2697 Westchester Avenue

Bronx, NY 10461BBL 2-04133-0200Map

Owner of record: NYC Department Of Education

2697 Westchester Avenue is a school building built in 1978 in Bronx, 10461. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
40
ECB violations
50
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 40

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 30, 2017

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2016 inspection/test

    Sep 15, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 12, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 24, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 27, 2010

    Dob violation - resolved
Show 30 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 30, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 9, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 7, 2006

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 27, 2005

    Dob violation - resolved
  • Construction other optional

    C-construction other optional

    Nov 4, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 14, 2004

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 28, 2001

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 6, 1998

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 17, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 3, 1993

    Vp*-violation unserved ecb- dismissed
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Oct 12, 1989

    Dob violation - dismissed

ECB violations · 50

  • Class - 2

    Exit door not self-closing. noted: emergency exterior exit door not self-closing due to binding, missing and/or faulty hardware on exterior door stair c exit 3 basement (1)door, stair a exit 3(1), exit 4 baseme

    Apr 16, 2026 · Penalty $625

    Active
  • Class - 2

    Reissue on ecb#35720665h failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency illuminated discharge and exit lig

    Apr 16, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue on ecb#35720664x failure to maintain building in code compliant manner.noted:fire rated classroom and smoke doors not self-closing due to binding,missing and or faulty hardware on classrooms 308,218a,21

    Apr 16, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue in ecb#35720663y failure to maintain building in code-compliant manner.noted:spalling plaster on ceiling due to water leak and damage on roof bulkheads a,b,c and d in various locations observed upon ins

    Apr 16, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:illegal kick stops permanently installed on classroom b21,smoke door basement,exit 3

    Apr 16, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:missing fire stopping in various locations throughout electric switch gear room observed upon inspection.rem:provide/maintain firestopping.

    Apr 16, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35684978n date of issue: 09-30-2024. failure to maintain building in code-compliant manner. at the time of inspection observed and noted at roof level. roofs water proof membrane in disrepair with trap

    Jun 11, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection observed at 3rd floor 2 place emergency exit

    Jun 11, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35684979p date of issue: 09-30-2024. failure to maintain building in code-compliant manner. at the time of inspection observed and noted evidence of water infiltration through roof or leak through roof

    Jun 11, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35684977l date of issue: 09-30-2024. exit door not self-closing properly at the time of inspection at the time of inspection observed and noted at 3rd floor level stairway "a" one exit door, at 2nd flo

    Jun 11, 2025 · Penalty $625

    Active
Show 40 more ↓
  • Class - 3

    Work without a permit. noted at exterior by exit #5, erected an approx. 15ftx18ft wooden shed structure. framed with 2x4 studs with door opening and sloped roof, covered with plastic roofing panels. structure i

    Sep 30, 2024 · Penalty $250

    Active
  • Class - 2

    Failure to maintain buildingin code-compliant manner. noted: at roof level, roots waterproof membrane in disrepair with trapped water underneath, several locations have tears, grading and bulging several loctai

    Sep 30, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted evidence of water infiltration through roof at classrooms 302,317a and 310 withstained, missing/peeling ceiling tiles, spalling plaster and missing l

    Sep 30, 2024 · Penalty $625

    Active
  • Class - 2

    Reissue #35673962k. exit door not self-closing. noted interior smokedoors at 3rd fl stair c and a, and at 1st fl stair c and a not closing proper;y. also exterior doors t exit #4 and 5 rub on frame/saddle and n

    Sep 30, 2024 · Penalty $625

    Active
  • Class - 2

    Exit door not self-closing properly at the time of inspection. at 3rd floor near stair "a" one exit door, at 2nd floor stair way "c" one exit door at 1st floor stairway "a" & stairway "c" each place one door no

    Jun 26, 2023 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner:no firestopping per bc 712.3;27-345.noted:observed at cellar level-rm#b-17(outside storage room)has several holes penetrating through the wall&ceiling corne

    Jun 21, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35591652k-failure to maintain building wall(s)or appurtenancesnoted:observed at exp#2 near exit to waters ave,the retaining wall hasa verticle crack approx.2ft(h)at the base of the wall,at playground th

    Jun 21, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Re-issue #35500814h.failure to maintain building wall(s)or appurtenances.noted:upon inspection observed retaining wall located at exp #1 corner of waters ave 2ft retaining wall has vertical crack at base of cha

    Aug 26, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building walls or appurtenances noted observed the retaining wall at the east elevation has vertical crack approx one inch wide at base by fence post at the south east elevation (exposed) th

    Jun 19, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Work without a permit.at time of inspection, i observed electrical work being performed on the 3rd floor hallway under job#201195444 that expired 8/26/19.stop all work under job#201195474.remedy:obtain all perm

    Oct 2, 2019

    Resolve
  • Class - 2

    Work after hours w/o variance permit contrary to 28-105.12.5.at time of inspection work performed under job#201197579 was observed with electrical work on 3rd floor and exterior facade work.all work contrary to

    Oct 2, 2019 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue:35290239h-exit door not self-closing.noted:at bsmt level exit#1 & exit#4 the doors not closing properly.also exit doors at stairway#1 on the 3rd flr not self closing properly.rem:repair and or replace.

    Jun 13, 2018

    Resolve
  • Class - 2

    Reissue:35290238x-failure to maintain building in code-compliant manner:noted.at the time of inspection water seeping in bsmt.from under bsmt fl.in boiler room,in storage room,also on 2nd floor nw wing.rem:repa

    Jun 13, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.noted at time of inspection water seeping inbsmt from under bsmt fl in boiler rm, and in storage rm.also on 2nd fl northwest wing in rms 208,204,205,206 and 207

    Sep 7, 2017

    Resolve
  • Class - 2

    Exit door not self closing.noted at bsmt level exit 1 and exit 4 doors not closing properly.also exit doors at exit 1-the bottom of door is rotten away.exit door at stairway 1 on the 3rd fl door not closing pr

    Sep 7, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg walls or appurtenances.@ 1st fl water penetrating masonry facade an 8ft long stop crack @ exit door exposure 4.

    Mar 13, 2015

    Resolve
  • Class - 2

    Doors not closing at first story exit 2 discharge doors exit 2 discharge doors. remedy: repair and/or replace doors noted

    Aug 5, 2014

    Resolve
  • Class - 2

    Reissue: 35019097n water penetrating bldg envelope at north and east elevations all levels various locations throughout. remedy: repair defects noted maintain weather proof integrity of bldg envelope

    Aug 5, 2014

    Resolve
  • Class - 2

    Reissue 34958044z water penetrating building envelope. at north/east elevations all levels various locations throughout. rmdy: repair defects noted. maintain weatherproof integrity of building envelope.

    May 28, 2013

    Resolve
  • Class - 2

    Sanitary facility - missing toilet,and stall partition dislodged/looseat 3rd story girls bathroom room 315. rmdy: repair defects noted.

    May 28, 2013

    Resolve
  • Class - 2

    Doors not closing - at 1st story exit discharge doors throughout (door& door jambs & saddles rusted deteriorated at base) stair a,& stair c at 2nd story stair b & stair c at 3rd story stair a,stair b & stair c.

    May 15, 2012

    Resolve
  • Class - 2

    Water penetrating building envelope. at roof safety fence pole pitch pockets have holes,north/east elevation water penetrating facade all levels various locations. remedy: repair defects noted maintain weather

    May 15, 2012

    Resolve
  • Class - 2

    Reissued #34901966h automatic fresh air louver inoperable at cellar boiler room. remedy: repair defect noted.

    May 15, 2012

    Resolve
  • Class - 2

    At the cellar level boiler rm f.a.i. is broken, defective in that louver fresh air motor is inoperative. when boiler is on louver does not open.remedy:replace motor to louver fai to maintain proper ventilation

    Feb 15, 2011

    Resolve
  • Class - 2

    Interior block wall has a crack approx 3'ft long located @ stair "c"between roof level & 3rd flr level.rem:repair &/or replace crack in wall

    Jul 14, 2010

    Resolve
  • Hazardous

    Re-issue 34586336x. concrete block wall is cracked located on basement level above exit door adjacent to room b14. remedy: repair concrete block wall above exit door.

    May 14, 2008

    Resolve
  • Non-hazardous

    Reissue: 34393457l exterior brick facade has become porous & allowing rain water to enter the bldg in various classroom to the 3rd flr level. remedy: water proof brick facade.

    Jul 31, 2007

    Resolve
  • Non-hazardous

    Concrete block wall is cracked located on basement level above exit door adj to room b14. remedy: repair concrete block wall above exit door

    Jul 31, 2007

    Resolve
  • Non-hazardous

    Reissue vi # 34307797y. water penetration into classroom through out. remedy: stop water penetration.

    May 31, 2006

    Resolve
  • Hazardous

    Failure to provide required means of egress for every floor. -escape windows in room 310 and 208 are partially blocked by scaffolding at exterior both in width and height. remedy: modify scaffold immediately to

    Oct 7, 2004

    Resolve
  • Hazardous

    Failure to maintain: defects are blacktop and concrete crackin and uneven settlements causing trip hazards. locations: rear play yard, and handicap ramps. remedy: make all necessary repairs.

    Mar 14, 2003

    Resolve
  • Non-hazardous

    Failure to maintain: defect are: roof leaks causing ceiling tile to sage and metal grid to rust at classrooms plaster and cement spalling at bulkheads. locations: ceiling on 3rd floor also 3rd floor bulkhead

    Mar 14, 2003

    Resolve
  • Non-hazardous

    Failure to use panic hardware where required by law. noted. no panic hardware on corridors exits. all floors. remedy: provide panic hardware.

    Jan 22, 2002

    Resolve
  • Non-hazardous

    Failure to maintain. noted: windows throughout school defective allowing water penetration ino class rooms. remedy: repair or replace windows and maintain building.

    Jan 22, 2002

    Resolve
  • Non-hazardous

    Failure to maintain. reissue. noted: at play yard blacktop cracked and sinking in various areas. remedy: repair play yard and maintain building.

    Jan 22, 2002

    Resolve
  • Hazardous

    Failure to maintain exterior building wall noted: at north and east facade of building 3rd floor mortar joints open and missing mortar and bulging in various areas causing water penetration into stairwells #1,2

    Jan 22, 2002

    Resolve
  • Non-hazardous

    Failure to maintain defect is defective windows throughout building allowing water peretration into classrooms remedy: repair all defective windows and chavlk all window prick opening.

    Apr 3, 2001

    Resolve
  • Non-hazardous

    Failure to maintain. defect is trip-hazards throughout outside black-top paved play-yard and handicap-ramp. uneven settlement and cracks at rampand play-yard. remedy; repair ramp and remove trip hazards at play

    Apr 3, 2001

    Resolve
  • Non-hazardous

    Failure to maintain defect is at masonry facfides motar joints are opening and facade is building at north-side 3 story elevation open gracks at stairwell areas. remedy: maintain building repair poing exterior

    Apr 3, 2001

    Resolve
  • Non-hazardous

    Failure to maintain exterior facade defect is concrete work is cracking spalling and exposed re-bars location front and sides of building in various location remedy make all necessary repair

    Apr 2, 1999

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1978
Floors
3
Residential units
—
Building area
50,787 ft²
Lot area
36,000 ft²
Zoning
R7-1
Community board
211
Council district
13
Block / lot
4133 / 200
Assessed value
$5,704,650
Landmark / historic district
No

Questions about 2697 Westchester Avenue

Who owns 2697 Westchester Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 2697 Westchester Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 2697 Westchester Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 2697 Westchester Avenue built?

City records list 1978 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.