Violations at 3710 Barnes Avenue

Bronx, NY 10467 · BBL 2-04675-0020 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

The newest 50 of 82 DOB violations. The city keeps the complete history.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 6, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 6, 2017

    Dob violation - resolved
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 22, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 22, 2016

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 14, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 14, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 6, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 6, 2011

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Vcat1-elevator annual inspection / test elevatorrequired

    Oct 8, 2010

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 18, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 17, 2010

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 4, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 4, 2008

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 2, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 1, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 10, 2006

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 14, 2004

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 21, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed

ECB violations

The newest 50 of 67 ECB violations. The city keeps the complete history.

  • Class - 2

    Exit door not self-closing. noted: roof level staircase "k" exterior door does not self-close when tested. remedy: repair/replace door.

    Apr 7, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. no fire-stopping per bc 712.3; 27-345. noted: in electric meter room, fire-stopping is missing due to mesh wire above entrance.

    Apr 7, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: interiorfire-proof doors do not self-close properly at 3rd flr-staircase "d", "n", smoke door near staircase "f". 2nd flr-staircase "g". classroom d

    Apr 7, 2026 · Penalty $1,250

    Active
  • Class - 2

    Re-issue #35719933r. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors perbc 1006.1; 27-381. noted: several locations throughout 3 story buildin

    Apr 7, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35684755x: failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridpts per bc 1006.1; 27-381. several locations on 3 story building, not operatio

    Jun 6, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35636555p failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:observed at various locations throughout the entire

    Aug 16, 2024 · Penalty $1,562

    Active
  • Class - 2

    At the time of inspection, it was observed that the material hoist was not installed per code bc3317.1. the hoist was missing inspection tags and was improperly secured. the basket hooks were not fully secured,

    Jul 31, 2024

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.observed at cellar level electrical rom ceiling above entry door electrical junction box missing cover,loose wires w/o wire knots hanging,electrical tape co

    Feb 21, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:no firestopping per bc 712.3; 37-345 observed at cellar level electrical room penetration in wall above electrical room entry door for newly installed condu

    Feb 21, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    28-301.1 unlawful display of artwork in corridors greater than 20 % per fdny 2008 code; fc 803.3.2 observed at fls 1,2,3 excessive display of artwork on corridor walls,paper/combustible decoration & artwork han

    Feb 21, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.observed fire proof self closing doors not closing properly.at 3rd fl stair n door is racked.at 2nd fl stair g door not self-closing fully.at 1st fl exit 12

    Feb 21, 2023 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing observed exterior exit doors not opening/closing properly at exit 12 & 13 door difficult to open while using excessive force.exit 11 door will not close properly.exit 2 & 3 one door i

    Feb 21, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35636555p failure to maintain building in code-compliant manner:illumination for exit,exit discharges & public corridors per bc 1006.1; 27-381 observed existing emergency lights not operational when te

    Feb 21, 2023 · Penalty $625

    Active
  • Class - 2

    Reissue35495276x-failure to maintain bldg in codecompliant manner:noted:illumination for exit discharges&public corridors per bc1006.1;27-381 noted:observed@3fl staird&e,360¬2fl thruout.comply w/code.

    Feb 9, 2022 · Penalty $1,562

    Active
  • Class - 2

    Reissue35386297m-failure to maintain bldg in codecompliant manner:noted:@bsmt level excessive debris,books chairs,wood equipment&paper.comply w/code

    Feb 9, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue #35491074j failure to maintain bldg in code compliant manner.noted:the windows through out the auditorium & gymnasium were not opening properly. remedy:repair & 1 replace.

    Feb 9, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35495275y failure to maintain bldg in code compliant manner noted:observed@cellar level excessive storage of combustible materials for example boxes of books,chairs&tables,etc.remove excessive storage fr

    Feb 9, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35495276x failure to maintain bldg in code compliant manner:illumination for exits,exit discharges&public corridors per bc1006.1,27-381.noted:observed on 1fl in auditorium 10emergency lights weren't work

    Feb 9, 2021 · Penalty $1,562

    Active
  • Class - 2

    Re issue #35495277h exit door not self closing.noted:on the 1st,2nd & 3rd these doors were not closing properly 1st fl stairs c,2nd fl stairs m & l & 3rd fl next to rm 303 & next to rm #325.remedy:repair/replac

    Feb 9, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self closing. noted: observed corridor fire proof self closing door next to room#325 next to 303,2nd fl-stair m & l,1st fl-stair c & o do not close properly due to defective hardware,out of square

    Apr 27, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted observed at 3rd fl by stair d & e,by room#360 at 2nd fl-stair f & g,entir

    Apr 27, 2020 · Penalty $625

    Active
  • Class - 2

    Reissue#35386297m failure to maintain bldg in code compliant manner. noted: observed at cellar,storage of combustible materials & items suchas desks,chairs,books,boxes,wooden items creating a fire hazard throug

    Apr 27, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue: 35386298y failure to maintain bldg in code compliant manner. noted; windows throughout gymnasium & auditorium do not open or close properly due to defective windows hardware,damage/broken balance.

    Apr 27, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building walls and appurtenances at second floor room 221 water intersoon vicible at wall beam windows near steam spalling from inside and (lindels) throughout windows rusted rotted.comply w

    Apr 16, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner windows in audtitorium & gymnasium balance broken do not open or close properly not working repari replace

    Apr 16, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner at basemnet/collar excessive combustible throughout front ,desk,chairs ,books.wood equipment all blocking hallways of egress fire hazard comply with code r

    Apr 16, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner at 1st floor room 121 and 3rd floor room 301 doors broken closer no closing or openings properly replace

    Apr 16, 2019

    Resolve
  • Class - 2

    Reissue #35317049y failued to maintain building in code compliant manner use of prohibied hardware hall doors & (fire) passage doors throughout kick stops doors throughout open.comply with code

    Apr 16, 2019

    Resolve
  • Class - 2

    Building or open lot occupied w/o a valid certificate of occupancy bldg occupied as school w/classrooms, cafeteria, gymnasium and auditorium, playground etc w/out a valid cofo. rmdy: obtain a valid cofo.

    Feb 26, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j) observed on variousdoors throughout school on all floors. door kick stops are placed on

    Feb 26, 2018

    Resolve
  • Class - 2

    Building or open lot occupied w/o a valid cofo noted: a bldg is occupied as a school with classrooms, cafeteria, gymnasium, auditorium, playground was observed w/o a valid cofo. rmdy: obtain a valid cofo.

    Feb 26, 2018

    Resolve
  • Class - 2

    Reissue #35260469x failure to maintain building in code-compliant manner: lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1 and 27-582 - defective emergency lighting

    Feb 26, 2018

    Resolve
  • Class - 2

    Exit door not self closing. noted: not self closing door observed at exit door from kitchen area broken door check at exit door #259. remedyrepair/replace door.

    May 5, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits,exit dischanges & public corridors per bc 1006.1;27-542. noted: defective emergency lighting was observed at 3rd sty publi

    May 5, 2017

    Resolve
  • Class - 2

    Sec. 28-118.1 bldg or open lot occupied w/o a valid c of o. noted: a bldg is occupied as school w/a c of o,classrooms,cafeteria,gymnasium,auditorium,playground area was observed. remedy: obtain a valid c of o.

    May 5, 2017

    Resolve
  • Class - 1

    02i10. alarm is not working from the button or stop switch (repair).

    Jun 2, 2016

    Resolve
  • Class - 1

    Cease use. 02l10,12d10,59m15.

    Jun 2, 2016

    Resolve
  • Class - 2

    Water penetrating roof. at various locations throughout 3rd story. rmdy: repair defect noted maintain waterproof integrity of roof.

    Jan 22, 2015

    Resolve
  • Class - 2

    Doors not closing. at 3rd story stair c, all cross corridor doors. at 1st stor exit discharge doors various locations throughout. rmdy: repair and/or replace doors noted.

    Jan 22, 2015

    Resolve
  • Class - 2

    Doors not closing. @3rd story stair c, cross corridor doors throughout 3rd story (5 sets) adjacent to rm 353,adjacent to rm 347b,adjacent to stair e,adjacent to rm 303,& adjacent to rm 325. rem:repair/replace d

    Jul 17, 2014

    Resolve
  • Class - 2

    3rd floor electrical closet fire stopping missing. rmdy: install fire stopping remove boxes.

    May 29, 2013

    Resolve
  • Class - 2

    Reissue #34926228r. decorative masonry ribbon/band spalling above 1st sty north elevation (e 217th street exposure). remedy: repair/replace defect noted.

    Jun 7, 2012

    Resolve
  • Class - 2

    Reissue #34926229z. - doors not closing - at: 1st sty stair (6) vestibule and room 149. at 2nd sty room 254. at 3rd sty room 351. remedy: repair/replace doors noted.

    Jun 7, 2012

    Resolve
  • Class - 2

    Re issue #34926230x water penetrating roof(s). at gymnasium roof and @stair jk, bulkhead roof. remedy: repair defects noted. maintain weather proof integrity.

    Jun 7, 2012

    Resolve
  • Class - 3

    Re-issue #34926232j. window sash missing. at 2nd sty room 209 upper sash. remedy: replace window sash.

    Jun 7, 2012

    Resolve
  • Class - 3

    Upper window sash missing in room 204. replace window sash.

    Aug 17, 2011

    Resolve
  • Class - 2

    Glazed ceramic block cracked vertically w/shifting block along columns of gymnasium north & south walls. remedy: provide structural stability report for north & south walls. repair defects in a safe & lawful

    Aug 17, 2011

    Resolve
  • Class - 2

    Doors not closing at: 1st story stair g vestibule,room 149 2nd story room 254,& 3rd story room 351. remedy: replace doors noted.

    Aug 17, 2011

    Resolve
  • Class - 2

    Decorative masonry ribbon spalling above 1st story along e 217th street (north elevation). remedy: repair/replace defect noted.

    Aug 17, 2011

    Resolve
  • Class - 2

    Reissue #34862752n plaster spalling/bulging/cracked & water damaged at: 1st story: auditorium north east column,corridor ceiling near rm. 144,girls bathroom ceiling & gymnasium ceiling 2nd story: boys bathroom

    Aug 17, 2011

    Resolve