2964 East Tremont Avenue

Bronx, NY 10461BBL 2-05368-0001Map

Owner of record: NYC Department Of Education

2964 East Tremont Avenue is a school building built in 1967 in Bronx, 10461. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
63
ECB violations
108
HPD complaints
4

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 63

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Jan 17, 2020

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Jan 17, 2020

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Jan 17, 2020

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Jan 17, 2020

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 5, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 5, 2019

    Dob violation - resolved
Show 40 more ↓
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 14, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 14, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 14, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 14, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 22, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 22, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 6, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 6, 2014

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 7, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 7, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 12, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 12, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 7, 2010

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 11, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 11, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 30, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 30, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 21, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 21, 2004

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed

ECB violations · 108

  • Class - 2

    Failure to maintain building in code-compliant manner. noted: interiorfire-proof doors do not self-close properly at 4th flr-staircase "e", "h". 3rd flr-staircase "j", "m". 2nd flr-"auditorium". 1st flr-stairca

    Apr 24, 2026 · Penalty $1,250

    Active
  • Class - 2

    Re-issue #35693300y. failure to maintain building in code-compliant manner. illuminations for exits, exit discharges and public corridors per bc 1006.1; 27-371. noted: in the basement gym(boys) the emergency li

    Apr 24, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35693301x. exit door not self-closing. noted: exterior fire-proof doors do not close properly when tested at 1st flr-"exit 8", "exit 5", "exit 10b", "exit 1". basement-"exit 9a". remedy: repair/replace

    Apr 24, 2026 · Penalty $1,562

    Active
  • Class - 2

    28-301.1 unlawful display of artwork in corridors greater than 20% perfdny 2008 code;fc 803.3.2.noted:on the 4th flr-rm 453 has flags hanging from the ceiling throughout the classroom.2nd flr-rms#237 & 268 have

    Apr 24, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing properly at the time of inspection. observed and noted at 1st floor stairway "j"; exit no-5 one exit door, at basement level caf-b 4 exit doors, at basement level gym-a 1 exit door, b

    Aug 15, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection observed and noted at basement level at gym-a

    Aug 15, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35672415l date of issue: 04-19-2023. failure to maintain building in code-compliant manner. no fire stopping per bc 712.3; 27-345. at the time of inspection observed and noted electrical room has multi

    Aug 15, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35672415l failure to maintain building in code compliant manner.no firestopping per bc 712.3;27-345.at time of my inspection i observed at cellar electrical room has multiple pipes and open hole that ar

    Aug 12, 2024 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35654809p failure to maintain building wall(s)or appurtenancesat time of my inspection i observed window on exposure#3 and 4 window is cracked need to make necessary repair or replace.rem:comply with co

    Aug 12, 2024 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).note:observed illegalhardware/kickdown door stops installed on fireproof self closing doors

    Apr 19, 2023 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code-compliant manner:no firestopping per bc 712.3;27-345.note:observed at cellar,electrical room has multiple pipes & open holes that are missing firestopping to seal the electr

    Apr 19, 2023 · Penalty $1,250

    Active
  • Class - 2

    Stair and/or floor identification signs missing and/or defective.note:observed at various staircase landings and/or corridors throughout the4 story school building.the location id signs are not provided identif

    Apr 19, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35423274j date:05/23/19 failure to maintain building in code compliant manner at time of inspection observed at roof level roof leaks in various areas on all roors.comply with code.remedy:repair and/or

    Apr 7, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self cloing properly at time of inspection at 1st floor level in main entrance (in side) emergency exit door no-1 & at basement level at boys gym in main entrance 1 emergency exit door not self cl

    Apr 7, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35553902r date:04/05/21 failure to maintain bldg in code compliant manner at time of inspection observed water intrusion above window at 4th floor stairwells above windows water penetration causing mol

    Apr 7, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35495379z date5.7.20 failure to maintain bldg wall(s) or appurtenance atoi i observed&noted thruout all elevations vert&horiz cracks thruout prefab concrete walls highway overpass spalling&cracked concre

    Apr 7, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue #35553901p date:04/05/21 failure to maintain building wall(s) or appurtenances.at time of inspection observed windows on exp #3 & #4 window is cracked.repair and/or replace.

    Apr 7, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue35434550k failure to maintain bldg in codecompliant manner noted:windows@exp3&4 cracked exterior cracks.comply w/code.

    Apr 5, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue35334421y failure to maintain bldg in codecompliant manner:water intrusion above window@4fl stairwells all thruout.also noted roof leaks thruout.comply w/code.

    Apr 5, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued #35423271y failure to maintain buidling wall(s) or appurtenances noted observed throughout all elevations vertical and horizontal cracks throughout pre-fab concrete walls highway overpass spallling and

    May 7, 2020 · Penalty $3,125

    Resolve
  • Class - 1

    Electrical closet/room not dedicated to electrical distribution equiptment only.basement electrical room:use electrical rooms as office,and storage!!remedy:comply with ec code.

    Nov 4, 2019 · Penalty $1,200

    Resolve
  • Class - 2

    Exit door not self closing.note:the following doors are not closing,door j corridor 5 no closure,hallway door by library and basement door by cafeteria are racked.remedy:repair or replace doors

    May 23, 2019 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.note of roof levle roof leaks in various areas on all roofs.remedy:repair and or replace.

    May 23, 2019 · Penalty $625

    Resolve
  • Class - 2

    Reissued#35334422h.failure to maintain building walls or appurtenance.note:exteriors walls of stairway 1thru6 have water penetration through cracks in exterior walls and around windows causing damage to interio

    May 23, 2019 · Penalty $3,125

    Resolve
  • Class - 2

    Reissued 35334421x.failure to maintain building in code compliant manner.note in all stairwells above windows water penetration causing moldand spaulding also paint is peeling and bubbling.remedy:repair and or

    May 23, 2019 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner use of prohibited door and or hardware per bc1008.1.8,27-371 (j)note the following doors have illegal kick stops installed.322,324,337,340,342,362,363,367,3

    May 23, 2019 · Penalty $625

    Resolve
  • Class - 2

    Reissued 35334420y.failure to maintain building in code compliant manner illumination for exits,exit discharges and public corridors per bc1006.1,27-381.note at basement level emergency lights 1thru8,32-43,28 a

    May 23, 2019 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg walls or appurtenances.noted:exterior walls of stairwells #1,2,3,4,5,6 have large vertical cracks @4th fl level allowing water to penetrate through bldg wall creating insterior damage t

    Jun 13, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.noted:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381 noted:emergency lights #1-8,21-28,32-43 loctaed in bsmt failed to operate w

    Jun 13, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner:no fire stopping.noted:larde holes in wall @exp#2 in electrical rm#274.

    Jun 13, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.noted:exit doors adjacent to room #274 in auditorium & adjacent to rm 277 failed to operate.doors are stuck closed,difficult to open.rem:repair &/or replace.

    Jun 13, 2018

    Resolve
  • Class - 3

    Failure to maintain bldg in code-compliant manner.noted:large verticalcracks located @elevated walkway fence posts inserted incorrectly.concrete is failing @every post.fence locns is between school & athletic f

    Jun 13, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.noted:water intrusion above window @4th fl stairwells #1,#2,#3,#4,#5 & #6.rem:repair &/or replace.

    Jun 13, 2018

    Resolve
  • Class - 2

    Reissue# 35213869n. failure to maintain bldg in code compliant manner spalling plaster in ceilings of staircase 2,3,4. rem: repair/replace.

    Jun 16, 2017

    Resolve
  • Class - 2

    Exit door not self closing. exit door not self closing at following locations. auditorium near room #177 and room #280(c) rmdy: repair/replace door.

    Jun 16, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. at cellar electrical room and cellar gas meter room being used for storage of construction and maintenance materials. rmdy: comply with code.

    Jun 16, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. @ stair# 1 bulkheadhallway plaster walls damaged from water penetration. rem: repair/replace.

    Jun 16, 2017

    Resolve
  • Class - 2

    Reissue 35213870k failure to maintain building in code compliant manner. roof leaking into stairway 2,3,4. rmdy: repair/replace.

    Jun 16, 2017

    Resolve
  • Class - 2

    28-301.1 unlawful placement of furnishings,decorations, objects at exits that obstruct access to egress from or visibility thereof. per fdny 2008-fc-1027.4 at exit #8 table and chairs at auditorium exit lea

    Jun 16, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. at cellar boiler room storage of gas fueled leaf vaccum. no storage of portable fueled equipment in bldg as per fc-313. rmdy: comply with code.

    Jun 16, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg walls or appurtenances-exterior entire facadeof bldg all exposures and entire roof parapet and entire retaining wall have numerous vertical cracks and spalling throughout.rmdy:maintain

    Jun 16, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.re issue nov 351283052 spalling plaster in ceilings of staircases 2,3 & 4.rem:comply w/nov

    Nov 2, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.front entrance doors& exit 10 a blocked by chairs,(rest) & security equipment.rem:comply w/nov.

    Nov 2, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. roof leaking into stairways 2,3 4. rmdy: comply w/nov.

    Nov 2, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: use of prohibited doors &/or door hardware per bc1008.1.8;27-371(j) reissue nov #35107371r. at various locations throughout all levels,cross corridor doors,sta

    Apr 22, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner re-issue nov #35107367y water damaged/spalling plaster at 4th sty stair c & stair h. remedy: comply w/notice of violation repair &/or replace defects noted.

    Apr 22, 2015

    Resolve
  • Class - 2

    Exit doors not self closing doors not closing: at 4th sty stairs,a,e &h at 3rd sty cross corridor doors adjacent to room 332 & stairs j,k,& l at 2nd sty stairs g & h at 1st sty h & stair g(door to basement)&

    Apr 22, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits,exit discharges & public corridors per bc1006.1;27-542 reissue of nov #35107373k. at basement gymnasium & public corridors

    Apr 22, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg walls or appurtenances re-issue nov #35107370p water penetrating bldg envelope at 4th sty stair c & stair h. remedycomply w/not ice of violation maintain weatherproof integrity of bldg

    Apr 22, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: failure to provide required corridor width per bc1016.2;27-369. at 3rd & 4th stories various locations public corridors partially obstructed by tables & chairs

    Apr 22, 2015

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Nov 20, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 27, 2021 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Mar 14, 2018 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Feb 5, 2018 · Apt BLDG

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1967
Floors
4
Residential units
—
Building area
450,000 ft²
Lot area
243,270 ft²
Zoning
R6
Community board
210
Council district
13
Block / lot
5368 / 1
Assessed value
$36,684,450
Landmark / historic district
No

Questions about 2964 East Tremont Avenue

Who owns 2964 East Tremont Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 2964 East Tremont Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 2964 East Tremont Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 2964 East Tremont Avenue built?

City records list 1967 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.