25, 2017
Resolve - Class - 2
Reissue 35129105l failure to maintain bldg in code compliant manner lack of emergency lighting for eits, exit discharge and public corridors per bc 1006.1; 27-542.emergency lights in the auditorium 9 out, gym
Oct 9, 2016
Resolve - Class - 3
Reissue 35102050n work w/o permit. full height partition was erected w/o a permit, full height partitition was erected in room 207 to create 2 separate rooms. rmdy: obtain permit or restore premises to prior le
Oct 4, 2016
Resolve - Class - 2
Combustible material in the stairway.note: excessive amount of paper artwork,posters and decorations on the walls in stairway #4/#6 at all floors. rmdy: comply w/nov.
May 11, 2015
Resolve - Class - 3
Reissure #35018123n. failure to maintain building wall(s) or appurtenances note: defective roof flashing on the parapet wall at east towardsthe playground. apprx 3'. rmdy: comply w/nov.
May 11, 2015
Resolve - Class - 2
Failure to maintain building in code compliant manner. note on the 1stflr corridor adjacent to room 150, the metal roll down gate is not secure in the open position. rmdy: comply w/nov.
May 11, 2015
Resolve - Class - 2
Failure to maintain emergency lighting. noted:emergency lights in the auditorium (10) gymnasium (2) and basement corridor (1) adjacent room b12 are inoperative. rmdy: comply w/nov.
May 11, 2015
Resolve - Class - 2
Reissure 35018118z. failure to maintain bldg wall(s) or appurtenances.note: masonry facade at various locations at all four exposures have missing mortar on the bricks,spalling concrete facade, and lintels hav
May 11, 2015
Resolve - Class - 2
Use of prohibited door hardware.use of door steps on the follwing doors in 115,68,201,202,205,211,225 & 311.remove door stops.
Jul 16, 2014
Resolve - Class - 3
Reissue 34981339l work w/o a permit.erected full height partition wallin rm 207 to create 2 seperate rooms.rem:obtain permit.
Jul 16, 2014
Resolve - Class - 2
Reissue 35018119k vision panels use of prohibited plexiglass throughout 3rd fl & room 219.rem:provide required glass panels.
Jul 16, 2014
Resolve - Class - 2
Reissue 35018121j exit doors not self closing.either door closure not working properly,door racked or doors stick making them difficult to open.1st fl exit #2,door #7 2nd fl,ext dor #8,exit #3 or 2nd fl.stair"d
Jul 16, 2014
Resolve - Class - 2
Failed to obtain a temporary construction permit prior to installationof sidewalk shed.pictures filed. rmdy: obtain temporary const permit.
Dec 6, 2013 · Penalty $1,250
Resolve - Class - 1
Defective/spalling concrete ceiling at 3rd fl stairway marked "exit 5 & 6". there is severe spalling of concrete ceiling in numerous areas over the stairs. the areas are in danger of being displaced & falling.
May 9, 2013
Resolve - Class - 2
Defective roof flashing at east bulkhead,bent & loose metal flasing oneast side toward playground. remedy: repair metal flashing.
May 9, 2013
Resolve - Class - 2
Sec. 712.3;27-345 missing fire stopping at cellar electric room,missing fire stop over entry door w/numerous conduits installed. remedy: provide/maintain fire stopping.
May 9, 2013
Resolve - Class - 2
Door not self closing at 3rd fl stairway marked "exit 4" has broken door closer. remedy: replace door closer.
May 9, 2013
Resolve - Class - 2
Reissue #34926551r defective masonry lintels at baltic street approx 100' of steel lintel is spalling,scaling & seperating. remedy: repair exterior steel lintels.
May 9, 2013
Resolve