Violations at 3800 Baychester Avenue
Bronx, NY 10466 · BBL 2-04935-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
The newest 50 of 73 DOB violations. The city keeps the complete history.
- Construction other optional
Structure rendered noncompliant due to motor vehicle impacting sidewal k shed damaging front left side upright post remedy: shed must be maintained in a code compliant manner
Apr 4, 2026
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 28, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 23, 2020
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 15, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 6, 2016
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2014 inspection/test
Jun 10, 2015
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 25, 2013
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2011 inspection/test
Oct 1, 2012
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2010 cat 1 insp/tst
Aug 15, 2012
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 14, 2012
Dob violation - resolved - Elevator elevatorrequired
C/u
Apr 6, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 10, 2010
Vw*-violation - work w/o permit dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 10, 2010
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 10, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 10, 2010
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 14, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 14, 2009
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 27, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 25, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 25, 2008
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 23, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 23, 2007
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 2, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 6, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 6, 2006
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 1, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 1, 2005
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Nov 19, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 21, 2004
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 11, 2004
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 11, 2004
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 3, 2003
Dob violation - resolved - Elevator elevatorrequired
2s717
Mar 4, 2002
Dob violation - resolved - Elevator elevatorrequired
2s718
Mar 4, 2002
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 19, 2002
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed
ECB violations
The newest 50 of 77 ECB violations. The city keeps the complete history.
- Class - 2
Work without a permit: expired permit. as noted: at time of inspectionobserved shed at exp #1 of building with expired permit #x00879974 ex 4/1/2026. remedy: renew permit.
Apr 4, 2026 · Penalty $6,250
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: in gas meter room there was 4 buffing machines, garbage bins and cart being stored inside room and no storage is permitted. remedy: remove material.
Apr 3, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. no fire-stopping per bc 712.3; 27-345. noted: inside gas meter room, fire-stopping was missing around pipes that go through the walls. in electric meter ro
Apr 3, 2026 · Penalty $1,250
Active - Class - 2
Re-issue #35717490h. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors perbc 1006.1; 27-381. noted: emergency lights inoperative when tested "em
Apr 3, 2026 · Penalty $3,125
Active - Class - 2
Re-issue #35717491j. failure to maintain building in code-compliant manner. noted: interior fire-proof doors do not self-close properly whentested at 2nd flr-staircase "d" and "b". 1st flr-staircase "d" and "b"
Apr 3, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. noted interior fire proof self-closing doors not working properly at: 3rd fl stair c,1st fl stair c, gymnasium exit #10 smoke doors , 1st fl stair i, exit
Jun 26, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted emergency lights inoperative when tested at: 1st fl corridor ligh
Jun 26, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner: use of prohibited door and/or hardware per bc 1008.1; 27-371(j). noted illegal kickstops mounted on doors to classroom #230, 129, 127, 126, 122, 121, 118,
Jun 26, 2025 · Penalty $1,250
Resolve - Class - 2
Reissue#35644560j failure to maintain building in code-compliant manner.at time of inspection i observed at boiler room the drain closed causing water to build up with standing pubbles violation#35644660j issue
Feb 13, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue#35644561l failure to maintain building wall(s)or appurtenancesnoted:at time of inspection i observed at the roof level along top gymside water leak causing water damage due to leak from the roof violati
Feb 13, 2023 · Penalty $3,125
Resolve - Class - 2
Reissued:35548106j-failure to maintain bldg wall(s) and appurtenances.roof of gym along top side on water damaged due to roof leak.remedy:comply with code.
Mar 4, 2022 · Penalty $3,125
Resolve - Class - 2
Reissued 35548105h-failure to maintain bldg in code compliant manner.noted:boiler rom drain is closed causing water to build up w/standing puddles.remedy:comply with code
Mar 4, 2022 · Penalty $1,562
Resolve - Class - 2
Reissued:35548105h-failure to maintain bldg in code compliant manner.noted:boiler rm drain is closed causes water to build up with standing puddles.remedy:comply with code.
Mar 4, 2022 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner.note:observed at gymnasium.sections of cp ceiling & windows showing clear signs of water damage due to leaks from roof.1 section was spilling & a section of ce
Feb 11, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg wall(s) or appurtenances.observed at roof of gymnasium along the sides the roof in disrepair & leaking into gymnasium below.remedy:repair &/or replace roof & make it waterproof.
Feb 11, 2021 · Penalty $1,250
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner.note:observed in boiler room the floor drain is closed & causes water to build up w/standing puddles on boiler rm fl.remedy:repair &/or replace
Feb 11, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner:illumination for exits,exit discharges & public corridors per bc1006.1;27-381 note:observed in auditorium.emergency exits lights not working when tested.(2 fixt
Feb 11, 2021 · Penalty $625
Resolve - Class - 2
97x05: provide certificate of compliance or restore to service immediately as per code
Dec 2, 2019 · Penalty $1,562
Resolve - Class - 1
100##07-cease use continue.the device was dismantle while a cease use order was in effect,contact nyc immediately at [email protected] to schedule an inspection and obtain a certificate of compliance and re
Oct 1, 2019 · Penalty $1,250
Resolve - Class - 2
Failure to maintain bld. in code compliant manner:at room 29a & room along that line.there are areas of water penetration that has caused the walls to fall apart.the plaster is coming off the wall exposing conc
Apr 29, 2019
Resolve - Class - 2
Failure to maintain bld.in code compliant manner:emergency lights not working properly at various locations on all floors.rem:repair &/or r eplace.
Apr 29, 2019
Resolve - Class - 2
Reissue:#35022937y-failure to maintain bld.in code compliant manner.note:garbage room ceiling walls cracked.concrete coming loose from wallsat rebar.several areas have chunks of concrete missing.rem:repair &/or
Apr 29, 2019
Resolve - Class - 2
Reissue:34863560n-failure to maintain bld.walls,exterior foundation wall has become porous & allowing rain to come into the bld.it's causinginterior damage in the boiler room.rem:maintain building walls.
Apr 29, 2019
Resolve - Class - 2
Reissue: 35235336h garbage room next to kitchen walls ceiling crackedmissing concrete spalling and expired rebar. rmdy: repair replace
Mar 7, 2018
Resolve - Class - 2
Reissue#35022937y failure to maintain bldg in code compliant manner. note: at garbage room next to the kitchen the walls & ceiling are cracked. concrete are falling off the walls. remedy: repair &/or replace.
May 4, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. spalling & cracked concrete walls & ceiling @ basement kitchen stair well & vestibule. rem: comply w/ nov.
Aug 9, 2016
Resolve - Class - 2
Re-issued vio#35101285n cracked/spalling concrete walls/ceilings @bsmtkitchen stairwell/vestibule.rem:repair defects noted.
Feb 2, 2015
Resolve - Class - 2
Re-issue vio#35101286p doors not closing @roof bulk heads (2 doors).rem:repair &/or replace doors noted.
Feb 2, 2015
Resolve - Class - 2
Doors not closing at : roof bulkheads ( 2 doors) remedy: repair and / or replace doors noted
Jul 24, 2014
Resolve - Class - 2
Re-issue ecb # 35022937y cracked / spalling concrete walls & ceiling at basement kitchen stairwell vestibule. remedy : repair defects noted
Jul 24, 2014
Resolve - Class - 2
Kitchen vestibule in basement, at stiar exit, cracked and delaminatingconcrete at walls and ceiling. rmdy: maintain building as per code.
Jun 4, 2013
Resolve - Class - 2
Auditorium stage missing two (2) exit signs and lights on right side of stage. rmdy: maintain exits as per code.
Jun 4, 2013
Resolve - Class - 2
Reissue 34981904p doors not closing at 1st story e,f,i exit vesibule door stair e and f at 2nd story stair e and f, at basement stair i. rmdy: repair and/or replace doors.
Jun 4, 2013
Resolve - Class - 2
Cars parked at front entry yard area zoned r4 general residential district at main entry vehicles jumped curb to park in front of main entrydoors contrary to zoning regulations & dept records. (c/o #26177).
Jun 7, 2012
Resolve - Class - 2
Doors not closing. at 1st story stair e,f and i, exit vestible door stair e and f. at 2nd story stair e and f. at basement stair i. remedy: repair/replace doors noted.
Jun 7, 2012
Resolve - Class - 2
Reissued #34926216j. water damaged plaster ceilings/walls at 1st storygymnasium adjacent to windows. remedy: repair defects noted.
Jun 7, 2012
Resolve - Class - 2
Ceiling tile displaced / displaced / dislodged / missing / delaminatedat basement corridor various locations throughout. remedy: repair/ replace ceiling.
Aug 19, 2011
Resolve - Class - 2
Reissue #34863567x plaster spalling/water damaged at 1st story gymnasium near windows. remedy: repairs damaged plaster.
Aug 19, 2011
Resolve - Class - 2
Interior plaster is spalling located in the gymnasium 1st flr level bythe windows.rem:repair &/or replace plaster.
Jul 15, 2010
Resolve - Class - 2
Interior concrete is cracked located @ the bsmt level @ exit 9.noted:crack is visable on the staircase coming down.the stairs.rem:repair &/or replace crack concrete
Jul 15, 2010
Resolve - Class - 2
The electrical room is being used as storage room consisting of used air conditions & one pianio.rem:remove stored items
Jul 15, 2010
Resolve - Class - 3
Failure to maintain. noted: cracks w/missing mortar & displaced brickwork. location: main chimney north side & east facade opposite playground: 2nd fl to roof. remedy: maintain bldg wall.
Mar 11, 2009
Resolve - Non-hazardous
Concrete block wall has a horizontal crack apprx 3'feet long located in the cellar next to the pump station. remedy: repair crack in wall.
Apr 10, 2008
Resolve - Non-hazardous
Reissue: 34592691l (partial) interior classroom doors are missing doorclosers located at rooms 320 & 322 on the 3rd flr level. remedy: replace missing doors closers.
Apr 10, 2008
Resolve - Non-hazardous
Reissue: 34592690j (partial) plaster on the ceiling is spalling located on the roof bulkhead at staircase #2. remedy: repair plaster on ceiling.
Apr 10, 2008
Resolve - Hazardous
Interior doors are missing door closers located @ rooms 320, 322, 327,328, staircase 2 on the 3rd floor level. remedy: replace missing door closers
Aug 22, 2007
Resolve - Hazardous
Plaster on the ceiling is spalling located on the ceiling above the window located in the gymnasium on the 1st floor level & buckhead @ staircase # 2 roof level. remedy : repair plaster on the ceiling
Aug 22, 2007
Resolve - Hazardous
Interior block wall has a step crack located in the gymnasium on the 1st floor. remedy : repair concrete block wall
Aug 22, 2007
Resolve - Hazardous
Reissue: 34466211x exterior east wall missing mortar from the bricks and cracked bricks adjacent to room b53. remedy: repair exterior wall.
Mar 3, 2006
Resolve - Non-hazardous
Reissue #34385826h at east wall 3rd fl south corner has mortar missingfrom bricks east wall:courtside window of b53 has brokken bricks & hole in brickwork eastwall north corner has missing mortar at top run of
Jan 19, 2005
Resolve