DOB building violations

37 DOB violations, newest first.

  • Construction other optional

    At time of inspection premise has been observed having general contractor withdrawn from application # x01062068 -i1. due to this withdrawal all work must stop immediately and new permit holder must be in place to ensure inspections occur as required by article 116 chapter 1 of the title 28 of the admin code.

    Nov 18, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Plumbing none

    P-plumbing none

    Jan 6, 1999

    Dob violation - active
  • Emergency none

    Egncy-emergency none

    Jul 17, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 17, 1993

    Dob violation - dismissed

ECB violations

The newest 50 of 67 ECB violations. The city keeps the complete history.

  • Class - 2

    Re-issue #35688885m. failure to maintain building in code-compliant manner. noted: interior fire-proof doors do not self-close properly at 3rd flr-staircase "c" and "d". 1st flr-staircase "c", exit "9"(interior

    May 4, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35720968p. exit door not self-closing. noted: exterior fire-proof doors do not self-close properly at exits "5" and "6" and exit "9". remedy: repair/replace door.

    May 4, 2026 · Penalty $1,562

    Active
  • Class - 2

    Re-issue #35720969r. failure to maintain building in code-compliant manner. no fire-stopping per bc 712.3; 27-345. noted: in electric meter room room, fire-stopping can not be applied around pipes because entra

    May 4, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: no firestoppingper bc 712.3; 27-345 at electrical room entrance door with with pipes penetrating no fire stopping. remedy: comply with code.

    Jul 18, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35688888h-exit door not self closing-at gym, and exit #9 doornot self-closing. remedy: comply with code.

    Jul 18, 2025 · Penalty $1,562

    Active
  • Class - 2

    Exit door not self-closing.noted:at gym,exit door and at exit#9 doors not self-closing.rem:repair/replace door.

    Sep 19, 2024 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:at cafeteria 3 emergency exit lighting and at auditorium one lighting

    Sep 19, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building wall(s)or appurtenances.noted:ceiling leak observed at classroom 401a,401b,401f due to defective roof.rem:make necessary repairs.

    Sep 19, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35663126k failure to maintain building in code-compliant manner.noted:approx.90% of all classroom doors do not close properly due todefective/missing hardware and are racked/out of plumb.rem:repair/repl

    Sep 19, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35665447k failure to maintain building in code-compliant manner.noted:at 4th floor,fireproof door self-closing door stair a,d at 3rdfloor stair d corridor door room 319 stair b at 2nd floor stair a,b,c,

    Sep 19, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35584312z.exit door not self-closing.noted observed at roof bulkhead stair a,exit door does not self-close.on 1st floor exit 5/6 left door leaf does not open at all.remedy:repair or replace door.

    Jun 23, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35584313k.failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc1006.1;27-381.noted observed existing emergency lights with battery back

    Jun 23, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35584314m.failure to maintain building in code compliant manner.noted observed fire proof self-closing doors on 4th floor stair a,d.3rd floor stair d,corridor door by room 319,stair b,2nd floor stair a,

    Jun 23, 2022 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.noted observed approx 90% of all wooden classroom doors throughout entire building do not self-close due to missing hardware and some doors are rack and out

    Jun 23, 2022 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.noted observed broken wire mesh gates at stair a between the 2nd and 3rd floor mid-landing.remedy:repair and/or replace.

    Jun 23, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35502116j failure to maintain bldg in code compliant manner: noted: observed on the 1st fl wooden smoke door 2nd fl stair b,c&d,3rd floor,b,c&d. all these doors were not closing properly. remedy: repair

    Jul 21, 2021 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35502117l failure to maintain bldg in code compliant manner: illumination for exits,exit exit discharges & public corridors per bc 1006.1;27-381. noted: observed at gymnasium 2 emergency lights were not

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35502118n exit door not self closing. noted: observed at staira roof bulkhead exit door not self closing. at 1st fk exit 5 & 6 left door,exit 9,all these doors are not closing properly,the doors are hit

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35502120m failure to maintain bldg in code compliant manner. noted: observed on the 4th fl room#401b ceiling & walls are damage due to water penetration. remedy: repair/replace.

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner:(interior)noted: observed spalling plaster & damage on ceiling in room 401b due to water penetration. remedy: repair &/or replace.

    Jul 10, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: observed kickstopsinstalled on wooden smoke doors by exit#1 & at kitchen's entrance/exit

    Jul 10, 2020 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing. noted: observed at roof,stair'a'roof bulkhead exit door not self closing,1st fl exit 5 & 6 left door not self closing properly door is stuck cant open easily,exit 9 door gets stuck &

    Jul 10, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: observed existing emergency lights w/battery power back-up at 3rd fl pac

    Jul 10, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: noted: observed at 3rd fl-fire proof self closing doors at stair b,c & d at 2nd fl-stair b,c & d are racked & not self closing properly,at 1st fl wooden smoke

    Jul 10, 2020 · Penalty $625

    Active
  • Class - 2

    Exit door not self-closing. noted: on first floor exit 3 and 4 the middle door is not closing properly. the door is hitting on the door frame. rmdy: repair/replace door.

    Jun 20, 2017

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner: noted: the emergency exit lights are not working throughout the building. rmdy: repair and/or replace.

    Jun 20, 2017

    Resolve
  • Class - 2

    Water damage to ceiling plaster.@ 4th fl room 401b.ceiling plaster spalling.rem:repair ceiling.

    Aug 28, 2014

    Resolve
  • Class - 2

    Doors not self closing.@ 1st fl main exit brass doors #1,9 & 2.doors racked & jams shut requiring extreme force to open.rem:repair/replace doors.

    Aug 28, 2014

    Resolve
  • Class - 2

    3rd flr left door not self-closing at gym. remedy: maintain bldg code.remedy: maintain bldg as per code.

    Apr 26, 2013

    Resolve
  • Class - 2

    Stair a - bulkhead roof door glass cracked (vision panel). remedy: maintain bldg as per code.

    Apr 26, 2013

    Resolve
  • Class - 2

    Reissue #34921895h terrazo floor cracked various locations throughout 1st story. remedy: repair defect noted.

    Apr 27, 2012

    Resolve
  • Class - 2

    Doors not closing.@ 4 story a,c,d,and e doors warped/racked not closing.rem:replace doors.

    Aug 3, 2011

    Resolve
  • Class - 2

    Terrazo flr cracked various locations through out 1 story main corridor.rem:replace terrazo.

    Aug 3, 2011

    Resolve
  • Class - 3

    Reissue#34861668x roof top ladder handrail support bracket weld broken above room 401a.rem:reattach hand rail to support bracket.

    Aug 3, 2011

    Resolve
  • Class - 2

    Failure to maintain observed: rooftop ladder above 401a, 401b handrail disconneted from ladder @ middle support bracket remedy: weld / reattach handrail to ladder

    Jun 25, 2010

    Resolve
  • Class - 2

    Failure to maintain observed : step cracking / missing mortar inner parapet wall above rms 401a, 401b remedy: maintain bldg

    Jun 25, 2010

    Resolve
  • Class - 2

    Failure to maintain observed: spalling plaster ceiling 401a, 401b remedy: maintain bldg

    Jun 25, 2010

    Resolve
  • Class - 2

    No fire-stopping applied in the electrical rm at cellar level between the pipe pentration and the wall leaving open gaps remedy:provide/maintain fire stopping

    Feb 13, 2009

    Resolve
  • Class - 2

    The plaster on the ceiling is spalling located in rm 401b on the 4th fl level remedy:repair/replace plaster on the ceiling

    Feb 13, 2009

    Resolve
  • Class - 2

    Corridor hallway is being used partially as a lounge area on the 2nd fl consisting of sofa chair and tables by rm 211 remedy:remove sofa chairs and tables from corridor hallway

    Feb 13, 2009

    Resolve
  • Non-hazardous

    Reissue 345769894 exterior foundation wall has become porous & allowing raw water coming into the bldg causing interior damages on cellar level boiler rm on north/west corner.remedy:water-proof exterior foundat

    Mar 20, 2008

    Resolve
  • Hazardous

    Reissue vi34445635r failure to provide panic hardware 1st fl corridor & door to auditorium vestible & adjacent exit has door knobs w/key lock.remedy:provide panic hardware at above locations

    Jun 20, 2007

    Resolve
  • Hazardous

    Reissue vi#34445634p plaster at following locations 4th fl ceiling of stwy 5-4 exposed wire ( )& rm 401a & 401b below n/w corner of roof.remedy:repair defects at above location.

    Jun 20, 2007

    Resolve
  • Hazardous

    Reissue vi#34445633n riain water leaks into cellar n/w corner walls (opp gas meter rm)in boiler rm.remedy:repair wall(stop leaks penetrationinto interior of bldg)

    Jun 20, 2007

    Resolve
  • Hazardous

    Reissue vi34445632l missing closers on both boiler room doors 4 auditorium doors.at main entrance door adjacent to auditorium stage doors tostwy 8 does not close freely.remedy:replace missing door closers at

    Jun 20, 2007

    Resolve
  • Hazardous

    1st flr corridor doors to auditoruim vestibule & adjacent exit open against flow of egress remedy:repair/replace defect

    May 24, 2006

    Resolve
  • Hazardous

    Failure to provide panic hardware where required by law noted:double,1st flr corridor drs to auditorium vestibule & adjacent exit have dr knobs w/clyinder locks & panic bars remedy:repair/replace doors

    May 24, 2006

    Resolve
  • Hazardous

    Collapsed cracked,bubbled water damaged plaster at following location:4thfl ceiling of stwy 5-4 w/exposed wire lathe rooms 401a & 401b belown/w crnr of roof remedy:repair source of leaks,repair/replace defects

    May 24, 2006

    Resolve
  • Hazardous

    Rain water, drainage leaks in cellar n/w crnr walls (opp.gas mtr rm),in boiler rm,e/elev. cellar wall, below auditorium at cellar level remedy:repair/replace drainage

    May 24, 2006

    Resolve
  • Hazardous

    Defective doors:missing closers on both boiler rm drs;4 auditoruim drsat main entrance do not shut by themselves;exit 7,1stfl vestibule drs adjacent to auditorium stage dr to stwy 8 does not close freely

    May 24, 2006

    Resolve