Violations at 413 Henry Street
Brooklyn, NY 11201 · BBL 3-00311-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
28 DOB violations, newest first.
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Construction other optional
C-construction other optional
Apr 29, 1999
Dob violation - dismissed - Construction other optional
C-construction other optional
Apr 29, 1999
Dob violation - dismissed - Construction other optional
C-construction other optional
Apr 29, 1999
Dob violation - dismissed - Construction other optional
C-construction other optional
Apr 29, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active
ECB violations
The newest 50 of 110 ECB violations. The city keeps the complete history.
- Class - 2
Temp construction equip/installation on site expired permit(shed). atoi, a sidewalk shed was observed erected at the playground area in exp #03 without valid/active dob permit authorizing the installation and m
Aug 10, 2026 · Penalty $1,250
Active - Class - 2
Exit door not self-closing. noted: at (1st fl)exit 6 stair e, d(2nd fl) stair i, h, e(3rd fl)(bulkhead) stair h doors in disrepair/not closing when tested. remedy: repair/replace door.
Apr 6, 2026 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: at stairways g, f, b, c not provided/installed or working lights throughout various floors. remedy: repair and/or replace.
Apr 6, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted: at (1st fl)stair b installed.used key locking device. remedy: provide legal hardw
Apr 6, 2026 · Penalty $1,250
Resolve - Class - 2
Reissue ecb #35691962y. failure to maintain building in code-compliantmanner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at (1st fl)gym/play areas 1 and 2, cafete
Apr 6, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: at t. o.i. there were several cross corridor and stairwell doors, that were not operating properly or not closing. remedy: repair/replace.
Apr 14, 2025 · Penalty $1,250
Resolve - Class - 2
Re-issue #35684625h. failure to maintain building in code-compliant ammanner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at t. o. i. there were several emergency lights
Apr 14, 2025 · Penalty $3,125
Active - Class - 2
Reissue#35672600n failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.at time of my inspection i observed at the first floor st
Jun 18, 2024 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code compliant manner:illumination for exits,exit discharges & public corridors per bc1006.1; 27-381.noted:on 1st fl staircase g, outer cafeteria baltic street side two lights, i
Feb 15, 2023 · Penalty $625
Active - Class - 2
Reissue #35655090h exit door not self-closing.noted:smoke door at cafeteria & exit 5 second fl staircase e, one door, first fl opposite security desk.all these doors are not closing properly.remedy:repair/repla
Feb 15, 2023 · Penalty $1,562
Resolve - Class - 2
Re-issue #35553861j(4/28/21)exit door not self closing smoke coor at cafeteria & exit #5(1st fl) 2nd floor stair "a" do not close properly.remedy:repair/replace doors
Apr 22, 2022 · Penalty $1,562
Resolve - Class - 2
Re-issue #35553862l(4/28/21)failure to maintain building in code compliant manner illumination for exits exit discharges & public corridors per bc 1006.1;27-381 existing emergency lights not operational when te
Apr 22, 2022 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bdlg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.observed:@1fl light near exit3,exit5 light16,auditorium light27,&29,@3fl light31 near
Apr 28, 2021 · Penalty $625
Resolve - Class - 2
Reissue#35495120j exit door no self closing. observed: at 2nd fl,stair'e'a door leaf does not close properly;1st fl smoke door between cafeteria & exit#5 does not close properly during inspection. remedy: repai
Apr 28, 2021 · Penalty $1,562
Resolve - Class - 1
Noted:unsafe conditions observed;the brick chimney at roof level of the adjacent property(194 baltic st) is in disrepair and is in danger ofcollapsing onto the schoolyard. remedy:vacate/discontinue use of porti
Mar 26, 2021 · Penalty $1,250
Resolve - Class - 2
Reissue#35422214n exit door not self closing. noted: observed on the 2nd fl stairway e one of the door is not opening & closing properly. remedy: repair/replace door.
Apr 30, 2020 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner note at bulkhead water penateration causing paint to peel and walls to spall repair or replace
May 6, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner note at 1st floor exit 6 door bucks no longer attached to ground at middle 2 jams.repair or replace
May 6, 2019
Resolve - Class - 2
Reissued #35325552l exit door not slef closing note at stairway e 2nd floor next to room all door not closing repair or replace door
May 6, 2019
Resolve - Class - 2
Reissued #35325555r failure to maintain building in code compliant manner use of prohibited door and or hardware as per bc 1008.1.9:27-371(j) note the following door have illegal kick stops auditorium door (8)
May 6, 2019
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. use of prohibited door and/or hardware as per 1008.1.9 1.8 27.371j kick stairs on doors in following locations rm 317 and auditorium doors. rmdy: provide lega
Mar 23, 2018
Resolve - Class - 2
28-301.1 unlawful display of artwork in corridors greater than 20% per fdny 2008 code fc 803.3.2 noted throughout the 2nd floor. rmdy: comply with notice of violation.
Mar 23, 2018
Resolve - Class - 2
Occupancy contrary to certificate of occupancy or dob records noted atstairway c near room 502 stair landing is being used as work location for school it employed with two 8' tables and chairs used as computer
Mar 23, 2018
Resolve - Class - 2
Exit door not self closing. noted stairway e multippurpose room, stairway e next to room 211. rmdy: repair and or replace door.
Mar 23, 2018
Resolve - Class - 2
Failure to maintain building in code compliant manner illumination forexits, exit discharges and public corridors per bc 1006; 1.27-381. noted at following locations rooom 424, room 318, in auditorium above ent
Mar 23, 2018
Resolve - Class - 2
28-301.1 unlawful placement of furnishings, decorations or other ob jects at exits that obstruct access to egress from or visibility thereof per fcny 2008 code fc 1027.4. noted at various locations stairway
Mar 23, 2018
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner;lack of emergency lighting for exits,exit discharges and public corridors as per bc 1006.1;27-542 noted:at cafe area,gym area and audit area.inoperative emergen
May 2, 2017
Resolve - Class - 2
Failure to maintain bldg in code complaint manner: no fire stopping per bc 712.3; 27-345. noted: @ electrical room & gas meter room, missingfire stopping on walls (hole approx 5 inch x 20 inch). rem: comply w/
May 2, 2017
Resolve - Class - 2
Reissue#35213801r exit door not self closing. noted: exterior doors atexp#1(2)doors have defective in the top hinge & do not self close,alsoforyer doors for the same exit have defective. also exit doors #3,4 at
May 2, 2017
Resolve - Class - 2
Exit door not self closing. noted: exterior doors at exp#1(4)doors do not self close,1st level,exit doors at interior do not close all the way,warped unaligned 4 doors. at exit 3,3 doors do not self close. at
Sep 27, 2016
Resolve - Class - 2
Combustible material in corridors.note:on the 1st,2nd,& 3rd fls there is an excessive amount of paper artwork on the walls (some areas flr to ceiling)on the 2nd,3rd & 4th fls students bookbags are being stored
May 6, 2015
Resolve - Class - 2
Failure to provide required corridor width.note:on the 2nd,3rd,4th & 5th fls the corridors are partially obstructed by book bags,book shelves,tables,chairs & othe school supplies & equipment.rem:comply w/the no
May 6, 2015
Resolve - Class - 2
Exit door not self-closing following doors are racked & do not close properly:exit from cafeteria to school yard side door stair 7 f @2nd fl,e 5 @2nd fl,stair h @ rear of auditorium exit 3c 5th fl,exit eti scho
Jul 18, 2014
Resolve - Class - 2
27-371(b) vision panels.use of prohibited plexiglass in rooms 211,205,200,324,304,300,305,306,317,308,311,414,410,409,419,407,406,405,404,400,505,527,506,507,523,524,508,514,132 no vision panels in rm 323 & ano
Jul 18, 2014
Resolve - Class - 2
Defective doors at room 514,4th fl stwy d,2nd fl stwy e,2 main entry vestibule doors are racked to frame,drag on floor &/or broken hinges. remedy: repair if feasible or replace doors.
May 8, 2013
Resolve - Class - 2
Ceiling & walls of 5th flr are cracked & spalling at various areas. rem:repair damaged ceilings & walls.
Mar 27, 2012
Resolve - Class - 2
Reissue 349265362. water penetrating into cellar at area of scuttle ladder. rem:provide waterproofing.
Mar 27, 2012
Resolve - Class - 2
27-371b:reissue 34926541n. plexi vission panels installed on doors at various locations throughout bldg. rem:provide required glass panels.
Mar 27, 2012
Resolve - Class - 2
1001.3;27-361:failure to maintain egress clear & unobstructed. noted:commercial freezer located in exit corridor at rear of cafeteria storage of fan cleaning supplies & stage equipment in exit stairs leading fr
Mar 27, 2012
Resolve - Class - 2
Failure to maintain reissue 34526537k. steel beam at cellar level corroding & missing fire stepping vertical cracks in masonry wall adjacentto skuttle ladder in boiler room. rem:repair all defects.
Mar 27, 2012
Resolve - Class - 2
Sec. 27-371(b) plexi vision panels. plexi (thermo plastic ) vision panels installed at various rooms throughout 4th fl. remedy: provide codecompliant vision panels
Aug 24, 2011
Resolve - Class - 2
Roof leak. the roof have become porous allowing rainwater to penetrateinto various 5th fl class rooms and into auditorium ceiling. remedy : water proof roofs.
Aug 24, 2011
Resolve - Class - 2
Defective doors.the fire proof self closing doors are racked to fram and jammed shut at auditorium roof, 2 of 4 doors jammed, north west and south east. remedy : repair doors to properly operate
Aug 24, 2011
Resolve - Class - 2
Reissue # 34856102k defective brick masonry @ cellar adjacent to scuttle ladder, vertical crack in brick masonry wall. remedy : repair brickmasonry
Aug 24, 2011
Resolve - Class - 2
Reissue # 34856103m water penetration @ cellar adjacent to scuttle ladder, the corrugated concrete ceiling has become porous allowing rain water to enter. remedy : water proof exposed area above
Aug 24, 2011
Resolve - Class - 2
Reissue # 34856104y defective steel beam and decking at cellar adjacent to scuttle ladder, rotting of steel beam and corrugated metal deck. remedy: repair or replace of required maintain
Aug 24, 2011
Resolve - Class - 1
Work w/o a permit.pavement is being remove along w/ playground area while pavement is being removed.no protection from uncontrolled movement of concrete during removal has been erected.see job filing#302558248.
Aug 24, 2010 · Penalty $8,000
Resolve - Class - 2
Failure to maintain interior bldg in code compliant manner!cracked brick wall @ firestair e boiler room wall adjacent to scuttle ladder@ cellar near waterfeed tank.cracked concrete masonry ceiling @ various loc
Apr 27, 2010
Resolve - Class - 2
No firestopping per bc 712.3 deteriorate concrete spray fireproofing @i-beam below corrugated metal decking adjacent to scuttle ladder boiler room. cellar access panel mesh opened to suspended ceiling below w/o
Apr 27, 2010
Resolve - Class - 2
No fire stopping per bc 712.3!missing mortar leaving exposed wide flange beam @ ceiling,auditorium exhaust room.remedy:provide and maintain the required fire stopping forthwith!
Apr 7, 2010
Resolve