Violations at 2050 Lafayette Avenue
Bronx, NY 10473 · BBL 2-03609-0016 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
14 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Construction other optional
Emergency work order.stop all concrete operations except compliance w/ emergency wrk ordr undr sprvsn of pe.m/m to include all equipment, materials, operation sequences,head counts required, etc
Jul 7, 2023
Dob violation - dismissed - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2020)
Oct 10, 2021
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 22, 2021
Dob violation - resolved - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 in 2019
Jun 29, 2020
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed
ECB violations
The newest 50 of 83 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner. no fire-stopping per bc 712.3; 27-345. noted: in the gas meter room, fire-stop is missing in multiple areas around pipes. also in electric meter room fire-
May 4, 2026 · Penalty $1,250
Active - Class - 2
Re-issue #35688891z. failure to maintain building in code-compliant manner. noted: classroom doors do not self-close properly. at 3rd flr rm#5-302, 304, 306, 318, 319, 322. 2nd flr rm #s-202, 219, 222. 1st flr
May 4, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection observed and noted at 2nd floor near rm #207
Jul 18, 2025 · Penalty $1,250
Resolve - Class - 2
Reissue #35688889j date of issue: 09-19-2024. failure to maintain building wall(s) or appurtenances. at the time of inspection observed and noted at gym, lunch room roof top parapet is not 42" height as require
Jul 18, 2025 · Penalty $6,250
Resolve - Class - 2
Reissue: 35688890r date of issue: 09-19-2024. failure to maintain building wall(s) or appurtenances. at the time of inspection observed and noted at rooftop brick chimney with 10" vertical crack, 10 inch vertic
Jul 18, 2025 · Penalty $6,250
Resolve - Class - 2
Reissue #35688891z date of issue: 09-19-2024. exit door not self-closing properly at the time of inspection at the time of inspection observed and noted at 3rd floor near rm #307 one corridor exit door not self
Jul 18, 2025 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:at 3rd floor corridor door next to room#307 do not close properly.rem:repair/replace door.
Sep 19, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building wall(s)or appurtenances.noted:at rooftop brick chimney with 10'vertical crack.rem:make necessary repairs.
Sep 19, 2024 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building wall(s)or appurtenances.noted:at gym lunchroom rooftop,parapet is not 42"height as required.rem:provide parapet/railing.
Sep 19, 2024 · Penalty $1,250
Resolve - Class - 2
Crane operations with missing flag person monitor traffic during lifts intersection lafayette and pugsley ave,field conditions not reflect dot stipulations occupancy of 8feet roadway with protected bike lane an
Aug 29, 2024 · Penalty $2,400
Active - Class - 1
At a incident that occurred at a 3 story building where concrete was being poured at roof level. formwork and shoring post gave out pouring onto the 3rd fl level. inspection revealed that no proper checklist fo
Jul 7, 2023 · Penalty $5,000
Resolve - Class - 2
Failure to provide an adequate curing box at construction site: as noted at time of my inspection observed (1) curing not plugin to regulate the temperature with 24 4x8 test cylinders inside which should be con
Jul 7, 2023 · Penalty $2,500
Resolve - Class - 2
Failure to perform proper concrete washout procedures and collection and containment: as noted at time of my inspection on a job site observed concrete pump truck washing out in a bag that (1) was not leakproof
Jul 7, 2023 · Penalty $2,500
Resolve - Class - 1
In response to incident where worker got injured it was reported that worker was standing on unsecured plywood that gave way causing worker to fall approx. 12 feet and cut his left arm and landing on 3rd story
Jun 20, 2023
Resolve - Class - 2
At time of inspection on active 3 story nb jobsite currently under foundation/ earthwork, i observed trees in place at exp#-3 on sidewalk at virgil place not protected as per rule.stop all ops at jobsite, provi
Oct 26, 2022 · Penalty $625
Resolve - Class - 2
At time of inspection on active 3 story nb jobsite currently under foundation/ earthwork, i observed ramp or runway in places at exp#-1 & 3 used by workers & for carrying construction material and equipments le
Oct 26, 2022 · Penalty $625
Resolve - Class - 1
At time of inspection on active 3 story nb jobsite currently under foundation/ earthwork, i observed in place at exp#-1&3&4 including area of installed laggings with excavation approximately 9ft to 22ft deep in
Oct 26, 2022 · Penalty $2,500
Resolve - Class - 1
At time of inspection on active 3 story nb jobsite currently under foundation/ earthwork, i observed excavated area of approximately 9ft to elevation 22ft deep across with no access or safe means of egress/ ing
Oct 26, 2022 · Penalty $2,500
Resolve - Class - 2
Reissue#35502103k fail to maintain building in code compliant manner iilluminate noted:at various location emergency light not working when tasted all over the school.rem:repair and/or replace.
Jul 27, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg walls or appurtenances. noted: observed at tranportable"t1"at north elevation,metal cladding rs loose & lifted at the bottom corner projecting outwards. remedy: maintain exterior bldg
Jul 7, 2020 · Penalty $1,250
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: observed key cylinders installed on panic bar hardware at gymnasium,auditorium & cafeter
Jul 7, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: observed at entrance lobby-emergency light package marked l2 at stair'a'
Jul 7, 2020 · Penalty $625
Resolve - Class - 2
Exit door not self closing. noted: fire proof self closing bdoors at 1st fl stair'a' cafeteria by exit 4,gymnasium exit doors do not self close properly due to doors being racked & knocking on door bucks.
Jul 7, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: noted: observed thefollowing room doors are not closing properly at rooms#302,306,318,319322,202,204,219,222,103,109,due to missing door closer hardware & room
Jul 7, 2020 · Penalty $625
Resolve - Class - 1
At time of inspection found tubes leaking on top and bottom. seal boiler at site.
Aug 7, 2019
Resolve - Class - 2
Failure to maintain bldg in code compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.noted emergency lights in both transportable are not working,when tested.rem repa
Jun 22, 2017 · Penalty $2,500
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.illumination for exits,exit discharges & public corridors per bc1006.1;27-381.noted emergency lights in the cafeteria,& in the basement are not working when tes
Jun 22, 2017 · Penalty $2,500
Resolve - Class - 2
Reissue #34957748m fail maintain bldg compliant manner:fire stopping note:fire stopping missing at gas meter room, conduit pipe penetration at basement. rem:comply w/nov
Sep 22, 2015
Resolve - Class - 2
Failure to maintain building in code-compliant manner:corridor width note:@stair 6 exit b debris,tables,ext 11 room b1 and sprinkler room partially blocked egress.rem:comply w/nov
Sep 22, 2015
Resolve - Class - 2
Failure to maintain building in code-compliant manner:corridor width note:@cellar combustible materials in corrodors,books cardboard,chairs,tables throughout.rem:comply w/nov
Sep 22, 2015
Resolve - Class - 3
Failure to maintain building wall(s) or appurtenances.note:chimney @roof (vorticle) cracks visible.rem:comply w/nov
Sep 22, 2015
Resolve - Class - 2
Reissue #35017075m.interior door hardware not self closing t-1,t-2,t-3& t-4.rem:repiar/replace.
Aug 28, 2014
Resolve - Class - 3
Reissue #35016749x.roof chimmey-north & west exposure vertical cracks.rem:repair defects noted.
Aug 28, 2014
Resolve - Class - 2
Reissue #35017076p.cellar-combustible material in corridors b-8 b-11,books clothings cardboard boxes storage.rem:maintain cellar as per code.
Aug 28, 2014
Resolve - Class - 2
Reissue #35017078z.stair 6 exit b-debris nurses tables.exit 11 room b-1,sprinkler room-storgae partially blocking egress @ these areas.rem:maintain all exits as per code.
Aug 28, 2014
Resolve - Class - 2
Fuel oil tank room - rear right side (possible water) penetration of liquid down wall and at flr. remedy: maintain oil tank room as per code.
Apr 29, 2013
Resolve - Class - 2
- stair 6 exit b - debris, nurses tables, windows, chain link fence. -exit 11 room b-1, sprinkler room - storage partially blocking egress @these areas. remedy: maintain all exits as per code.
Apr 29, 2013
Resolve - Class - 2
1st flr girls and boys bathroom piping (plumb) leaking into boiler room. remedy: repair/replace pipes as per code.
Apr 29, 2013
Resolve - Class - 2
Cellar - combustible material in corridors, b-8, b-11, books, clothingcardboard boxes, storage. remedy: maintain cellar as per code.
Apr 29, 2013
Resolve - Class - 2
Interior door hardware not self-closing - t-1, t-2, t-3, t-4. remedy: repair/replace.
Apr 29, 2013
Resolve - Class - 3
Reissue 34957746z. roof chimney - north & west exp vertical cracks. remedy: maintain bldg as per code.
Apr 29, 2013
Resolve - Class - 2
Exterior ramps and stairs rotting out - material: wood. remedy: maintain exterior bldg walls or appurtenances - exterior.
Apr 29, 2013
Resolve - Class - 2
Fire stopping missing at gas meter room conduit pipe penetration to exit 11 vestibule. remedy: provide fire stopping.
Apr 27, 2012
Resolve - Class - 1
Misc. furniture, file cabinets, etc: obstructions in stair enclosures & public corridors. at: basement public corridor and exit 11 vestibule. at: stair a (exit 9) stair. at: 2nd story public corridors, inside
Apr 27, 2012
Resolve - Class - 3
Re-issue #34926825p cracked brick chimney at roof chimney cracked vertically north & west exposures. remedy: repair defects noted.
Apr 27, 2012
Resolve - Class - 2
Re-issue #34921899p water penetrating foundation walls at basement boiler room pit area. remedy: repair defect noted maintain water proof integrity of foundation.
Apr 27, 2012
Resolve - Class - 3
Floor buckling at transportable classroom t3 near near entry door. remedy: repair floor.
Aug 4, 2011
Resolve - Class - 2
Doors not closing. at 3rd story hallway smoke corridor doors,at 2nd story room 220,at 1st story auditorium stage exit door south. (2) stair 'a' @ 2nd floor. remedy: replace doors.
Aug 4, 2011
Resolve - Class - 3
Cracked brick chimney. vertical cracks approx 12 lf north & west exposures of chimney at roof level. remedy: repair chimney.
Aug 4, 2011
Resolve - Class - 2
Reissue #34861664z water penetration through foundation walls at boiler room pit area. remedy: provide water proofing for foundation walls.
Aug 4, 2011
Resolve