Violations at 2195 Bathgate Avenue

Bronx, NY 10457 · BBL 2-03049-0037 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

30 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2020)

    Jun 20, 2021

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2019

    Jun 29, 2020

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 17, 1993

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 17, 1993

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 17, 1993

    Dob violation - dismissed

ECB violations

The newest 50 of 92 ECB violations. The city keeps the complete history.

  • Class - 2

    Reissue #35684930y daet of issue: 09/27/2024. failure to maintain building wall(s) or appurtenances at yard 2nd floor window section of bricks cracked above 4th and 5th floor wall cracked. exposure 1(front) cra

    May 20, 2026 · Penalty $6,250

    Active
  • Class - 2

    Reissue #35721552x date of issue: 07/29/2025. failure to maintain building in code-compliant manner. at the time of inspection observed and noted at the time of inspection fpse doors are not self-closing proper

    May 20, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35721553h date of issue: 07/29/2025. failure to maintain building in code-compliant manner. illumination for exits, exit dischargesand public corridors per bc 1006.1; 27-381. at the time of inspection

    May 20, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35721554j date of issue: 07/29/2025. exit doors not self-closing properly. at the time of inspection when tested at exot #7, 6, 4, 3, 2 and 1 were not properly self-closing. remedy: repair or replace a

    May 20, 2026 · Penalty $1,562

    Active
  • Class - 2

    Reissue #35721555l date of issue: 07/29/2025. failure to maintain building in code-compliant manner. at the time of inspection observed and noted spalling and crumbling plaster on wall at stairwell 'd' bulkhead

    May 20, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35721556n date of issue: 07/29/2025. failure to maintain building in code-compliant manner. at the time time of inspection observedand noted interior steel steps at stairwell "d" leading to exit-4 were

    May 20, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35721558r date of issue; 07/29/25. failure to maintain building in code-compliant manner. at the time of inspection observed and noted exp #4 retaining wall has spalled/missing areas of concrete along

    May 20, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted exp #4 retaining wall has spalled/missing areas of concrete along the top. remedy: repair and/or replace.

    Jul 29, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35684930y. failure to maintain building wall(s) or appurtenances. noted at exp #1 facade, cracked and spalling sections of limestone finish at scattered locations. also at expo #4 step cracks in brick

    Jul 29, 2025 · Penalty $6,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted interior steel steps at stairwell d, leading to exit #4, were heavilly corrodedwith large hole along step riser(4th from bottom). remedy: repair and/

    Jul 29, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted spalling and crumbling plaster on wall at stairwell d bulkhead and at exit #7 vestibule above the exit doors. remedy: repair and/or replace.

    Jul 29, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35684932h. exit door not self-closing. exterior doors at exit#7, 6, 4, 3, 2 and 1 were not properly self-closing when tested. remedy: repair/replace door.

    Jul 29, 2025 · Penalty $1,562

    Active
  • Class - 2

    Reissue #35684931x. failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted emergency lights not working when tested: (3)

    Jul 29, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35684933j. failure to maintain building in code-compliant manner. noted interior fpsc doors not closing properly at: 4th fl corridor smoke door by 404a, 3rd fl smoke door by 303, classroom doors #303 a

    Jul 29, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35663466r date of issue:07.12.2023 failure to maintain building in code-compliant manner at the time of inspection observed and noted at 5th floor stair b smoke by room 501,4th floor smoke by stair b at

    Sep 27, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35663467z date of issue:07.12.2023 exit door not self closing properly at the time of inspection at stair b 3rd floor one exit door stair b 5th fl one exit door & stair d 4th floor one exit door,at stai

    Sep 27, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue:35663469m date of issue:07.12.2023 failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.at the time of inspection noted

    Sep 27, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35663472n date of issue:07.12.2024 failure to maintain building wall(s)or appurtenances at yard 2nd floor window section of bricks.cracked above 4th & 5th floor wall cracked.rem:repair or replace window

    Sep 27, 2024 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35654779n failure to maintain building in code-compliant wall(s) or appurtenances. at yard 2 floor window section of bricks. cracked, above 4 & 5 wall cracked, exposure 1 (front) cracks in limestone ab

    Jul 12, 2023 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at 4 floor exit sign stair b by room 402, 3 floor exit sign by 302, 2fl

    Jul 12, 2023 · Penalty $625

    Active
  • Class - 2

    Exit door not self-closing. noted at doors 2,4,6,7 doors are rubbing and functioning properly remedy: repair/replace door

    Jul 12, 2023 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at 5 floor stair b smoke by room 501, 4 floor smoke by stair b at room 401, 402, 405, 3 floor, 302a, 303, 2 floor auditorium left main entrance doors

    Jul 12, 2023 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner all exits exter ior doors all frames rusted with holes at base of all frames.rem:repair and/or replace.

    May 26, 2022 · Penalty $625

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner.retaining wall between park and school on the 182 st sidewalk in disrapair cracking and parks missing.also retaining wall in schoolyard wall is cracked and

    May 26, 2022 · Penalty $1,250

    Resolve
  • Class - 3

    Feed line on rightside of boiler leaking above feed valve.

    Jan 12, 2022 · Penalty $500

    Resolve
  • Class - 2

    Reissue35500900y failure to maintain bldg wall(s) or appurtenances.noted:during insp observed@exp4 on 182ndst along sidewalk,wall has large vert&horiz step cracks approx10'-12'l on masonry wall.maintain exterio

    Jun 1, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Exit door not self closing. noted: exterior door exit 2 by staircase cnot self closing & defected. remedy: repair & or replace.

    Jun 22, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissue ecb#35442142l failure to maintain bldg walls or appurtenances.noted: at 12 street north west corner adjacent to sidewalk has a vertical crack seperating wall from school property. also by exit door 2 &

    Jun 22, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    Re-issue #34862246k.failure to maintain bld.wall(s)or appurtenances.noted@182 street n.w corner adjacent to side walk has a vertical crack separating wall from school property.re:maintain bld.walls

    Jul 9, 2019

    Resolve
  • Class - 2

    Re-issue #35261005m failure to maintain bldg in code compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.noted:none of the emergency lights were working when tested t

    May 3, 2018

    Resolve
  • Class - 2

    Re-issue #35261006y failure to maintain bldg wall(s) or appurtenances.noted:@exp#4 on 182 street north west corner,large crack in the masonry wall (vertical & horizontal) approx 10 feet long.rem:maintain exter

    May 3, 2018

    Resolve
  • Class - 2

    Re-issue #35261007x failure to maintain bldg in code-compliant manner:noted:@cellar level boiler room & gas meter room damage to wall due to water penetration throughout retaining wall.also bulkhead staircase (

    May 3, 2018

    Resolve
  • Class - 2

    Exit door not self-closing. noted: at 3rd floor room #305 and at 6th floor exit 4,5 and at 2nd floor exit 2,3, the doors have defective in the top hinge and closer.rmdy: comply with code/repair or replace.

    Jun 1, 2017

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at 1st floor, boys bathroom, missing ceramic tiles in the wall for area 4' x 4'. rmdy: comply with code/install a new tile.

    Jun 1, 2017

    Resolve
  • Class - 2

    Failure to maintain building in code-compliantmanner. at cellar level gas meter room, water damage to wall due to water penetration through retaining wall. also at bulkhead staircase (e) water damage to wall.

    Jun 1, 2017

    Resolve
  • Class - 2

    Reissue #35216557h for failure to maintain walls or appurtenances. noted at exp#4, 182nd north west corner, large cracks in the masonry wall (vertical and horizontal) apprx 10'long with spalling concrete.rmdy:

    Jun 1, 2017

    Resolve
  • Class - 2

    Reissue #35213819p for failure to maintain building in code-compliantmanner. lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1; 27-542. noted: defective emergency lights

    Jun 1, 2017

    Resolve
  • Class - 2

    Reissue: 35120524p issued 4-17-15 failure to maintain bldg in code cokmpliant manner(interior). noted: spalling & crumbling plaster surface at bulkhead walls. remedy: repair or/& replace.

    Oct 24, 2016

    Resolve
  • Class - 2

    Reissue: 35128026z issued 4-17-15 failure to maintain bldg in code compliant manner;lack of emergency lighting for exits,exit dischages & public corridors per bc1006.1;27-542. noted: defective emergency lightin

    Oct 24, 2016

    Resolve
  • Class - 2

    Reissue:(35128025r)level 4-14-15 failure to maintain bldg walls or appurtenances(exterior)noted: at exp#4,82nd northwest corner,corner of retaining wall large cracks(vertical & horizontal)approx 10'-0"length w/

    Oct 12, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. roof lights not working in operable. remedy: comply w/notice of violation.

    Apr 17, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner lack of emergency lighting. defective emergency lighting throughout bldg including p/a spaces,lights are in operable. remedy: comply w/notice of violation.

    Apr 17, 2015

    Resolve
  • Class - 2

    Reissue #35101642m failure to maintain bldg in code compliant manner. spalling & crumbling plaster surface at bulkhead walls. remedy: complyw/notice of violation.

    Apr 17, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg walls & or appurtenances cracked retaining wall at 182nd st side exposure#2 corner of wall has approx 10'ft vertical crack w/spalling concrete. remedy: comply w/notice of violation.

    Apr 14, 2015

    Resolve
  • Class - 2

    Spalling & crumbling plaster surface. at north bulkhead walls. remedy: repair plaster surfaces.

    Jun 25, 2014

    Resolve
  • Class - 2

    Service room storage. at electric meter service room, contractor supplies stored in service room -no active contractors. remedy: remove all items, maintain meter room storage free.

    Jun 25, 2014

    Resolve
  • Class - 2

    Re-issue # 35018357x. cracked retaining wall. at 182 street northwest corner of wall has approx 10' vertical crack with spalling concrete. remedy: repair retaining wall.

    Jun 25, 2014

    Resolve
  • Class - 2

    Re-issue # 35018358h. defective emergency lighting. throughout including p/a spaces, inoperable emergency lights with battery back up. remedy: repair &/or replace emergency lighting.

    Jun 25, 2014

    Resolve
  • Class - 2

    95% of emergency lighting inoperable at 2 flr auditorium, 1 floor gym,cafeteria. rmdy: repair/replace.

    May 31, 2013

    Resolve
  • Class - 2

    Reissue: 34987267z, 34926326k, 34862246k retaining wall along 182nd street northwest corner vertical crack, also coping stone on top of retaining wall spalling/breaking apart.rmdy: make safe.

    May 31, 2013

    Resolve