1020 Stratford Avenue
Bronx, NY 10472BBL 2-03718-0001Map
Owner of record: NYC Department Of Education
1020 Stratford Avenue is a school building built in 1953 in Bronx, 10472. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 89
- ECB violations
- 122
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 89
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 27, 2009
Dob violation - dismissed
Show 40 more ↓
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 18, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 18, 2008
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 7, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 7, 2007
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 2, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 21, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 21, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 7, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 7, 2006
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 23, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 23, 2005
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Nov 19, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 21, 2004
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 26, 2004
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 26, 2004
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Elevator elevatorrequired
2s418
Dec 17, 2002
Dob violation - resolved - Elevator elevatorrequired
2s414
Dec 17, 2002
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed
ECB violations · 122
- Class - 2
Reissue on ecb#35720960k failure to maintain building in code-compliant manner.noted:concrete ceiling with several linear stress crack in old girls locker room now used as storage observed upon inspection.rem:r
May 5, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:cracked wire mesh glass vision panel on smoke door in gym,and cracked wire mesh vision panel on smoke door at stair e 1st fl and cracked glass at trop
May 5, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:fire ratedclassrooms and smoke doors not self closing due to binding,missing andor faulty hardware on classrooms,429,426,427,424-2 doors,418,411,302,3
May 5, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency illuminated discharge exit lights and exit signs not working
May 5, 2026 · Penalty $1,250
Active - Class - 2
Exit door not self-closing.noted:emergency exterior exit door not selfclosing due to binding,missing and or faulty hardware on exterior exitdoor at exit 2 1st fl,exit 3 1st fl,and exit 10 1st fl observed upon i
May 5, 2026 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:illegal kick stops installed on fire rated classrooms and smoke doors on smoke door s
May 5, 2026 · Penalty $1,250
Active - Class - 2
Exit door not self-closing.noted:emergency exterior exit door not selfclosing due to binding,missing and or faulty hardware at exit 1 exterior door at mini school observed upon inspection.rem:repair/replace doo
May 5, 2026 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:fire ratedclassrooms and smoke doors not self-closing due to binding,missing andor faulty hardware on smoke doors at exit 3(1)door and exit 2(2)doors
May 5, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency illuminated discharge exit lights and exit signs not operati
May 5, 2026 · Penalty $1,250
Active - Class - 2
Reissue: 35672232z-failure to maintain buildings in code-compliant manner:mini school classroom door/are not self-closing throughout entire.remedy: comply with code.
Jul 16, 2025 · Penalty $3,125
Resolve
Show 40 more ↓
- Class - 2
Reissue: failure to maintain building in code-compliant manner: cracked concrete @ ceiling in old girls locker room. remedy: comply with code.
Jul 16, 2025 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.old girls lockerroom crack in concrete ceiling.rem:repair and/or replace.
Sep 19, 2024 · Penalty $625
Active - Class - 2
Reissue#35663114n-failure to maintain building wall(s)or appurtenancesnote:observed at roof level,parapet wall has several delaminated bricks & missing mortar at various locations of the inside/roof side.rem:ma
May 16, 2023 · Penalty $3,125
Resolve - Class - 2
Reissue#35663112j-failure to maintain building in code-compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.note:observed at various locations of the 4th,3rd,2nd & 1st
May 16, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue#35663117z-failure to maintain building in code-compliant manner.noted:observed at mini-school,classroom doors(approx.70%)are not self-closing due to missing hardware.rem:repair and/or replace,install se
May 16, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue#35663113l-failure to maintain building in code-compliant manner.note:observed at cellar level,gas meter room has step cracks at various locations of the concrete walls.rem:repair and/or replace.
May 16, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue#35663118k-failure to maintain building in code-compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.note:observed at the occupied mini-school,corridor has numb
May 16, 2023 · Penalty $1,562
Resolve - Class - 2
Reissued#35502421x failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors,per bc 1006.1;27-381.noted:observed existing emergency lights,approx.90% of a
Jun 15, 2022 · Penalty $1,562
Resolve - Class - 2
Reissued#35502417n failure to maintain building wall(s)or appurtenances:noted:observed at roof level,parapet wall brick mortar at joints at various locations.rem:maintain exterior building wall.
Jun 15, 2022 · Penalty $3,125
Resolve - Class - 2
Reissued#35502422h failure to maintain building in code-compliant manner:noted:observed throughout mini-school,approx.70% of classroom doorsdon't close properly due to missing door closing hardware.rem:repair a
Jun 15, 2022 · Penalty $1,562
Resolve - Class - 2
Reissued#35502415j failure to maintain building in code-compliant manner:noted:observed two bulkhead door are in disrepair and excessively corroded,not allowing the doors to open easily or self-close properly.r
Jun 15, 2022 · Penalty $1,562
Resolve - Class - 2
Reissued#35502420y failure to maintain building in code-compliant manner:noted:observed at cellars gas meter room,horizontal and vertical step cracks on cmu block wall and concrete foundation wall.rem:repair/an
Jun 15, 2022 · Penalty $1,562
Resolve - Class - 2
Reissued#35502416l failure to maintain building in code-compliant manner:noted:observed throughout entire building at each level,approx.80% of classroom doors do not self-close due to defective or missing door
Jun 15, 2022 · Penalty $1,562
Resolve - Class - 2
Reissued#35502423j failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:observed throughout mini school,existing emergency
Jun 15, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35500792x failure to maintain bldg in code compliant manner. noted: upon inspection observed at cellar level-the gas meter room has diagonal cracks inside & near the gmr walls. remedy: repair &/or repla
Jul 21, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35500795l failure to maintain bldg in code compliant manner. noted: upon inspection observed at the mini-school more than 1/2 of theschool has doors w/defective &/or missing the self closer hardware e.g
Jul 21, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35500796n failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.127-381. noted: upon inspection observed,at the mini school above room
Jul 21, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35500786j failure to maintain bldg in code compliant manner. noted: upon inspection observed,at roof level 2 of 3 bulk head doors are in state of disrepair in both 4 rooms,the doors hace excessive rust
Jul 21, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35500787l failure to maintain bldg in code compliant manner. noted: upon inspection observed the following doors located at rm#433,#429,426,424,418,413,411,342,326,327,324,320,313,both doors,rm#311,303,
Jul 21, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35500790m failure to maintain bldg in code compliant manner. noted: upon inspection observed in electrical closets located at rm#319,219,119,& cellar level fan motor rooms have an excessive amount of st
Jul 21, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35500791y failure to maintain bldg in code compliant manner: illumination for exits,exit discharge & public corridors per bc 1006.1;27-381. noted: upon inspection observed at above rm#105,11st fl by exi
Jul 21, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35500794j failure to maintain bldg in code compliant manner. noted: upon inspection observed,at mini-school rm#8(mechanical/elec rm)has an excessive amount at storage due to the several boxes,cleaning
Jul 21, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35500793h failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: upon inspection observed at mini-school nearly 3/4 of the e.g. rm#2,18
Jul 21, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35500785h failure to maintain bldg in code compliant manner. noted: upon inspection observed,at cellar level-boiler room has water penetrating through the walls & floor at various locations.
Jul 21, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35500788n failure to maintain bldg walls or appurtenances. noted: upon inspection observed,at roof level-the parapet in various locations throughout have numerous spalling bricks & missing mortar betwee
Jul 21, 2021 · Penalty $3,125
Resolve - Class - 2
Reissue#35500789p failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: upon inspection observed illegal kickstops installed on the following
Jul 21, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35442381z failure to maintain building in code compliant manner noted observed in various locations in cellar boiler room water penetrating the walls and up through floor slab repair and or replace
Jun 29, 2020 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner noted observd classroom doors at 4th floor rooms 433,429,424,418,413,411 3rd floo rooms 302.303.320 bathroom + 324, 327, 326,342, 2nd floor room 242 ,226
Jun 24, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner illuminationf or exits,exit discharge and public corridors per cb 1006.1 27-381 noted observed existing emergency lights above 105 bby stair a 1st floor (by
Jun 24, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner noted observed at gas meter room located in the celllar horizontal cracks and spalling concrete throughout walls repair and or replace
Jun 24, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner use of prohibited door and or hardware per bc 1008.1.8;27-371(j) noted observed at minischool doors at rooms 2,8,19,20,21,22,23,27, and 28 have kickstops in
Jun 24, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner noted observed at mini school class room doors at room 2,18 do not close properly due to missing door closer hardware repair and or replace
Jun 24, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner use of prohibited door and or hardware per bc 1008.1.8;27-371(j) noted observed use of illegal kickstops at rooms /doors by the boys bathroom fire proof
Jun 24, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner noted excessive storage of garbage bins and boxes brooms school chairs table/desks within electrical closets in rooms 219,319,119 and cellars fan motor room
Jun 24, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner noted observed at minischool excessive storage of boxes garbage bins ,brooms plastic milk crate school desk chairs snow blowers being kept in mechanical ele
Jun 24, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner illumination for exits, exit discharges and public corridors per bc 1006.1;27-381 noted observed at mini school existing emergency lighst over room #5 and m
Jun 24, 2020 · Penalty $625
Resolve - Class - 2
Reissue #35442382k failure to maintain buuilding in code compliant manner noted observed the two bulkhead doors are in disrepair rusted and not opening easily and or not self closing (fan/motor room) repair
Jun 24, 2020 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building wall(s) or appurtenances noted observed at roof level delamination of bricks locations throughout parapet wall maintain exterior building wall maintain exterior building wall
Jun 24, 2020 · Penalty $1,250
Resolve - Class - 2
Reissue: 34861856n - failure to maintain building in code-compliant manner: water penetration at cellar boiler room and various locations. remedy: repair and/or replace
Aug 8, 2019
Resolve - Class - 2
Failure to maintain building in code-compliant manner: bulkheads door are in disrepair and very hard to open. rusty and falling apart. remedy: repair and/or replace
Aug 8, 2019
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1953
- Floors
- 4
- Residential units
- —
- Building area
- 190,920 ft²
- Lot area
- 143,578 ft²
- Zoning
- R6
- Community board
- 209
- Council district
- 18
- Block / lot
- 3718 / 1
- Assessed value
- $12,573,900
- Landmark / historic district
- No
Questions about 1020 Stratford Avenue
Who owns 1020 Stratford Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 1020 Stratford Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 1020 Stratford Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 1020 Stratford Avenue built?
City records list 1953 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.