Bronx, NY 10473 · BBL 2-03644-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

The newest 50 of 93 DOB violations. The city keeps the complete history.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 20, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 20, 2017

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2015 inspection/test

    Dec 1, 2016

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2015 inspection/test

    Dec 1, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 28, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 28, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 24, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 24, 2015

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2014 inspection/test

    Jun 10, 2015

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2014 inspection/test

    Jun 10, 2015

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 7, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 7, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 7, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 7, 2013

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2011 inspection/test

    Oct 1, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 1, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 1, 2012

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2011

    Dob violation - resolved

ECB violations

The newest 50 of 59 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner. no fire stopping per bc 712.3; 27-345. noted: missing fire stopping in several locations in electrical switch gear room at basement level observed upon ins

    May 4, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing. noted: emergency exterior exit door, not self-closing due to binding missing and/or faulty hardware on exterior door at exit 11 stair a and exterior at basement level boiler room obs

    May 4, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: emergency illuminated discharge exit light and exit signs not wo

    May 4, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue on ecb #35720967n. failure to maintain building in code-compliant manner. noted: fire rated classrooms and smoke doors not self-closing properly due to binding, missing and/or faulty hardware on classro

    May 4, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.exit#2 line of doors top to bottom not closing properly.exit g gym doors/and cafeteriadoors.rem:comply with code.

    Jul 17, 2025 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:at cafeteria 2 emergency exit lighting found inoperational when tested

    Sep 24, 2024 · Penalty $625

    Resolve
  • Class - 2

    Reissued#35501072m failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:observed existing emergency lights labeled#4,#2b b

    Jun 30, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35501073y failure to maintain building wall(s)or appurtenances:noted:observed on bolton avenue,sidewalk hatch's concrete footing has 1 inch horizontal crack going through it,waterproof sealant is compr

    Jun 30, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Reissued#35501072m.failure to maintain building in code compliant manner.illumination per exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 1st floor emergency light#1a,2b,9,10,15b,16,16a

    Jul 21, 2021 · Penalty $1,562

    Active
  • Class - 2

    Reissued#35501073y.failure to maintain building wall(s) or appurtenances.noted:at southern(bolton ave)side of the building sidewalk hatch footing has cracks and also observed at southern elevation.missing sever

    Jul 21, 2021 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building wall(s) or appurtenances noted observed at south elevation concrete footing for the sidewalk hatch has an approx 4 ft long x 1 inch wide horizontal crack also at south elevation abo

    Jul 2, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination for exits , exit discharges and public corridors per bc 1006.1;27-381 noted observed existing emergency lighst with battery back up power inst

    Jul 2, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35148040n failure to maintain bldg in code compliant manner. at cellar level elevator door & jamb rusted & deteriorated in operable. remedy: comply w/notice of violation.

    Nov 16, 2016

    Resolve
  • Class - 2

    Reissue nov #35108027m issued 8/29/2014.failure to maintain building in code compliant manner.note:at cellar elevator door jamb and door rusted,deteriorated rendering elevator inoperable. rem:repair defect note

    Sep 30, 2015

    Resolve
  • Class - 2

    Approx 4" seperation gap of concrete sidewalk along perimeter of bldg exterior walls.rem:repair/replace defects noted.

    Aug 29, 2014

    Resolve
  • Class - 2

    Reissue #35017091n.cellar elevator door & door jamb rusted & deteriorated.door inoperable.rem:repair/replace noted defects.

    Aug 29, 2014

    Resolve
  • Class - 2

    27-371(b),reissue #35017092p.vision panel not by code-plexi glass.room327 door gym doors.rem:maintain vision panels as per code.

    Aug 29, 2014

    Resolve
  • Class - 2

    Reissue #35017093r.expansion joints raised/broken transition strip.trip hazard @ exit 1,2,3,4 & near teachers cafeteria.rem:repair/replace defects.

    Aug 29, 2014

    Resolve
  • Class - 2

    Reisssue #35017094z.water penetration.@ fuel tank room concrete fl hasbecome porous w/ approx 2" standing water.rem:water proof concrete fl.

    Aug 29, 2014

    Resolve
  • Class - 2

    Reissue #35017095k.exit 10 exterior steps crackes & broken.rem:repair/replace as per code.

    Aug 29, 2014

    Resolve
  • Class - 2

    Reissue #35017096m.water penetration.@ fuel tank room,foundation wall has become porous allowing water to enter w/ 2" standing water.rem:water proof foundation wall.

    Aug 29, 2014

    Resolve
  • Class - 2

    Fuel tank room - wall penetration in cmu wall approx 6" x 10". remedy:maintain fuel tank room enclosure - install cmu.

    May 2, 2013

    Resolve
  • Class - 2

    Exit 10 exterior steps cracked & broken. remedy: repair/replace as percode.

    May 2, 2013

    Resolve
  • Class - 2

    Fuel tank room - water penetration through wall and flr. remedy: maintain bldg as per code.

    May 2, 2013

    Resolve
  • Class - 2

    Expansion joints - reissue 34957750l. 1- expansion joints raised/broken transition strip. trip haz at exit 3 at 1,2,3,4 and near teachers cafeteria - exit 4. remedy: repair/replace defect.

    May 2, 2013

    Resolve
  • Class - 2

    Sec. 27-371(b) vision panel not by code- plexiglass. room 327 door gymdoors. remedy: maintain vision panels as per code.

    May 2, 2013

    Resolve
  • Class - 2

    Reissue: 34957751n. cellar elevator door and door jamb rusted and deteriorated. door inoperable. remedy: repair/replace.

    May 2, 2013

    Resolve
  • Class - 2

    Door not closing. at: cellar elevator door rusted deteriorated door & door jamb - door inoperable. remedy: replace door & jamb (door frame).

    May 1, 2012

    Resolve
  • Class - 2

    Expansion joints raised/broken transition strips - trip hazard - at: 1st,2nd,3rd and 4th stories in line w/exit 3. remedy: repair defects noted.

    May 1, 2012

    Resolve
  • Class - 2

    Doors not closing; at: stair d & g 2nd story stair b & c 3rd story stair c & 4th story. remedy: repair/replace doors.

    Aug 8, 2011

    Resolve
  • Class - 2

    Water penetrating foundation wall/slab at oil tank room standing waterobserved in oil tank room. remedy: provide water/weather proofing for foundation.

    Aug 8, 2011

    Resolve
  • Class - 2

    Work does not conform to approved construction documents &/or approvedamendments. stop work order issued: supported scaffold erected in area,that is not on approved plan. supported scaffold is on top of sidewal

    Dec 29, 2010

    Resolve
  • Class - 2

    Fail to maintain. observed cracked/spalling plaster on ceiling/suffit by window rm 273. remedy: maintain bldg

    Jun 30, 2010

    Resolve
  • Class - 2

    Reissue 34761632x. fail to maintain observed foundation wall has become porous allowing water penetration at cellar level boiler pit area & oil tank room. remedy: maintain bldg

    Jun 30, 2010

    Resolve
  • Class - 2

    No fire stopping provided in the electrical room (b15) at basement level. noted: pipe penetration going through the wall has no fire stopping leaving open gaps between pipes & wall. remedy: provide/maintain fir

    Feb 19, 2009

    Resolve
  • Class - 2

    No fresh air ventilation supplied in the gas meter room (b1) at basement level. remedy: provide fresh air ventilation in gas meter room.

    Feb 19, 2009

    Resolve
  • Class - 2

    Foundation wall has become porous & allowing rain water into the building causing interior damages in the boiler room at cellar level adjacent to story ave. remedy: water proof foundation wall.

    Feb 19, 2009

    Resolve
  • Class - 2

    Corridor smoke door is missing located on the 3rd flr level by room 327. remedy: replace missing smoke door.

    Feb 19, 2009

    Resolve
  • Non-hazardous

    27-127 roof above the auditorium stage has become porous and allowing rain water into the building causing interior damages in the auditorium stage 1st floor rem: water prood above auditorium stage

    Apr 4, 2008

    Resolve
  • Non-hazardous

    27-127 concrete block wall has a step crack in the gymnasium storage room on the 1st floor rem: repair/replace concrete block wall

    Apr 4, 2008

    Resolve
  • Non-hazardous

    27-127 reissue 34576986z plaster is spalling on the ceiling in the bathroom room 243 on the 2nd floor rem: repair plaster on ceiling

    Apr 4, 2008 · Penalty $2,500

    Resolve
  • Hazardous

    27-127 reissue 34576987k roof adjacent to roof bulkhead b has become rorous allowing rain water into the building calling interior damages at roof bulkhead b rem: water proof exterior roof

    Apr 4, 2008

    Resolve
  • Hazardous

    Reissue vi 34393467p failure to maintain roof next to bulkhead(b)wateris ponding under roof ceiling rubber.remedy:repair defect & remove ponding water at above location.

    Jun 20, 2007

    Resolve
  • Hazardous

    Reissue vi34393466n failure to maintain bathroom#243 ceiling plaster is spalling & missing.remedy:repair defect at above location.

    Jun 20, 2007

    Resolve
  • Non-hazardous

    Failure to maintain roof next to bulkhead(b) water is ponding under roof. noted:large area of ponding water of roof. remedy:remove water that is ponding (repair roof).

    Jun 1, 2006

    Resolve
  • Non-hazardous

    Failure to maintain bathroom # 243 ceiling plaster is spalling & missing. remedy:repair plaster ceiling in bathroom # 243.

    Jun 1, 2006

    Resolve
  • Non-hazardous

    Failure to maintain bulkhead #12 water penetrating through brick wall into interior. remedy:stop water penetration in to interior.

    Jun 1, 2006

    Resolve
  • Non-hazardous

    Reissue vi#34466502x. vertical & horizontal crack in concrete block wall & loose block at steal ladder. location: auditorium back stage wall at right side of stage. remedy:repair concrete block wall.

    Jun 1, 2006

    Resolve
  • Non-hazardous

    50a/50b. 50a- pipe down the safety valve discharge to a safe point to prevent scalding 50b- install a fixed ladder to provide safe access to the top of the boiler.

    Feb 7, 2006

    Resolve
  • Non-hazardous

    18a/50a/50b/50c. 18a- repair all the leaking hand holes. 50a- repair the corroded manhole ring. 50b- repair the leaking feed water supply nozzel. 50c- install a fixed ladder to provide safe access to the top of

    Feb 7, 2006

    Resolve