Violations at 456 White Plains Road

Bronx, NY 10473 · BBL 2-03478-0018 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

35 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 22, 2019

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2016 inspection/test

    Sep 15, 2017

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2015 inspection/test

    Dec 1, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 15, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 17, 2015

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 23, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 19, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 13, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 17, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 28, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 25, 2005

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 21, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 25, 2004

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 30, 2002

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    May 31, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - dismissed
  • Elevator elevatorrequired

    (51) restore elevator to service so a proper inspection may be made by an inspector from this dept

    Mar 3, 1989

    Dob violation - resolved

ECB violations

The newest 50 of 80 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: exit sign #s a1, a11, a23, b4, b6, b8, b12, b13, b20, b25,b29, c

    May 1, 2026 · Penalty $1,250

    Active
  • Class - 2

    Re-issue #35717274n. failure to maintain building in code-compliant manner. noted: interior fire-proof doors do not self-close properly at 4th flr-smoke door near rm #s-45, 44 and near staircase "c", staircase

    May 1, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35688907y-failure to maintain building in code-compliant manner. doors are not closing properly @ 4th fl. #48, 43, 44, 46, corridor444, 3rd floor 35, 2nd fl. 134, 217, stage right by 204, stair c by rm

    Jul 14, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35688908x-exit door not self-closing at 4th fl. smokedoors atstair g, 3 fl. stair c, and 1st floor main entrance. remedy: comply with code.

    Jul 14, 2025 · Penalty $625

    Resolve
  • Class - 2

    Reissue: 35688909h. failure to maintain building in code-compliant mannerr: door not self-closing at 4th floor corridors #444, 2nd floor corridor by #215, 1st floor smoke door by exit #3. also noted @ rm 217 gl

    Jul 14, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue #35673025k. failure to maintain building in code-compliant manner. at 4 floor corridor #444; 2fl. corridor by 215 and 217 glass missing and 1fl smoke by exit 3. remedy: repair and/or replace.

    Sep 16, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self-closing.at 4 fl smoke at stair g 3 fl stair c and 1fl main entrance doors are not closing properly.rem:repair/replace door.

    Sep 16, 2024 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35673028x failure to maintain building in code-compliant manner.at 4th floor 48,43,44,416,corridor 444,3 fl,35,2 fl corridor by 217 stage right by 209 and stair c by 21.rem:repair and/or replace.

    Sep 16, 2024 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner:illumination forexits,exit discharges & public corridors per bc 1006.1,27-381.note:observed at 2nd floor-auditorium has a exit that is not operational when

    May 8, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.note:observed atvarious locations of the occupied school building,fireproof self-closing doors(located at 4th floor-room#43,staircase c at 2nd floor-room#21

    May 8, 2023 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner:no firestopping per bc 712.3;27-345.note:observed at cellar level,electrical room has numerous open holes & conduit pipes penetrating the walls at various l

    May 8, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    Stair and/or floor identification signs missing and/or defective.note:observed at various locations staircase landings and/or corridors throughout the occupied school building.the location id signs are not prov

    May 8, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.note:observed at4th floor corridor-door frame#444 has a glass panel that is missing.at2nd floor corridor near room#215 & #217 has a glass panel that is miss

    May 8, 2023 · Penalty $625

    Resolve
  • Class - 2

    Emergency signs at elevator call station missing,defective or non-compiant with section requirements.note:observed at 4th & 2nd floor of theoccupied school building,the sign that provides staircase diagram/loca

    May 8, 2023 · Penalty $625

    Resolve
  • Class - 2

    Exit door not selfclosing.noted:observed exterior exit doors@exit2,3 dont selfclose properly due to doors rubbing on saddle,also doors are diff to push open.repair/replace door.

    Jun 17, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:no firestopping per bc712.3;27-345.noted:observed@electrical rm,conduit penetrating thru walls,holes&openings,in cmu block wall w/no firestopping provided.provid

    Jun 17, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:noted:observed@4fl-stairc,fpsc door missing wire mesh glass,@2fl-staircase3,staird,are missing wire mesh glass compromising fpsc doors smoke barrier.repair &or r

    Jun 17, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:noted:observed fireproof selfclosing doors@4fl staira,corridor by rm44,stairc,3fl-stairc,staird,corridor by rm24 by rm218a,stairb,by rm229,staird@1fl,staira,stai

    Jun 17, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner: illumination for exits, exit discharges and public corridors per bc 1006; 27-381. noted: lights not working when tested. unit 1-4,a6,a7,a10,a13,a14,a19,a

    Jun 19, 2017

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner: no fire stopping per bc 712.3,27-345 noted: gas meter room holes not fire stopper,switch gear room has holes above door and on wall that go through into th

    Jun 19, 2017

    Resolve
  • Class - 2

    Failure to matintain building in code compliant manner.doors not closing or working properly throughout all corridors on every floor. remedy:comply with notice of violation.

    Sep 21, 2015

    Resolve
  • Class - 2

    Water penetration/damage to ceiling.@ 3rd fl girls bathroom.rem:repair/replace ceiling.

    Aug 25, 2014

    Resolve
  • Class - 2

    Reissue #35016725l.sanitary stall partitions deteriorated missing supports brackets dislodged.3rd story girls bathroom.2nd story boys & girls bathroom.1st story boys bathroom.rem:repair/replace bathroom stall p

    Aug 25, 2014

    Resolve
  • Class - 2

    Reissue #35016726m.exit doors not self closing.cross corridor doors,not self-closing throughout.rem:maintain all doors as per code.

    Aug 25, 2014

    Resolve
  • Class - 2

    Reissue 34957730y exit doors not self closing. cross corridor doors, not self-closing throughout. remedy: maintain all doors as per code.

    Apr 22, 2013

    Resolve
  • Class - 2

    Reissue: 34957730y. failure to maintain bldg in code compliant manner.sanitary stall partitions deteriorated missing supports brackets dislodged. 3rd sty girls bathroom - 3rd sty girls bathroom - 2nd sty boys

    Apr 22, 2013

    Resolve
  • Class - 2

    Sanitary stall partitions deteriorated w/doors missing/support brackets cracked/dislodged/unsecured. at: 3rd story girls bathroom. 2nd storyboys & girls bathrooms. 1st story boys room. remedy: repair &/or repla

    Apr 26, 2012

    Resolve
  • Class - 2

    1'x 1' ceiling tile dislodged/loose in danger of falling. at 1st storystudent cafeteria various locations throughout. remedy: repair &/or replace ceiling.

    Apr 26, 2012

    Resolve
  • Class - 2

    Doors not closing at various locations throughout all levels/stairs/cross corridors. remedy: repair &/or replace doors.

    Apr 26, 2012

    Resolve
  • Class - 2

    Reissue #34921883k masonry wall cracked/bulging/displaced. at: west elecvation below boiler room vents. remedy: repair &/or replace defects noted.

    Apr 26, 2012

    Resolve
  • Class - 2

    Reissue #34921884m water penetrating building envelope at 2nd,3rd,4th stories south elevation at 2nd story north wall of gymnasium. remedy: repair &/or replace defect noted,maintain weatherproof integrity of

    Apr 26, 2012

    Resolve
  • Class - 3

    Exhaust ventilation fan motors not operating w/ missing belts & inoperative motors vent#25 & 26 @ roof.rem:replace belts/motors for forced ventilation units designated#25 & #26.

    Aug 2, 2011

    Resolve
  • Class - 2

    Water penetration/damage south elevation 2,3,4 stories along corridor walls/ceilings flrs 3 & 4 & @ north wall of gym through ceiling where 2 story roof set back joins main portion of school(4 story section).@

    Aug 2, 2011

    Resolve
  • Class - 2

    Masonry wall cracked/bulging/displaced west elevation below boiler room vents.rem:repair/replace wall.

    Aug 2, 2011

    Resolve
  • Class - 3

    Linoleum flooring curled @ seams cracked/deteriorating @ auditorium.rem:replace flr covering.

    Aug 2, 2011

    Resolve
  • Class - 2

    Reissue#34861651j.smoke corridor doors not closing throughout 3 & 4 story.rem:replace doors.

    Aug 2, 2011

    Resolve
  • Class - 2

    Failure to maintain observed : defective pivot hinges and / or closer on cross corridor doors near rms. 418a, 409, 427, 335, 340, 318, 317 225 remedy: maintain bldg

    Jun 22, 2010

    Resolve
  • Class - 2

    Failure to maintain adequate fire stopping observed : inadequate fire stopping around electrical conduits passing through demising wall electric to oil tank room. remedy: maintain fire stopping

    Jun 22, 2010

    Resolve
  • Class - 2

    Fireproof self closing door at staircase #3(c) is not closing properlyon the 1fl.noted:door hinge is defective.remedy:repair/repair door hinge.

    Feb 18, 2009

    Resolve
  • Class - 2

    No fire stopping provided at the electrical room at the cellar level noted:pipe penetration through the wall has open gaps between pipe & wall.remedy:provide/maintain fire stopping.

    Feb 18, 2009

    Resolve
  • Class - 2

    Reissue:34639749k. exterior brick column is vertically cracked at rooflevel by stair bulkhead #2 approximately 4'long.remedy:repair cracked brick column.

    Feb 18, 2009

    Resolve
  • Hazardous

    Reissue 345769974 cermaic tiles are cracked & missing located at stairway # 2 on the 1st fl & roof buckheads on northside the fan rm on the 4th fl has a vertical crack (5'long) remedy:repair all defect noted ab

    Mar 19, 2008

    Resolve
  • Hazardous

    Reissue 34576994z fire-proof self closing door in the boiler rm is missing the key set cylinder leavinga hole in the door on cellar level remedy:replace missing key set cylinder

    Mar 19, 2008

    Resolve
  • Hazardous

    Reissue 34576993r exit doors are not self closing located at staircase"c' on the 4th fl staircase "c" 3rd fl remedy:repair replace exit doors

    Mar 19, 2008

    Resolve
  • Hazardous

    Reissue 34576992p exterior door frame is rotten corroded located at exit "c" on the 1st fl level making exit door hard to open & close properly remedy:repair replace door frame

    Mar 19, 2008

    Resolve
  • Hazardous

    Reissue vi 34445606h. failure to maintain bldg interior corroded rusted metal stairway tread pan at following locations: exit 3 entry lobby exit 2 at stwy 2 (b), 1 fl stwy (c) 3 at 3 fl. remedy: repair/ replace

    Jun 22, 2007

    Resolve
  • Hazardous

    Reissue vi 34445607j. crack & spalling plaster at following locations 2 fl boys gym stwy b above doors 1 fl kitchen & hallway door plaster cover over w/ plexey glass in hallway 4 fl stwy c (3) 1" wide nr rm 428

    Jun 22, 2007

    Resolve
  • Hazardous

    Reissue vi #34445608l. cracked masonry spalled concrete fl & step at bulkhead 2 cracked ceramic partition tiles at stairway 2 1 fl exit partof wall missing covered w/ plywood sty c(3) 4 fl . vertical crack in

    Jun 22, 2007

    Resolve
  • Hazardous

    Reissue vi #34445609n. rusted corroded metal door jams at exit 3 & door is hard to open. remedy: replace door buck at above location.

    Jun 22, 2007

    Resolve
  • Hazardous

    Reissue vi 34445610k. no fire stopping in cmu wall around pipes in gasmeter room & in paint room. remedy: fill up holes w/ fire stopping at above location.

    Jun 22, 2007

    Resolve