Violations at 1794 East 172 Street
Bronx, NY 10472 · BBL 2-03786-0016 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
21 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 17, 1993
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 17, 1993
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 17, 1993
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 17, 1993
Dob violation - dismissed - Construction other optional
C-construction other optional
May 4, 1989
Dob violation - dismissed
ECB violations
The newest 50 of 69 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted: installatiin of illegal kick stops and/or make shift flash bolts on fire rated cl
Apr 29, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain builiding in code-compliant manner. noted: fire rated classrooms and smoke doors not self-closing due to binding, missing and/or fault hardware on classrooms 402, 207, 203, 202, 200, 110, an
Apr 29, 2026 · Penalty $1,250
Active - Class - 2
Reissue on ecb #35720769m. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors. noted: emergency illuminated discharge lights and exit lights not
Apr 29, 2026 · Penalty $3,125
Active - Class - 2
Reissue on ecb #35720971k. failure to maintain building in code-compliant manner. noted: at 1st floor exterior emergency exit door behind auditorium back stage exit rusted bottom of door allowing water to penet
Apr 29, 2026 · Penalty $3,125
Active - Class - 2
Reissue on ecb #35720770j. exit door not self-closing. noted: exterioremergency exit door not self-closing due to binding missing and/or faulty hardware on exterior doors both sides at back of stage, exit 10 1s
Apr 29, 2026 · Penalty $1,562
Active - Class - 2
Reissue ecb #35720972h. failure to maintain building in code-compliantmanner. noted: water penetration through porous foundation wall in oiltank room, gas meter room, water meter room/sprinkler room including v
Apr 29, 2026 · Penalty $3,125
Active - Class - 2
Reissue on ecb #35720973j. failure to maintain building in code-compliant manner. noted: cracked and/or missing wire glass panel or vision panels on stair b 1st floor to basement-stairwell, stair b 2nd floor to
Apr 29, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. at cafeteria exit, broken glass in door held by duct tape. remedy: comply with code.
Jul 21, 2025 · Penalty $1,250
Active - Class - 2
Reissue: 35672240z-failure to maintain building in code-compliant manner: observed at celllar level. boiler room, electrical rm, oil tank rmand stairs at various locations have water damage. remedy: comply with
Jul 21, 2025 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner: 1st floor exit doors at auditorium exit are rusted @ bottom, allowing water penetration. remedy: comply with code.
Jul 21, 2025 · Penalty $1,250
Active - Class - 2
Exit door not self-closing properly at the time of inspection at the time of inspection observed and noted at basement level-2 2 exit doors,at basement level exit-3, 1 exit door, at basement level auditorium 3
Jul 17, 2025 · Penalty $625
Active - Class - 2
Reissue #35663138h date of issue: 06-24-2022. failure to maintain building in code-compliant manner: illumination for exits, exit dischargesand public corridors per bc 1006.1; 27-381. at the time of inspection
Jul 17, 2025 · Penalty $6,000
Active - Class - 2
Reissue: 35672240z date of issue: 05-18-2023. failure to maintain building in code-compliant manner. at the time of inspection observed and noted at cellar level foundation walls have become porous allowing wat
Jul 17, 2025 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. st. lawrence ave side or school exp 4 retaining wall in a severe state of deterioration in area's cracks in mortar and parts missing and top sections of wa
Oct 1, 2024 · Penalty $625
Resolve - Class - 2
28-301.1 unlawful placement of furnishing, decorations, or other objects at exits that obstruct access to, egress from visibility thereof per fdny 2008 code; fc 1027.4. note: observed at various location, misce
May 18, 2023 · Penalty $1,250
Resolve - Class - 2
Stair and/or floor identification signs missing and/or defective. note: observed at various staircase landings and/or corridors throughout the occupied 5 story school building. the location id signs are not pro
May 18, 2023 · Penalty $625
Resolve - Class - 2
Reissue#35663137x failure to maintain building in code-compliant manner. note:observed at cellar level, boiler room, gas meter room, oil tank room and other various locations throughout the cellar. foundation w
May 18, 2023 · Penalty $1,562
Active - Class - 2
Reissue#35663137x failure to maintain building manner: no fire stopping per bc 712.3;27-345. note: observed at cellar level, electrical meter room cmu wall has a opening approx 16"(w)x18"(h) exposing the floor
May 18, 2023 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code compliant manner illumination for exits exit discharges & public corridors per bc 1006.1;27-542 noted:observed existing emergency light with battery back-up power labeled #1
Jun 24, 2022 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner.no fire stopping per bc 712.3; 27-345 noted:observed at cellar electrical room 16 inch x 18 inch opening in cmu block wall exposing pipes & q-decking from f
Jun 24, 2022 · Penalty $1,250
Resolve - Class - 2
Reissued #35582383r failure to maintain building in code compliant manner:noted:foundation walls have become porous allowing water to penetrate into building at various location throughout cellar e.g.boiler rm,
Jun 24, 2022 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code compliant manner noted:at cellar level water leakage & penetration throughout foundation wall(boiler room,gas room;tank room)rem:repair and/or replace.
Jul 22, 2021 · Penalty $1,562
Active - Class - 2
Reissue: #35272280k- failure to maintain bldg in code-compliant mannernote:at cellar level bricks have water damage.water penetrating through wall.remedy:repair and/or repair
Jun 23, 2020 · Penalty $1,562
Active - Class - 2
Failure to maintain bldg in code compliant manner. noted: observed at cellar-water penetration through bricks at the 172nd street,st. ;awrence & beach ave sides. remedy: repair &/or replace.
Aug 21, 2019 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code-compliant manner. lack of emergency lighting for exits at auditorium cafeteria and some exits lighting not working. rem: repair/replace lighting.
Jun 19, 2018
Resolve - Class - 2
Reissue #35272280k. failure to maintain building in code-compliant manner. at basement observed water penetration throughout basement new walls damp excessively visible (beach avenue side). rem: replace/repair.
Jun 19, 2018
Active - Class - 2
Failure to maintain bldg in code compliant manner. noted: @ basement level, observed water penetration in the basement on beach ave side. also there is water penetration in the gas meter room, from east 172nd s
Jul 5, 2017
Active - Class - 2
Failure to maintain bldg in code compliant manner: lack of emergency lighting fox exits, exit discharges & public corridors per bc 1006.1; 27-542. noted: in the auditorium none of the emergency lights are worki
Jul 5, 2017
Resolve - Class - 2
Reissue #35148031l failure to maintain:provide required corridor width per bc 1016.2;27-369 noted @2nd level;designated 1st fl public corridor reduced by combustible wood furniture (wider tables & seating,wood
Nov 15, 2016
Resolve - Class - 2
Fail to maintain bldg in code-compliant manner.corridor width.note: @2nd story designated 1st fl public corridor width reduced by combustible wood furniture(wicker tbls/seating,wood pianos)partially obs egres
Sep 25, 2015
Resolve - Class - 2
Reissue #35017064h.doors not closing.@ cross corridor doors @ 2nd fl,3rd fl,4th fl,5th fl & 1st fl stair b.rem:repair/replace doors.
Aug 25, 2014
Resolve - Class - 2
Reissue #35017066l.roof north raised & dislodged metal coping.rem:repair/replace according to code.
Aug 25, 2014
Resolve - Class - 2
Broken vision panel cracked. exit c-4. remedy: repair/replace.
May 7, 2013
Resolve - Class - 2
Roof - north - raised and dislodged metal coping. remedy: repair/replace according to code.
May 7, 2013
Resolve - Class - 2
Reissue 34958003m. public corridors partially obstructed by (class) furniture, cross corridors, banners (near room 352) at various locations& near exits on the flrs & some end corridor locations - flrs 2,3,4,5.
May 7, 2013
Resolve - Class - 2
Reissue: 34926866l. doors not closing: 1st sty designated flr b door, stair b, room 103, 2nd flr door room 254 - cross corridor near room 208. remedy: repair/replace doors.
May 7, 2013
Resolve - Class - 3
Violation of parking regulation in a residential district. parking a motor vehicle at the front of school on the e172nd st. rem:conform to parking regulations.
Jun 13, 2012
Resolve - Class - 3
Work without a permit work noted:on the e172nd street installed a curbout contrary to job application #413-78. rem:obtain permit.
Jun 13, 2012
Active - Class - 2
Doors not closing. at: 1st story main entry exit discharge door (door #12) at: various locations throughout all levels stair doors not closing. remedy: repair &/or replace doors.
May 2, 2012
Resolve - Class - 2
Re-issue #34926867n public corridors partially obstructed by (class) furniture,cross corridor banners. at various locations throughout all floors/corridors. remedy: remove obstructions maintain full width of
May 2, 2012
Resolve - Class - 3
Water damaged plaster walls & ceilings at: 5th story room designated 403 water damage plaster ceiling & walls. at stair d between 4th & 5th stories (floors designated 3 & 4) water damage above stair window.
Aug 10, 2011
Resolve - Class - 2
Egress/exit passageways obstructed by furniture (tables,chairs & wicker patio furniture) at 2nd story (1st fl),3rd story (2nd fl),4th story (3rd fl) 5th story (4th fl),public corridors obstructed by furniture
Aug 10, 2011
Resolve - Class - 2
Doors not closing at: 1st story designated floor b,doors: stair c,dyestibule,stair f 2nd story designated 1st fl,doors;stair b,room 103,cross corridor doors (2 sets) 3rd story designated 2nd fl,door;room 254,
Aug 10, 2011
Resolve - Class - 2
Failure to maintain observed spalling & scaling of brick perimeter foundation wall possible water penetration ponding water observed on st lawrence ave side of cellar rem: maintain bldg
Jul 7, 2010
Resolve - Class - 2
Work w/o a permit found at location gas piping in cafeteria replaced also new 3/4 & 1" fitting all work performed w/o a permit rem: obtain a permit & arrange for insp w/ this dept
Dec 8, 2009
Resolve - Class - 1
Use of prohibited door and/or hardware. noted: auditorium front 2 exit on the 1st flr exit doors has a showing bolt w/o a lock open position(hazardous). remedy: provide legal hardware.
Feb 25, 2009
Resolve - Class - 2
The plaster on the wall & ceiling spalling located at room 212 on the 2nd flr & room 309b on the 3rd flr level due to moisture. remedy: repair/replace plaster.
Feb 25, 2009
Resolve - Hazardous
Exit passage or corridor required width decreased noted:3rd fl exits a& b,e & f are partially blocked with tables chairs & book cases adjacent to rm 301 & 311.remedy:remove obstruction
Mar 18, 2008
Resolve - Hazardous
Plaster on wall is spalling located in rm 212 on the 2nd fl adjacent to the window remedy:repair replace plaster
Mar 18, 2008
Resolve - Non-hazardous
Cracks in brickwork @ parapet (roof level) location: north east interior corner of north facade.southeast interior corner of north facade.south east interior corner of south facade.remedy:repair defective brick
Feb 8, 2005
Resolve