Violations at 650 Hollywood Avenue
Bronx, NY 10465 · BBL 2-05438-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
27 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 20, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 8, 2014
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 9, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 24, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 9, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 11, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 2, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 27, 2007
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 2, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 8, 2006
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed
ECB violations
The newest 50 of 82 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted: permanent illegal kick stops installed on fire rated classrooms smoke and exterio
May 1, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: emergency exit illumination discharge and exit signs not working
May 1, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: fire rated classrooms and smoke doors not self-closing due to binding, missingand/or faulty hardware on classrooms 410, 414b, 426, 332, 326, 318 art
May 1, 2026 · Penalty $1,250
Active - Class - 2
Reissue #35673009k. failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381, at time of my inspection i observed exiting exit e
Aug 9, 2024 · Penalty $1,562
Resolve - Class - 2
Reissue#35654639l-failure to maintain building in code-compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.note:observed existing exit/emergency lights fixtures locat
Apr 24, 2023 · Penalty $1,562
Resolve - Class - 2
Exit door not self closing properly at time of inspection observed 3rd floor stairway "c" one exit door 3rd floor stairway "b" 2 exit doors stairway "e" one exit door at 2nd fl at stair "e" one exit door not se
Apr 6, 2022 · Penalty $625
Resolve - Class - 3
Reissue #35553903z date:4/5/21 failure to maintain bldg in code compliant manner at time of inspection observed at electrical room ceiling in disrepari from water damage spalling & cracking.remedy:repair and/or
Apr 6, 2022 · Penalty $500
Resolve - Class - 2
Reissue #35553904k date:4/5/21 failure to maintain building in code compliant manner illumination for exits exit discharges & public corridors per bc1006.1;27-381 at 1st floor gym 6 emergency lights are not ope
Apr 6, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue #35553905m date:4/5/21 failure to maintain building in code compliant manner no fire stopping per bc712.3;27-345 at time of inspection noted gas meter room has pipes penetrating through wall w/o fire st
Apr 6, 2022 · Penalty $3,125
Resolve - Class - 2
Reissue:35495385p failure to maintain bldg in code-compliant manner:nofire stopping osr bc212.3;27.345 noted:gas meter room has pipes penetrating through wall w/out fire stopping.remedy:repair &/or replace.
Apr 5, 2021 · Penalty $1,250
Resolve - Class - 2
Reissue: 35995382j failureto maintain bldg in code-compliant manner:illumination for exits,exit discharges & public corridors.per code bc 1006.1;27-381 noted:emergency lights at cafeteria left entrance not work
Apr 5, 2021 · Penalty $625
Resolve - Class - 3
Reissue:35334472x failure to maintain bldg in code-compliant manner.noted:electrical/room ceiling in disrepair from water damage.spalling & cracking.remedy:repair &/or replace.
Apr 5, 2021 · Penalty $500
Resolve - Class - 2
Failure to maintain building in code compliant manner no fire stopping per bc 712.3 ;27-345 noted observed at gas meter room pipe penetrating through wall into corridor and at electrical room conduits penetrati
May 7, 2020 · Penalty $1,250
Resolve - Class - 2
Exit door not self closing noted observed at exit #1 main entrance right hand door that leads out to hollywood avenue does not open easily and door does not fully closes due to excessive rubbing on door saddle
May 7, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner (interior) noted observed at stair "a" exit #3 next to left exit door approx 5 ft of glazed tiles are missing along teh side of door frame repair and or rep
May 7, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner illuination for exits exit discharges and public corridors per bc 1006.1;27-381 noted observed exitsing emergency lights at cafeteria over left entrance doo
May 7, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain buidling in code compliant manner (exterior) noted observed at southeast entrance stairs aluminium handrail is loose and on teh verge of becoing dislocated repair and or replace
May 7, 2020 · Penalty $625
Resolve - Class - 3
Failure to maintain building in code compliant manner noted observed at cellar eletrical room spalling plaster and crack in ceiling due to water penetration (reissued #353334472x) repair and or replace
May 7, 2020 · Penalty $500
Resolve - Class - 1
Bc3303.9 maintain required means of egress in existing building underconstruction at the time of inspection observed heavy duty sidewalk shed at exp3. also observed that 14' height sidewalk shed and overhead
Mar 28, 2019
Resolve - Class - 1
05a10,70y10,70o2-05a10)door zone restrictor not working tampered with , this is a safety device to ensure passenger safety. 70x10)oil leak in the pit, make necessary repair to prevent leak. 70o2)clean oil leak
Jul 3, 2018
Resolve - Class - 3
Failure to maintain building in code compliant manner.note:at inspection cellar level electrical meter room water damage with flaky & spalling on ceiling & walls.rem:repair and or replace.
Jun 15, 2018
Resolve - Class - 2
Failure to maintain building in code compliant manner.lack of emergency lighting for exits,exit discharges and public corridors per bc1006.127-542.note:at inspection emergency lights throughout building non ill
Jun 15, 2018
Resolve - Class - 2
Failure to maintain bldg walls or appurtenances. at south east corner of lot adjoining play yard paved surfaces heaved/uneven - trip hazard.remedy: comply w/notice of violation repair defects noted.
Apr 17, 2015
Resolve - Class - 2
Reissue # 35019592k spalling concrete at gas meter room, spalling concrete ceiling and wall rear sprinkler main. remedy: repair concrete surfaces
Aug 5, 2014
Resolve - Class - 2
Reissue # 35019595x work w/o permit. at auditorium, stage extension approx. 6' x 12' on unsecured wood 4" x 4" legs. remedy: obtain permit or restore to prior legal condition
Aug 5, 2014
Resolve - Class - 2
Work w/o permit. noted: auditorium stage has been extended outward approximately 6'x 12' feet and being supported by wooden piles. rmdy: obtain permit or restore premises to prior legal condition.
May 29, 2013
Resolve - Class - 2
The gas meter room is lacking fresh air ventilation at the cellar level. rmdy: provide/maintain fresh air ventilation at the gas meter room.
May 29, 2013
Resolve - Class - 2
Reissue: 34958015j the metal under stair the treads & riser is deteriorating located at stair "d" 1st floor level. rmdy: repair stairs.
May 29, 2013
Resolve - Class - 2
Reissue 34958017n the concrete ceiling is spalling located at the gas meter room at cellar level. rmdy: repair and/or replace concrete ceiling.
May 29, 2013
Resolve - Class - 2
(1) kick stop hold opens on corridor doors (2) door closure/coordinator not operable on auditorium entry door. (kick stops on corridor doorsthroughout all levels). remedy: remove illegal hardware,repair &/or
May 3, 2012
Resolve - Class - 2
Spalling concrete ceiling & wall. at cellar gas meter room. remedy: repair defect noted.
May 3, 2012
Resolve - Class - 2
Doors not closing - at 1st story cafeteria to public corridor doors,exit 'a' discharge door & vestibule door,exit 'b' discharge door. at 2ndstory stair 'b',cross corridor door near room 214 at 3rd story stair '
May 3, 2012
Resolve - Class - 2
Re-issue #34918337x rusted thru/deteriorated metal stair tread & riserpan. at: stair 'd' 1st up tread from 1st story landing to 2nd story. remedy: repair defect noted.
May 3, 2012
Resolve - Class - 2
Concrete floor heaved/cracked w/approx 1/2" height differential - triphazard- at 4th fl stair 'd' & 3rd story stair 'e'. remedy: repair defects noted.
May 3, 2012
Resolve - Class - 2
Flr tiles @ staircase h(b)had risen causing a 2"inch lip leading to roof.bulkhead @ the 4th flr level.rem:repair &/or replace flr tiles
Jun 14, 2011
Resolve - Class - 2
The metal behind staircase h(8)is rusted located between 1st & 2nd flr evel.rem:repair stairs
Jun 14, 2011
Resolve - Class - 2
The mortar between the glazed block wall is missing located in the corridor hallway by room 420 on the 4th flr level.rem:replace missing mortar between glazed blocks
Jun 14, 2011
Resolve - Class - 2
Failure to maintain. observed: no fresh air ventilation gas meter room.
Jun 15, 2010
Resolve - Class - 2
Failure to maintain. observed: spalling concrete, exposed rebar ceiling electric room (cellar) along foundation. also, collapsed interior walkway to cellar, to left of hollywood ave entrance, trip hazard at top
Jun 15, 2010
Resolve - Class - 2
Foundation wall has become porous & allowing rain into the bldg causing interior damage in the electrical room (b33) at cellar level. remedy: water-proof foundation wall.
Mar 10, 2009
Resolve - Class - 2
Reissue: 34639021h. interior classroom doors is missing door closers on various room on fl 1st through 4th fl. remedy: replace missing door closers.
Mar 10, 2009
Resolve - Hazardous
27-127 reissue 34526679n plaster on walls is (spalling) due to water penetration located in various classroom on floors 1st thhrough 4th floor rem repair plaster on walls/ water proof exteriror facade
Apr 1, 2008
Resolve - Hazardous
27-127 reissue 34577915x plaster on ceiling is (spalling) located in the coat room at the main entrance 1st floor rem repair plaster on ceiling
Apr 1, 2008
Resolve - Hazardous
27-127 reissue: corridor smoke doors are missing located at the 1st floor level adjacent to room 121 on first level rem: replace missing door
Apr 1, 2008
Resolve - Hazardous
27-127 reissue:34577916h classroom doors are missing door closers at various places 1st floor through 4th floor rem:replace missing door closers
Apr 1, 2008
Resolve - Hazardous
27-127 reissue:345779175 corridor smoke doors are defective noted: doors do not self close properly located on the 2nd & 3rd floor rem repair/replace corridor smoke doors
Apr 1, 2008
Resolve - Hazardous
27-127 concrete block wall is cracked vertically approximately 3 ft long located in the hallway near room b29 at cellar lvl rem repair concrete block wall
Apr 1, 2008
Resolve - Hazardous
27-127 plaster is (spalling) on the ceiling located in the electrical room (b33) at cellar level rem repair plaster on ceiling
Apr 1, 2008
Resolve - Hazardous
Reissue: 34526677j. exterior wall has become porous & allowing rain water in causing interior damages in various locations on 2 thru 4 fl bybruckner blvd. remedy: water-proof exterior wall.
Jun 26, 2007
Resolve - Hazardous
Reissue: 34526678l. roof has become porous & allowing rain water in causing interior damages in various location on the 4,3 & 2 fls. remedy:water-proof roof.
Jun 26, 2007
Resolve