1020 Stratford Avenue

Bronx, NY 10472BBL 2-03718-0001Map

Owner of record: NYC Department Of Education

1020 Stratford Avenue is a school building built in 1953 in Bronx, 10472. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
89
ECB violations
122
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 89

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 27, 2009

    Dob violation - dismissed
Show 40 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 18, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 18, 2008

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 7, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 7, 2007

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 2, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 21, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 21, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 7, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 7, 2006

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 23, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 23, 2005

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 21, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 26, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 26, 2004

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatorrequired

    2s418

    Dec 17, 2002

    Dob violation - resolved
  • Elevator elevatorrequired

    2s414

    Dec 17, 2002

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed

ECB violations · 122

  • Class - 2

    Reissue on ecb#35720960k failure to maintain building in code-compliant manner.noted:concrete ceiling with several linear stress crack in old girls locker room now used as storage observed upon inspection.rem:r

    May 5, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:cracked wire mesh glass vision panel on smoke door in gym,and cracked wire mesh vision panel on smoke door at stair e 1st fl and cracked glass at trop

    May 5, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:fire ratedclassrooms and smoke doors not self closing due to binding,missing andor faulty hardware on classrooms,429,426,427,424-2 doors,418,411,302,3

    May 5, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency illuminated discharge exit lights and exit signs not working

    May 5, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing.noted:emergency exterior exit door not selfclosing due to binding,missing and or faulty hardware on exterior exitdoor at exit 2 1st fl,exit 3 1st fl,and exit 10 1st fl observed upon i

    May 5, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:illegal kick stops installed on fire rated classrooms and smoke doors on smoke door s

    May 5, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing.noted:emergency exterior exit door not selfclosing due to binding,missing and or faulty hardware at exit 1 exterior door at mini school observed upon inspection.rem:repair/replace doo

    May 5, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:fire ratedclassrooms and smoke doors not self-closing due to binding,missing andor faulty hardware on smoke doors at exit 3(1)door and exit 2(2)doors

    May 5, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency illuminated discharge exit lights and exit signs not operati

    May 5, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue: 35672232z-failure to maintain buildings in code-compliant manner:mini school classroom door/are not self-closing throughout entire.remedy: comply with code.

    Jul 16, 2025 · Penalty $3,125

    Resolve
Show 40 more ↓
  • Class - 2

    Reissue: failure to maintain building in code-compliant manner: cracked concrete @ ceiling in old girls locker room. remedy: comply with code.

    Jul 16, 2025 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.old girls lockerroom crack in concrete ceiling.rem:repair and/or replace.

    Sep 19, 2024 · Penalty $625

    Active
  • Class - 2

    Reissue#35663114n-failure to maintain building wall(s)or appurtenancesnote:observed at roof level,parapet wall has several delaminated bricks & missing mortar at various locations of the inside/roof side.rem:ma

    May 16, 2023 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35663112j-failure to maintain building in code-compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.note:observed at various locations of the 4th,3rd,2nd & 1st

    May 16, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35663117z-failure to maintain building in code-compliant manner.noted:observed at mini-school,classroom doors(approx.70%)are not self-closing due to missing hardware.rem:repair and/or replace,install se

    May 16, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35663113l-failure to maintain building in code-compliant manner.note:observed at cellar level,gas meter room has step cracks at various locations of the concrete walls.rem:repair and/or replace.

    May 16, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35663118k-failure to maintain building in code-compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.note:observed at the occupied mini-school,corridor has numb

    May 16, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35502421x failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors,per bc 1006.1;27-381.noted:observed existing emergency lights,approx.90% of a

    Jun 15, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35502417n failure to maintain building wall(s)or appurtenances:noted:observed at roof level,parapet wall brick mortar at joints at various locations.rem:maintain exterior building wall.

    Jun 15, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Reissued#35502422h failure to maintain building in code-compliant manner:noted:observed throughout mini-school,approx.70% of classroom doorsdon't close properly due to missing door closing hardware.rem:repair a

    Jun 15, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35502415j failure to maintain building in code-compliant manner:noted:observed two bulkhead door are in disrepair and excessively corroded,not allowing the doors to open easily or self-close properly.r

    Jun 15, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35502420y failure to maintain building in code-compliant manner:noted:observed at cellars gas meter room,horizontal and vertical step cracks on cmu block wall and concrete foundation wall.rem:repair/an

    Jun 15, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35502416l failure to maintain building in code-compliant manner:noted:observed throughout entire building at each level,approx.80% of classroom doors do not self-close due to defective or missing door

    Jun 15, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35502423j failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:observed throughout mini school,existing emergency

    Jun 15, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35500792x failure to maintain bldg in code compliant manner. noted: upon inspection observed at cellar level-the gas meter room has diagonal cracks inside & near the gmr walls. remedy: repair &/or repla

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35500795l failure to maintain bldg in code compliant manner. noted: upon inspection observed at the mini-school more than 1/2 of theschool has doors w/defective &/or missing the self closer hardware e.g

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35500796n failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.127-381. noted: upon inspection observed,at the mini school above room

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35500786j failure to maintain bldg in code compliant manner. noted: upon inspection observed,at roof level 2 of 3 bulk head doors are in state of disrepair in both 4 rooms,the doors hace excessive rust

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35500787l failure to maintain bldg in code compliant manner. noted: upon inspection observed the following doors located at rm#433,#429,426,424,418,413,411,342,326,327,324,320,313,both doors,rm#311,303,

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35500790m failure to maintain bldg in code compliant manner. noted: upon inspection observed in electrical closets located at rm#319,219,119,& cellar level fan motor rooms have an excessive amount of st

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35500791y failure to maintain bldg in code compliant manner: illumination for exits,exit discharge & public corridors per bc 1006.1;27-381. noted: upon inspection observed at above rm#105,11st fl by exi

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35500794j failure to maintain bldg in code compliant manner. noted: upon inspection observed,at mini-school rm#8(mechanical/elec rm)has an excessive amount at storage due to the several boxes,cleaning

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35500793h failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: upon inspection observed at mini-school nearly 3/4 of the e.g. rm#2,18

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35500785h failure to maintain bldg in code compliant manner. noted: upon inspection observed,at cellar level-boiler room has water penetrating through the walls & floor at various locations.

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35500788n failure to maintain bldg walls or appurtenances. noted: upon inspection observed,at roof level-the parapet in various locations throughout have numerous spalling bricks & missing mortar betwee

    Jul 21, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35500789p failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: upon inspection observed illegal kickstops installed on the following

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35442381z failure to maintain building in code compliant manner noted observed in various locations in cellar boiler room water penetrating the walls and up through floor slab repair and or replace

    Jun 29, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner noted observd classroom doors at 4th floor rooms 433,429,424,418,413,411 3rd floo rooms 302.303.320 bathroom + 324, 327, 326,342, 2nd floor room 242 ,226

    Jun 24, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illuminationf or exits,exit discharge and public corridors per cb 1006.1 27-381 noted observed existing emergency lights above 105 bby stair a 1st floor (by

    Jun 24, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner noted observed at gas meter room located in the celllar horizontal cracks and spalling concrete throughout walls repair and or replace

    Jun 24, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner use of prohibited door and or hardware per bc 1008.1.8;27-371(j) noted observed at minischool doors at rooms 2,8,19,20,21,22,23,27, and 28 have kickstops in

    Jun 24, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner noted observed at mini school class room doors at room 2,18 do not close properly due to missing door closer hardware repair and or replace

    Jun 24, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner use of prohibited door and or hardware per bc 1008.1.8;27-371(j) noted observed use of illegal kickstops at rooms /doors by the boys bathroom fire proof

    Jun 24, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner noted excessive storage of garbage bins and boxes brooms school chairs table/desks within electrical closets in rooms 219,319,119 and cellars fan motor room

    Jun 24, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner noted observed at minischool excessive storage of boxes garbage bins ,brooms plastic milk crate school desk chairs snow blowers being kept in mechanical ele

    Jun 24, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination for exits, exit discharges and public corridors per bc 1006.1;27-381 noted observed at mini school existing emergency lighst over room #5 and m

    Jun 24, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35442382k failure to maintain buuilding in code compliant manner noted observed the two bulkhead doors are in disrepair rusted and not opening easily and or not self closing (fan/motor room) repair

    Jun 24, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances noted observed at roof level delamination of bricks locations throughout parapet wall maintain exterior building wall maintain exterior building wall

    Jun 24, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue: 34861856n - failure to maintain building in code-compliant manner: water penetration at cellar boiler room and various locations. remedy: repair and/or replace

    Aug 8, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner: bulkheads door are in disrepair and very hard to open. rusty and falling apart. remedy: repair and/or replace

    Aug 8, 2019

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1953
Floors
4
Residential units
—
Building area
190,920 ft²
Lot area
143,578 ft²
Zoning
R6
Community board
209
Council district
18
Block / lot
3718 / 1
Assessed value
$12,573,900
Landmark / historic district
No

Questions about 1020 Stratford Avenue

Who owns 1020 Stratford Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 1020 Stratford Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 1020 Stratford Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 1020 Stratford Avenue built?

City records list 1953 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.