283 Adams Street
Brooklyn, NY 11201BBL 3-00140-0010Map
Owner of record: NYC Department Of Education
283 Adams Street is a school building built in 1954 in Brooklyn, 11201. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 143
- ECB violations
- 54
- HPD complaints
- 1
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 143
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active
Show 40 more ↓
- Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 in 2020
Jun 20, 2021
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 4, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 4, 2021
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 4, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 30, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 3, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 3, 2019
Dob violation - resolved - Elevator elevatorrequired
Violation issued to elevator-failure to file category 1 2017 insp/test
Apr 5, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 3, 2018
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 3, 2018
Dob violation - resolved - Elevator elevatorrequired
Violation issued to elevator-failure to file category 1 2016 insp/test
Sep 15, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 22, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 22, 2017
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Elevator elevatorrequired
Violation issued to elevator-failure to file category 1 2015 insp/test
Dec 1, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 20, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 20, 2016
Dob violation - resolved - Elevator elevatorrequired
Violation issued to elevator-failure to file category 1 2014 insp/test
Jun 10, 2015
Dob violation - resolved - Elevator elevatorrequired
Violation issued to elevator-failure to file category 1 2013 insp/test
Oct 31, 2014
Dob violation - resolved - Elevator elevatorrequired
Violation issued to elevator-failure to file category 1 2012 insp/test
Mar 31, 2014
Dob violation - resolved - Elevator elevatorrequired
Nyc department of citywide services
Feb 27, 2014
Dob violation - resolved - Elevator elevatorrequired
Nyc department of citywide services
Feb 27, 2014
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Elevator elevatorrequired
Violation issued to elevator-failure to file category 1 2011 inspt/tst
Oct 1, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 24, 2012
Dob violation - resolved - Elevator elevatorrequired
Violation issued to elevator-failure to file category 1 201 inspt/test
Dec 13, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 8, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 23, 2010
Dob violation - resolved - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 27, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 11, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 11, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 17, 2008
Dob violation - resolved
ECB violations · 54
- Class - 2
Reissue 35490629j failure to maintain bldg in code compliance manner. noted: at rooms 415,356,347,307,305,257,255,249,247,242-2,242-1,213,151,149,119c,b45 & b53 doors are not self closing properly. remedy: repa
Apr 20, 2021 · Penalty $1,562
Resolve - Class - 1
Restore to service and contact nycdob by emailing [email protected] so that a proper inspection of the device can be scheduled by this department
Mar 2, 2021 · Penalty $3,125
Resolve - Class - 2
Reissue#35423401n-noted:at rooms 415,356,347,307,305,257,255,249,247,242-2,242-1,213,151,149,147,119c,b45 and b53:the doors are not working properly.remedy:repair and/or replace.
Apr 16, 2020 · Penalty $1,562
Resolve - Class - 2
Exit door not self-closing.reissue#35423405h.noted:at the 5th floor stair c,4th floor stair b,3rd floor smoke by 322 and stair b ny 337,2nd floor stairc,1st floor 119(kitchen)cafeteria entrance 105-2 and smoke
Apr 16, 2020 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner:no fire stoppingper bc212.3,27-345.noted:at the basement electrical room:has holes in the walls above the entrance doors.remedy:provide/maintain fire stoppi
Apr 16, 2020 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:at the 1stflr,rooms(147,149,151)2nd flr,rooms(242-1,247,255,257)door are not working properly due to defective hardware.rem:repair and/or replace.
May 24, 2019
Resolve - Class - 2
Emergency signs at elevator call stations missing,detective or non compliant with section requirements.noted:at the 3rd and 6th flr,elevatorband(13)is missing the elevator call station emergency sign.
May 24, 2019
Resolve - Class - 2
Exit door not self closing.noted:at the cafeteria main entrance(105-2)and the kitchen,3rd floor by room 337,exit doors not working properly de to detective hardware.rem;repair/replace door.
May 24, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:at the 5thflr,stairway b,missing tiles on the walls,exposing the framing.rem:repair and or replace
May 24, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:at the main entrance to the building,handicap ramps are missing mortar,in various areas.also at the left and right side of the steps has cracks and th
May 24, 2019
Resolve
Show 40 more ↓
- Class - 2
Reissue #35085609n exit passage is obstructed at 2nd flr library withfile cabinets, book cases. rmdy: remove obstruction.
Mar 6, 2015
Resolve - Class - 2
Reissue 35019596h exit passage is obstructed at 2 floor library with file cabinets, book cases. remedy : remove obstruction
Apr 8, 2014
Resolve - Class - 2
Exit passagewat obstructed at basement with custodian equipment and rear alleyway with excessive debris. remedy: remove obstructions
Apr 8, 2014
Resolve - Class - 2
6th flr gymnasium is partially obstructing the exit #630 w/exercise flr mats. remedy: remove obstruction.
May 30, 2013
Resolve - Class - 2
Reissue: 34954526n - exit passageway is partially obstructed by file cabinet & book cases located at the 2nd flr library. remedy: remove obstructions.
May 30, 2013
Resolve - Class - 2
Sec. 27-369; 28-301.1. excessive combustibles in corridors. paper signs, art work on walls and balloons hanging from ceilings in corridors in various location throughout bldg.remedy:remove combustiblematerials
Apr 20, 2012
Resolve - Class - 2
Exit lighting defective. exit light in library at doors 213 not working. remedy: repair/replace exit light.
Apr 20, 2012
Resolve - Class - 2
1017;27-361: exit corridor partially obstructed by tables & chair at 1st flr & file cabinets at cellar also library doors labeled 213 blocked by book shelves. rem:remove all obstruction.
Apr 20, 2012
Resolve - Class - 2
Exit doors not self closing. doors 455,457 and 117c. doors are racked preventing them from fully closing. remedy: repair/replace doors.
Apr 20, 2012
Resolve - Class - 2
Partial corridor obstruction. 1st flr corridor partially obstructed w/large table,chairs,tv & stacks of boxes cellar level adjacent to room b231 partly obstructed w/stacks of boxes.rem: remove all items,maintai
Jun 23, 2011
Resolve - Class - 2
Electric room storage @ cellar level electric room storage of school material, ie:metal lockers,boxes room clearly marked "no storage" rem:remove all items maintain electric room free of storage.
Jun 23, 2011
Resolve - Class - 2
Corridor hallway was partially obstructed w/ tables chairs bbq grill located by the exit passageway leading to the courtyard at ground lvl rem: remove obstruction
Jun 9, 2010
Resolve - Class - 2
No current place of assembly at the 6th floor gymnasium at time of insp rem: obtani a place of assembly cert of operation
Jun 9, 2010
Resolve - Class - 2
Exit passage or corridor required width decreased by obstruction. noteresidual construction material such as wall base, ceiling tile, plywood and drywall stored in cellar corridor width reduced to as little as
Mar 19, 2009
Resolve - Class - 1
Failure to safeguard all persons & property affected by construction operations. noted at cellar level with school in progress construction material in corridors & restricted areas in cellar are accessible to p
Oct 31, 2008 · Penalty $2,400
Resolve - Class - 1
Provision of law 28-201.1 failure to store combustible material as per code. noted at exterior gases in properly stored. rem: store as per code!!
Oct 31, 2008 · Penalty $1,600
Resolve - Class - 2
Missing stairway smoke doors 3 flr stair c & d 4 doors. remedy: install doors.
Oct 13, 2008
Resolve - Class - 2
Sec. 3314.3.2 work does't conform to approved plans there are 5 fully planked levels on scaffolds instead of 1 by approved plans (shed -2) or more amendments. remedy: conform to plans.
Jul 29, 2008 · Penalty $400
Resolve - Class - 2
Sec. 3314.13.1 scaffolds doesn't meet building code standards 1) missing diagonal bracing on exposure 2 remedy: conform to code.
Jul 29, 2008 · Penalty $400
Resolve - Class - 2
Only workers with certificate of(completion) 32 hr training program can erect, modify scaffolds above 10'h erection scaffold on roof terrance(h 70'). remedy: stop work! obtain certificate for erectors.
Jul 29, 2008
Resolve - Non-hazardous
Failure to maintain exterior building wall defect noted:grout line is missing & water is leaking through @ front facade of building remedy:repair defect
Jan 24, 2002
Resolve - Hazardous
No permit for sidewalk shed:work noted;a shed was erected at front ofbuilding approx 84'x16'x10' high with a scaffold on top of it.remedy:obtain permit for sidewalk shed
Jan 24, 2002
Resolve - Non-hazardous
73, return device to service so that a complete inspection can be made by this department.
Nov 1, 1999 · Penalty $2,500
Resolve - Non-hazardous
09h 16h 07x 74m 74 missing hand rail
Mar 1, 1999
Resolve - Non-hazardous
07x 74m 74 missing hand rail
Mar 1, 1999
Resolve - Non-hazardous
75m73m35d73-city id tags 35-floor gratings.
Jan 9, 1998 · Penalty $2,500
Resolve - Non-hazardous
75m73m35d 73-city id tags 35-floor gratings
Jan 9, 1998 · Penalty $2,500
Resolve - Non-hazardous
75m73m35d 35-floor gratings 73-city id tags.
Jan 9, 1998 · Penalty $2,500
Resolve - Non-hazardous
37m35d75m73m 37-cover controllers 35-floor gratings. 73 city id tags.
Jan 9, 1998 · Penalty $2,500
Resolve - Non-hazardous
75m73m35d 35-floor gratings
Jan 9, 1998 · Penalty $2,500
Resolve - Non-hazardous
75m73m35d 35-floor gradings.
Jan 9, 1998 · Penalty $2,500
Resolve - Non-hazardous
75m73m35d 35-floor gratings.
Jan 9, 1998 · Penalty $2,500
Resolve - Non-hazardous
75m73o35d 35-floor gratings.
Jan 9, 1998 · Penalty $2,500
Resolve - Non-hazardous
73x,73x.return to service for complete inspection or /file for removal
Feb 14, 1996 · Penalty $5,000
Resolve - Non-hazardous
40l.40-stop car from releveling into floors and blowing overolad.
Mar 24, 1995 · Penalty $1,000
Resolve - Non-hazardous
73l. 73-restore elevator 3f5237 to full service or properly dismantlesame and file with this department.
Mar 24, 1995 · Penalty $5,000
Resolve - Non-hazardous
57z9, 3l12. replace missing cab floor tile.
Mar 24, 1995
Resolve - Non-hazardous
73x return to service elevator.
Feb 2, 1994 · Penalty $5,000
Resolve - Non-hazardous
09h,35#, 35 stop water leak from roof into machinery room to prevent damage to equipment.
Feb 2, 1994 · Penalty $1,000
Resolve - Non-hazardous
73x 73u return elev to service
Mar 3, 1993 · Penalty $1,000
Resolve
Complaints
- Heat/hot water
Entire building
Jan 30, 2025 · Apt BLDG
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1954
- Floors
- 6
- Residential units
- —
- Building area
- 141,300 ft²
- Lot area
- 71,886 ft²
- Zoning
- C5-4
- Community board
- 302
- Council district
- 33
- Block / lot
- 140 / 10
- Assessed value
- $7,943,850
- Landmark / historic district
- No
Questions about 283 Adams Street
Who owns 283 Adams Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 283 Adams Street have violations?
NYC HPD has no housing violations on record for this property.
Is 283 Adams Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 283 Adams Street built?
City records list 1954 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.